G21 Impact 40 User manual

HU PL
SK
DE
EN
CZ
Manual
DEHUMIDIFIER G21
Model Impact - 40


Thank you for purchasing our product!
Read this manual carefully prior to using the appliance.
Safety instructions
• Install this appliance on afirm level place to reduce vibration and noise.
• Do not place in water or other liquids.
• In order to prevent accidents, please do not use this dehumidifier if wires or other
connections are damaged.
• This appliance can be used by children aged from 8 years and above and people with
reduced physical, sensory or mental capabilities or lack of experience or knowledge if they
have been given supervision or instruction concerning the use of this appliance in asafe
way and understand the hazards invloved. Children shall not play with the appliance,
cleaning and user maintenance shall not be made by children without supervision.
• After you turn the appliance OFF, take the plug out of the socket.
• Indoors use only.
• Empty the water tank to prevent overflow and spill before restarting.
• Do not tilt as it may cause water leakage and damaging the appliance.
• Do not insert any hard objects into the appliance in case error and damage occur.
• If the supply cord is damaged, it must be replaced by aqualified person in order to avoid
any damage.
Warning:
• Do not place close to heating devices (flame or heaters, etc.).
• Do not turn OFF by pulling the power cord out of the socket.
• Do not use any flammable substances near this appliance.
• Do not clean with water, use adamp soft cloth.
• Do not wipe with chemical solvents, use anatural detergent.
• Do not tilt over 45°or place upside down.
Frequent questions
Why does the appliance store less water in the water tank in winter?
The temeprature is low and air is dry, not afault.
Why can’t the appliance run or stops running suddenly?
The water tank might be full of water or it is not installed properly – drain the water tank or re-install
it. The appliance might be in the „dehumidification mode“, the ambient temperature is lower or
higher than requested (it cannot be performed when the ambient temperatur eis < 5 °C or > 32 °C).
Why is hot air blown out from the air supply outlet?
The appliance extracts air in the room and the dehumidification unit cools the air. The
temperature decreases below the condensation point, the air condenses into water drops, which
fall into the water tank and the dehumidified air is heated by the temperature running unit. This
can reduce energy consumption and also accelerate dehumidification, therefore, hot air is blown
out, not afault.

Installation
• Please drain the water from the water tank before running the appliance.
• When the appliance is ON, please do not open doors and windows if possible since it can
save energy resources.
• When the dehumidifier is installed, acertain space must be reserved around the appliance.
The minimum distance above is 50 cm and 20 cm in any other direction, as shown in the
picture below.
• When big noise is found during operation of this dehumidifier:
• It is recommended to insert pads or damping rubber sheets below this appliance. It can
reduce the vibration and noise and can also reduce damaging wood floor or carpet (due to
vibrations or water leakage).
• Activated carbon filter
Filter frame
• Before turning the machine on, také down the filter frame and put the activated carbon in it.
(Clean and dry the filter and filter frame regularly.)
• Do not turn the machine on before the filter and filter frame are well assembled.
2
11
2
1
2
2
11
2
1
2
Components
Water tank
Water tank handle
Water tank cover
Wind blade
Humidity indicate light
Control panel
Front cover
Back cover

2
11
2
1
2
back side Handle
Filter frame
Drainage
Wrapping post
Wheel
Control panel with WIFI and water pump
Timer
24h timer setup, press this key to set on/off time of the dehumidifier. The setting range is 1-24h. If
you want to cancel the setting, press twice after confirming the time setting.
Dry key in dehumidifier
Press this key to start drying procedure in the appliance. This mode can prevent mold inside the
appliance due to dampness. The whole drying procedure nees approximately 1h to finish. Press
this button again to cancel the drying mode and to recover to running state beforehand.
Air speed
In AUTO or CONTINUOUS mode air speed, high and low can be circularly selected.
2
11
2
1
2
LED display
This figure displays room humidity. When humidity is set in AUTO mode, this figure shows the set
humidity and displays the set time in timer state, % represents percentage of humidity.
Humidity setting
Once this button is pressed, the humidity is displayed circularly in the range 30-80 % and the
humidity setting is only valid in AUTO mode.
Long press this button for 3 seconds to turn on/off the pump function.
Mode
During startup or timer setting, press this button to select desired mode. After choosing, the light
indicator of the selected mode is on. Long press the Mode button to activate the Child Lock –
repeat to unlock.
On/Off button
Press this button to turn the appliance on/off.

