1-2. Outdoor unit
Type Inverter heat pump
Model name AOYG18KBTA3 AOYG24KBTA3
Power source 230 V 50 Hz
Available voltage range 198—264V
Standard combination of indoor unit Wall mounted
ASYG07KMCC ×3
Wall mounted
ASYG07KMCC
ASYG09KMCC ×2
Capacity
Cooling
Rated kW 5.4 6.8
Btu/h 18,400 23,200
Min.—Max. kW 1.8—7 1.8—8.5
Btu/h 6,100—23,800 6,100—29,000
Heating
Rated kW 6.8 8.0
Btu/h 23,200 27,300
Min.—Max. kW 2.0—8.0 2.0—9.2
Btu/h 6,800—27,300 6,800—31,400
Input power
Cooling Rated
kW
1.13 1.74
Max. 1.90 2.65
Heating Rated 1.39 1.82
Max. 1.85 2.35
Current Cooling Rated A5.1 7.7
Heating Rated 6.2 8.1
EER Cooling kW/kW 4.78 3.90
COP Heating 4.89 4.40
Starting current A 6.2 8.1
Maximum operating current *1A 12.0 14.5
Fan
Type × Q'ty Propeller × 1
Airflow rate Cooling m3/h 2,220 2,270
Heating 2,160 2,730
Motor output W 49 49
Sound pressure level *2Cooling dB (A) 46 48
Heating 49 53
Heat exchanger
Dimension (H x W x D) mm
Main1: 672 × 881 × 18.19
Main2: 672 × 851 × 18.19
Fin pitch 1.3
Rows × Stages Main1: 1 × 32
Main2: 1 × 32
Pipe type (Material) Copper tube
Fin type (Material) Aluminum
Compressor Type DC twin rotary
Motor output W 1,200
Refrigerant Type R32 (675)
Charge g 1,800
Refrigerant oil Type RmM68AF
Amount cm3550
Enclosure
Material Steel sheet
Color Beige
(Approximate color of Munsell 10YR 7.5/1.0 NN)
Dimensions
(H x W x D)
Net mm 716 × 820 × 315
Gross 890 × 1,027 × 445
Weight Net kg 46
Gross 55
Connection
pipe
Size Liquid mm (in) Ø6.35 (Ø1/4) × 3
Gas Ø9.52 (Ø3/8) × 3 Ø9.52 (Ø3/8) × 2, Ø12.70 (Ø1/2) × 1
Method Flare
Pre-charge length (Total)
m
30
Maximum length (Total) 50
Maximum length (Each) 25
Minimum length (Total) 10
Minimum length (Each) 2.5
Maximum height difference between outdoor
unit and each indoor units. 15
Maximum height difference between indoor
units. 10
Operation range Cooling °C -10 to 46
Heating -15 to 24
Drain hose Material PP
Tip diameter mm Ø13.0 (I.D.), Ø16.0 to Ø16.8 (O.D.)
NOTES:
• Specifications are based on the following conditions:
– Power source of specifications: 230 V
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
– Cooling: Indoor temperature of 27.0 °CDB/19.0 °CWB, and outdoor temperature of 35 °CDB/24.0 °CWB.
– Heating: Indoor temperature of 20.0 °CDB/15.0 °CWB, and outdoor temperature of 7.0 °CDB/6.0 °CWB.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• For other combination, refer to the combination table.
• The protective function might work when using it outside the operation range.
• This data is based on EN 14511 standard.