Operating methods
Setting the timer off
When the dehumidifier is running, press the TIMER button to adjust time from 1 to 24 hours.
Press the button once to increase the setting by 1 hour – after the set time exceeds 24 hours,
the figure returns back to 1 hour. The TIMER button can also be pressed at any time needed,
the time increases or decreases circularly. When the time expires, the appliance turns OFF
automatically. After the setting is completed, if the TIMER button does not act at all within
5seconds, the set time is confirmed. In timer off state the key lamp on the TIMER button is ON.
Setting of timer on
When the dehumidifer is in standby mode, the method for adjustment of setting time by the
TIMER button is the same as timer off. After the setting is completed, if the TIMER button does
not act at all within 5 seconds, the set time is confirmed. In timer off state the key lamp on the
TIMER button is ON and the set time is displayed on control panel.
AUTO mode
Select AUTO dehumidification. If the room humidity is higher than the set humidity by + 5 %, the
compressor will start and the fan will run at the set speed. If the room humidity is between +5%
or - 5% of the set humidity, the compressor and the fan will run at the set speed. If the room
humidity is lower than the set humidity by - 5%, then the compressor will stop but the fan will run
at the set speed. The default set humidity value is 50%.
CONTINUOUS mode
Select CONTINUOUS dehumidification, no matter how the relative humidity in the room is,
the compressor starts, the fan runs at high speed in default setting and the air speed can be
regulated via the air speed button.
DRYING function
Press the DRYING button to start the drying process. The appliance starts at HIGH air speed and
releases air continuously for 30 minutes. The appliance turns to run at LOW air speed and lasts
for 20 minutes.
To stop, press the DRYING button again to cancel the process and recover to the prior running
mode. Or, press the POWER button to stop the process and recover to standby mode.
Humidity indicate function
Press the humidity setting button and the mode button at the same time to turn ON/turn OFF
the humidity light indicator. When the machine works, the color of light belt on the front cover
will change with humidit level. Red color show humidity over 60 %, green color shows humidity
40-60 % and blue color shows less than 40 % humidity.
Pump function
Press the humidity setting for 3 seconds to turn on/off the pump function (connect the drainage
pipe before turning the on the pump function).
Air-swing function
Press the Timer button and the Drying button at the same time to start or end the Air-swing
function.
Water drainage
When the water tank is full, the full water icon on LCD display flashes (the compressor, fan and
negative ion will stop running), the buzzer sounds 10 times to remind the user till the water is
drained.

2
11
2
1
2
• Place both hands respectively at the side of the back cover side of the depression, gently
remove the water tank and open the tank cover on the right side of the body, then pour the
water from the gap between water tank and the cover.
• Close the tank cover and rotate the water tank handle down, then put the water tank gently
back in to restart the appliance.
Attention: when the water tank is full of water, please empty it. Before putting the water tank into
the dehumidifier, please confirm whether the floater rotates flexibly or not, then put it in position
using both hands.
2
11
2
1
2
Continuous drainage
If you don’t want to drain water from the water tank frequently, you can connect adrainage pipe:
When the pump funtion is off
• a. Connect adrainage pipe (with outer diameter 13 mm) on the back of this dehumidifier.
• b. Find agarden hose with standard thread with 26,98 mm outer diameter and 11,5 TPI
pitch
When the pump function is on
• Connect adrainage pipe (with inner diameter 5 mm) on the back of this dehumidifer (the
suggested drainage height is no more than 5 m).
Note:
• With water-containing plate clean function. If won’t use
it for along time, také down the water cover and clean
the dehumidifer.
• Before také down the water cover, use acup to hold
water to avoid leakage.

2
11
2
1
2
When the pump function is off
Find the position of water outlet, také down water cover, pull down the water plug.
Connect the pipe with 13 mm diameter/garden pipe.
Note:
The length of drainage pipe shall not be too long (suggest less than 60 cm), the end of drainage
pipe shall be lower than the outlet for at least 10 cm and keep it straightened out.
2
11
2
1
2
2) When the pump function is on
Find the position of water outlet, také down water
cover, pull down the water plug.
Connect the pipe with 5 mm diameter.
Connect the pipe before turning the pump
function on to prevent water leakage.
2
11
2
1
2

Maintenance
Precautions:
• Please disconnect the power plug before maintenance or repair to prevent electric shock.
• If the dehumidifier is not used for along time, please disconnect the power suply.
• Please do not clean the appliance‘s body with chemical solvents such as alcohol, gasoline
etc..
• Please clean the water tank and its cover
with soft cloth dipped in cold or warm water
at regular time to prevent mould inside the
dehumidifer.
2
11
2
1
2
• Wipe the surface of the appliance slightly
with wet cloth and do not use detergent
or abrasive in case the plastic surface is
damaged.
2
11
2
1
2
• Clean the washable PP strainer at least once
per two weeks with cold or warm water. Do
not use chemical solvents or hot water.
2
11
2
1
2

The English version of the manual is an exact translation of the original manufacturer‘sinstructions.
Images used in this manual are for illustrational purposes only and may differ from the actual product.
Symptoms Possible reason Solution
The dehumidifier does
not run.
• Power plug fell out. • Insert the plug into socket.
• Water tank full of water
or place dat incorrect
position.
• Drain the water tank and
place it back in correctly.
• The ambient temperatur
eis lower than 5 °C or
higher than 32 °C.
• Normal phenomenon.
The dehumidification
function is not effective.
• Room temperature or
humiditiy too low.
• In dry seasons the
dehumidification ability will
reduce.
• Air outlet and inlet
blocked.
• Clean up the object block the
air outlet and inlet.
Air is not blown out. • Air filter blocked. • Clean the air strainer.
Noise is abnormal
during operation.
• Appliance placed
improperly so that itis
inclined or unstable.
• Place the appliance on afirm
level place.
• Air strainer blocked. • Clean the air strainer.
• „Tittering“ sound. • The flowing sound of
refrigerant, anormal
phenomenon.
Water leakage • Connection of drainage
pipe becomes loose.
• Fasten drainage pipe.
• Drainage system is
blocked.
• Remove obstacles and
straighten out the waterpipe.
Frosting occurs • The ambient temperature
is low and itis in the state
of waiting to defrost.
• It is anormal phenomenon
and the appliance has the
automatic defrosting function.
Troubleshooting
Display code – Instruction
FL – The water tank is full
E1 – The coil sensor detects anomaly
E2 – The room temperature sensor detects anomaly
P1 – The unit is in the defrosting mode, normal
CL – The unit is in the internal drying state, normal
LC – Child lock on
My appliance Sous vide Akura
Choose the type of the
appliance you want to add
Connect to the WiFi
you want to add your
appliance to
Appliance connected!
You’re connected to the Mojewifina WiFi.
If you want to add the appliance to this
WiFi, click continue.
Otherwise, go to WiFi setting in your
smartphone and connect to desired WiFi.
The appliance Dehumidifier Impact is
ready to use. You can change the name
of your appliance now
Name of the appliance
Menu
Sous vide cookbook Air conditioning Envi 12 H
G21 Vitality Dehumidifier Impact
Instagram G21 Vitality
Manuals
Add appliance Back WiFi setting
Pairing the app with the device
G21 Smart Home app
Dehumidifier G21 Impact screen
Download the G21 Smart Home app from Google Play or App Store.
Click „Add
appliance“.
When switched on, the
lamella starts moving.
Turns on/off the
appliance after set
time.
Use to set desired
humidity.
Switching between „Auto“
and „Continuous“ mode.
When switched on, the
appliance start the self-
drying process.
Install drainage hose
prior to turning this
function on.
Turns on/off the
appliance on set time.
„Low“ low power
„High“ high power
Locks the appliance’s
control panel.
/ Lamella
/ Timer
/ Mode
/ Self-drying
/ Water drainage
Plans
Power
Humidity
/ Lock
Choose the
appliance.
Follow the
instructions on the
screen.
Name your
appliance and
click „Finish“
Current humidity
Continue Finish
Stop
Plans
Dehumidifier G21 Impact – Home
EN

My appliance Sous vide Akura
Choose the type of the
appliance you want to add
Connect to the WiFi
you want to add your
appliance to
Appliance connected!
You’re connected to the Mojewifina WiFi.
If you want to add the appliance to this
WiFi, click continue.
Otherwise, go to WiFi setting in your
smartphone and connect to desired WiFi.
The appliance Dehumidifier Impact is
ready to use. You can change the name
of your appliance now
Name of the appliance
Menu
Sous vide cookbook Air conditioning Envi 12 H
G21 Vitality Dehumidifier Impact
Instagram G21 Vitality
Manuals
Add appliance Back WiFi setting
Pairing the app with the device
G21 Smart Home app
Dehumidifier G21 Impact screen
Download the G21 Smart Home app from Google Play or App Store.
Click „Add
appliance“.
When switched on, the
lamella starts moving.
Turns on/off the
appliance after set
time.
Use to set desired
humidity.
Switching between „Auto“
and „Continuous“ mode.
When switched on, the
appliance start the self-
drying process.
Install drainage hose
prior to turning this
function on.
Turns on/off the
appliance on set time.
„Low“ low power
„High“ high power
Locks the appliance’s
control panel.
/ Lamella
/ Timer
/ Mode
/ Self-drying
/ Water drainage
Plans
Power
Humidity
/ Lock
Choose the
appliance.
Follow the
instructions on the
screen.
Name your
appliance and
click „Finish“
Current humidity
Continue Finish
Stop
Plans
Dehumidifier G21 Impact – Home
EN

Safety instructions for installing the device using the R290 refrigerant
gas
To avoid damage, place the unit in an upright position for at least 24 hours before initiation.
Make sure that the air outlet and air inlet are never blocked.
Only operate the unit on a horizontal surface to ensure no water leaks out.
Warnings
• Do not exceed impedance greeter than 0.236ohm in supply the appliance is connected to.
• Any person who is involved with working on or breaking into a refrigerant a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment authority.
• Remember the environment when disposing of packaging around the appliance and when the
appliance has reached its by date.
• A warning that the appliance shall be stored in a well-ventilated area where the size
corresponds to the room area as specified for operation.
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Information for spaces where refrigerant pipes are allowed, including statements
» that the installation of pipe-work shall be kept to a minimum;
» that pipe-work shall be protected from physical damage and, in the case of flammable
refrigerants, shall not be installed in an unventilated space;
» that compliance with national gas regulations shall be observed;
» that mechanical connections shall be accessible for maintenance purposes;
» that, for appliances containing flammable refrigerants, the minimum floor area of the room shall
be mentioned in the form of a table or a single figure without reference to a formula;
• A warning to keep any required ventilation openings clear of obstruction;
• A notice that servicing shall be performed only as recommended by the manufacturer;
• When the portable air conditioner or dehumidifier is turned on, the fan can work continuously
stable under normal conditions to provide the minimum air volume of 100m3/h even when the
compressor is closed due to the temperature controller.
• Use only implements recommended by the manufacturer for defrosting or cleaning
• Do not perforate any of the components in the refrigerant circuit. Refrigerant gas may be
odourless
• Use care when storing the appliance to prevent mechanical faults.
• Maintenance and repairs requiring the assistance of other qualified personnel must be carried
out under the supervision of specialists in the use of inflammable refrigerants.
CAUTION ON FIRE
READ THE MAUAL CAREFULLY BEFORE USING THE APPLIANCE
R290 refrigerant gas complies with European environmental directives.
Appliance shall be installed, operated and stored in a room with a floor area larger than 4 m2.

Additional warning for appliance with R290 refrigerant gas (refer to the rating plate
for the type of refrigerant gas used)
1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary
to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following
precaution shall be completed prior to conducting work on the system.
2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable
gas or vapour being present while the work is being performed.
3. General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work
being carried out. Work in confined spaces shall be avoided.
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to
ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the
leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-
sparking, adequately sealed or intrinsically safe.
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing any
pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or
explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during which refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the area around the
equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period that
the work is carried out.
8. Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service guidelines shall be followed.
If in doubt, consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
• the actual refrigerant charge is in accordance with the room size within which the refrigerant
containing parts are installed;
• the ventilation machinery and outlets are operating adequately and are not obstructed;
• if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
• marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
• refrigerating pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded or
are suitably protected against being so corroded.

1. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. If a fault exists that could compromise safety, then no electrical supply
shall be connected to the circuit until it is satisfactorily dealt with
Initial safety checks shall include:
• that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
• that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
• that there is continuity of earth bonding.
2. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a permanently operating
form of leak detection shall be located at the most critical point to warn of a potentially hazardous
situation.
Particular attention shall be paid to the following to ensure that by working on electrical components,
the casing is not altered in such a way that the level of protection is affected. This shall include
damage to cables, excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
Ensure that seals or sealing materials have not degraded to the point that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer’s specifications.
3. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this
will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence
of a flammable atmosphere.
Replace components only with parts specified by the manufacturer. Other parts may result in the
ignition of refrigerant in the atmosphere from a leak.
4. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
5. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
6. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional
procedures shall be used. However, for flammable refrigerants it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered to:
• remove refrigerant;
• purge the circuit with inert gas;
• evacuate;
• purge with inert gas;
• open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances

containing flammable refrigerants the system shall be purged with oxygen-free nitrogen to render
the appliance safe for flammable refrigerants. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be achieved by
breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working
pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This
process shall be repeated until no refrigerant is within the system. When the final oxygen-free
nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work
to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take
place.
Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that
ventilation is available.
1. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
• Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant
contained in them.
• Cylinders shall be kept in an appropriate position according to the instructions.
• Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The
system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak
test shall be carried out prior to leaving the site.
2. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerants are recovered
safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case
analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is
available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
» mechanical handling equipment is available, if required, for handling refrigerant cylinders;
» all personal protective equipment is available and being used correctly;
» the recovery process is supervised at all times by a competent person;
» recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
f) Start the recovery machine and operate in accordance with instructions.
g) Do not overfill cylinders (no more than 80 % volume liquid charge).
h) Do not exceed the maximum working pressure of the cylinder, even temporarily.
i) When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from site promptly and all isolation valves on the equi-
pment are closed off.

a) Recovered refrigerant shall not be charged into another refrigerating system unless it has been
cleaned and checked.
1. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that
there are labels on the equipment stating the equipment contains flammable refrigerant.
2. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total system
charge is available. All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be
complete with pressure-relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants
including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall be complete with leak-free disconnect
couplings and in good condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units
and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers.
Only electric heating to the compressor body shall be employed to accelerate this process. When
oil is drained from a system, it shall be carried out safely.

Danke, dass Sie unser Produkt gekauft haben!
Lesen Sie diese Anleitung vor der Verwendung sorgfältig durch.
Sicherheitshinweise
• Das Gerät muss auf einer ebenen und stabilen Oberfläche betrieben werden, um Vibrationen
und Geräusche zu vermeiden.
• Das Gerät darf nicht mit Wasser oder anderen Flüssigkeiten in Kontakt kommen.
• Verwenden Sie dieses Gerät nicht, wenn das Netzkabel oder die Schaltkreise beschädigt
sind. Es besteht Verletzungsgefahr.
• Dieses Gerät kann von Kindern ab 8 Jahren und Personen mit eingeschränkten physischen,
sensorischen oder geistigen Fähigkeiten oder Mangel an Erfahrung und Wissen verwendet
werden, sofern sie beaufsichtigt sind oder eingewiesen wurden und die Gefahren verstehen.
Kinder dürfen mit diesem Gerät nicht spielen. Reinigung und Wartung sollten nicht von
Kindern ohne Aufsicht durchgeführt werden.
• Trennen Sie das Gerät nach dem Ausschalten, vor dem Zurücksetzen und vor der Wartung
immer vom Netz.
• Dieses Gerät ist nur für den Innengebrauch bestimmt.
• Entleeren Sie den Wassertank, bevor Sie das Gerät wieder in Betrieb nehmen, um mögliches
Überfüllen zu vermeiden.
• Kippen Sie das Gerät nicht, um mögliche Schäden durch das Wasser aus dem Tank zu
vermeiden.
• Führen Sie keine harten Gegenstände in das Gerät ein. Es könnte so beschädigt werden.
• Wenn das Netzkabel beschädigt ist, muss es von einem Servicetechniker ausgetauscht
werden. Versuchen Sie niemals, das Kabel selbst auszutauschen oder es zu reparieren.
Hinweis:
• Stellen Sie das Gerät nicht in der Nähe von Wärmequellen (Heizkörper, Heizung, Herd usw.)
auf.
• Schalten Sie das Gerät niemals so aus, indem Sie es vom Netz trennen.
• Verwenden Sie keine brennbaren Substanzen in der Nähe des Geräts.
• Reinigen Sie das Gerät nicht mit Wasser. Verwenden Sie immer ein feuchtes und weiches
Tuch.
• Wischen Sie das Gerät nicht mit Chemikalien ab. Wenn das Gerät verschmutzt ist,
verwenden Sie ein neutrales Reinigungsmittel.
• Neigen Sie das Gerät nicht um mehr als 45° und stellen Sie es nie verkehrt um auf.
Häufige Fragen
Warum sammelt sich im Winter weniger Wasser im Wassertank?
Im Winter sind die Temperaturen niedrig und die Luft ist trocken, sodass das Gerät weniger
Feuchtigkeit aufnimmt als im Sommer.
Warum kann das Gerät nicht eingeschaltet werden oder schaltet sich gleich von selbst aus?
Der Wassertank ist möglicherweise voll oder falsch positioniert. Entleeren Sie den Wassertank
oder stellen Sie diesen in die richtige Position. Die Außentemperaturen reichen möglicherweise für
die ordnungsgemäße Funktion des Geräts nicht aus. Das Gerät wird nicht funktionieren, wenn die
Temperaturen unter 5°C oder über 32°C liegen. (Der optimale Nutzungsbereich ist von 16-32°C.)

Warum bläst heiße Luft aus dem Lufteinlass?
Das Gerät saugt die Raumluft ab und die Entfeuchtungseinheit kühlt sie ab, die Temperatur sinkt
unter den Kondensationspunkt, die Luft kondensiert zu Wassertröpfchen, die schließlich in den
Wassertank fallen. Danach wird die entfeuchtete Luft wieder auf die ursprüngliche Temperatur
erwärmt. Dies kann den Energieverbrauch senken und auch die Entfeuchtung beschleunigen,
sodass heiße Luft ausgeblasen wird. Es handelt sich nicht um eine Fehlfunktion.
Installation des Gerätes
• Lassen Sie das Wasser aus dem Wassertank ab, bevor Sie das Gerät starten.
• Öffnen Sie bei eingeschaltetem Gerät möglichst keine Türen und Fenster - dies kann
Energieressourcen sparen.
• Wenn der Luftentfeuchter installiert ist, muss um das Gerät herum folgend Platz freigehalten
werden: über dem Gerät 50 cm und 20 cm in jede andere Richtung, wie in der Abbildung
unten gezeigt.
• Wenn während des Betriebs dieses Luftentfeuchters laute Geräusche festgestellt werden:
• Es wird empfohlen, Pads oder Dämpfungsgummi unter dieses Gerät zu legen. Dies kann
Vibrationen und Geräusche reduzieren und auch Schäden an Holzböden oder Teppich
(aufgrund von Vibrationen oder Wasserlecks) reduzieren.
2
11
2
1
2
2
11
2
1
2
Gerätbeschreibung
Wassertank
Griff des Wassertanks
Deckel des Wassertanks
Regulierungsgitter
Feuchtigkeitsanzeige
Schalttafel
Abdeckung vorn
Abdeckung hinten

2
11
2
1
2
Rückseite Griff
Filterrahmen
Wasserauslass
Kabelhalterung
Räder
Schalttafel
Zeiteinstellung
Drücken Sie diese Taste, um die Betriebsdauer des Luftentfeuchters einzustellen. Der
Einstellbereich beträgt 0-24 Stunden – jeder Tastendruck erhöht die Zeit um 1 Stunde. Halten Sie
gedrückt, um die Einstellung abzubrechen.
Funktion zum Trocknen der Innenteile des Gerätes
Drücken Sie diese Taste, um den Prozess des Trocknens des Geräts zu starten. Dadurch kann
die Bildung von Schimmel aufgrund der feuchten Umgebung im Inneren des Geräts verhindert
werden. Der gesamte Trocknungsvorgang dauert etwa eine Stunde. Drücken Sie diese Taste
erneut, um diese Funktion abzubrechen und das zuvor laufende Programm wiederherzustellen.
2
11
2
1
2
Luftzirkulationsgeschwindigkeit
Im AUTO oder CONTINUOUS Modus kann die Luftgeschwindigkeit HIGH (hoch) oder LOW
(niedrig) gewählt werden.
LED-Anzeige
Zeigt die Raumfeuchtigkeit in den Modi AUTO, CONTINUOUS und TROCKNEN an. Im AUTO-
Modus wird die prozentuale Luftfeuchtigkeit angezeigt und die eingestellte Zeit angezeigt.
Feuchtigkeitseinstellung
Durch das Drücken dieser Taste wird die Luftfeuchtigkeit im Bereich von 30% - 80% angezeigt.
Die Feuchtigkeitseinstellung ist nur im AUTO-Modus gültig.
Modus
Wählen Sie beim Einschalten des Geräts oder beim Starten des Timers den gewünschten Modus
(AUTO/CONTINUOUS) durch Drücken dieser Taste - die dem Modus entsprechende Anzeige
leuchtet auf. Kindersicherung: Drücken Sie während des Betriebs die MODE-Taste länger als
3 Sekunden. Wenn die Kindersicherung aktiviert ist, funktioniert keine Taste. Drücken Sie zum
Entsperren erneut die MODE-Taste für 3 Sekunden.
ON/OFF Taste
Durch diese Taste wird das Gerät ein-, oder ausgeschaltet

Arbeitsmethoden
Automatisches Ausschalten des Gerätes durch einen Timer
Wenn der Luftentfeuchter in Betrieb ist, drücken Sie die TIMER-Taste, um die Betriebsdauer
von 1 bis 24 Stunden einzustellen. Mit einem Tastendruck erhöhen Sie die Einstellung um
1Stunde - nach der eingestellten Dauer von 24 Stunden kehrt der Wert auf 1 Stunde zurück.
Nach Ablauf der gewählten Zeit schaltet sich das Gerät automatisch ab. Nach Auswahl der
gewünschten Betriebsdauer wird der gewählte Wert nach 5 Sekunden gespeichert. Wenn der
Timer ausgeschaltet ist, leuchtet die Kontrollleuchte der TIMER-Taste.
Automatisches Einschalten des Geräts über einen Timer
Wenn sich der Luftentfeuchter im Standby-Modus befindet, ist der Vorgang zum Bestimmen
der Betriebsdauer mit der TIMER-Taste derselbe wie beim Ausschalten des Timers. Wenn nach
Abschluss der Einstellung die TIMER-Taste innerhalb von 5 Sekunden nicht funktioniert, ist die
eingestellte Zeit bestätigt. Wenn der Timer ausgeschaltet ist, leuchtet die Kontrollleuchte der
TIMER-Taste und die eingestellte Zeit wird angezeigt.
AUTO Modus
Wählen Sie den AUTO-Modus. Ist die Luftfeuchtigkeit im Raum um + 5 %, höher als die
eingestellte Luftfeuchtigkeit, schaltet sich der Kompressor ein und der Ventilator läuft mit der
bereits eingestellten Drehzahl. Liegt die Luftfeuchtigkeit im Raum zwischen + 5 % oder – 5 %
der eingestellten Luftfeuchtigkeit, laufen der Kompressor und der Ventilator mit der eingestellten
Geschwindigkeit. Wenn die Luftfeuchtigkeit im Raum um -5 % unter der eingestellten
Luftfeuchtigkeit liegt, schaltet sich der Kompressor aus, der Ventilator läuft jedoch mit der
eingestellten Drehzahl weiter. Die Standardeinstellung der Luftfeuchtigkeit beträgt 50 %.
CONTINUOUS Modus
Wählen Sie die KONTINUIERLICHE Entfeuchtung aus. Unabhängig von der relativen
Luftfeuchtigkeit im Raum schaltet sich der Kompressor ein, der Ventilator läuft standardmäßig
mit hoher Geschwindigkeit und die Luftgeschwindigkeit kann durch die zuständige Taste reguliert
werden.
Trocknungsfunktion der Innenteile des Geräts
Drücken Sie die Taste TROCKNEN, um den Vorgang zu starten. Das Gerät startet mit HOHER
Luftgeschwindigkeit und bläst für 30 Minuten lang kontinuierlich Luft aus. Das Gerät schaltet
dann für 15 Minuten auf NIEDRIGE Luftgeschwindigkeit um. Um den Vorgang zu stoppen,
drücken Sie erneut die Taste TROCKNEN. Der vorherigen Betriebsmodus wird erneut gestartet.
Durch das Drücken des Netzschalters wird der Vorgang gestoppt und der Standby-Modus
fortgesetzt.
Feuchtigkeitsindikator
Drücken Sie gleichzeitig die Taste zur Einstellung der Feuchtigkeit und die Modustaste, um
die Feuchtigkeitsanzeigeleuchte ein-/auszuschalten. Wenn das Gerät läuft, ändert sich die
Farbe des Leuchtstreifens auf der Frontabdeckung gemäß der Luftfeuchtigkeit. Rot zeigt eine
Luftfeuchtigkeit über 60% an, grün bedeutet eine Luftfeuchtigkeit von 40-60 % und blau zeigt
eine Luftfeuchtigkeit unter 40 % an.
Pumpenfunktion
Drücken Sie die Taste zur Einstellung der Feuchtigkeit für 3 Sekunden, um die Pumpenfunktion
ein-/auszuschalten (schließen Sie den Ablaufschlauch vor dem Einschalten der Pumpenfunktion
an).
Table of contents
Languages:
Other G21 Dehumidifier manuals