Gamewell GF505 Series User manual

0
GAMEWELL-FCI
12 CLINTONVILLE ROAD
NORTHFORD, CT 06472
GF505 & GF510 Series
FIRE ALARM CONTROL PANELS
INSTALLATION, PROGRAMMING & OPERATION MANUAL
P/N: 53164 Rev. A
03/26/07 ECN 07-129

PrecauLarge.PMD 02/26/2007
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise follow-
ing the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These docu-
ments can be found at http:/www.systemsensor.com/html/
applicat.html. A study by the Federal Emergency Manage-
ment Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens-
ing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flam-
ing fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently con-
sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmis-
sion systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the require-
ments of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Fire Alarm System Limitations

PrecauLarge.PMD 02/26/2007
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso-
ciated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F and at a relative humidity of
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room tempera-
ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
FCC Warning
Installation Precautions

Table of Contents
4GF505 & GF510 P/N: 53164:A 03/26/07
SECTION 1: Product Description .........................................................................................................................12
1.1: Product Features..........................................................................................................................................12
1.2: Specifications ..............................................................................................................................................13
1.3: Controls and Indicators................................................................................................................................15
1.4: Digital Alarm Communicator/Transmitter..................................................................................................17
1.5: Components.................................................................................................................................................17
1.6: Optional Modules and Accessories.............................................................................................................17
1.7: Telephone Requirements and Warnings ......................................................................................................19
1.7.1: Telephone Circuitry...........................................................................................................................19
1.7.2: Digital Communicator.......................................................................................................................19
1.7.3: Telephone Company Rights and Warnings.......................................................................................20
SECTION 2: Installation ........................................................................................................................................21
2.1: Backbox Mounting......................................................................................................................................21
2.2: Operating Power..........................................................................................................................................24
2.3: Input Circuits...............................................................................................................................................25
2.4: Output Circuits ............................................................................................................................................27
2.4.1: Notification Appliance Circuits ........................................................................................................27
2.4.2: Special Application DC Power Output Connections ........................................................................28
2.4.3: Relays - Programmable.....................................................................................................................28
2.4.4: Remote Synchronization Output.......................................................................................................29
2.5: Power-limited Wiring Requirements...........................................................................................................30
2.6: Digital Communicator.................................................................................................................................31
2.7: Installation of Optional Modules.................................................................................................................32
2.7.1: CAC-5X Class A Converter Module ................................................................................................32
2.7.1.1 Installation ...............................................................................................................................32
2.7.1.2 Wiring NACs and IDCs for Class A .......................................................................................33
2.7.2: 4XTMF Option Module....................................................................................................................34
2.7.2.1 4XTMF Transmitter Module Installation ................................................................................35
2.8: ANN-BUS Devices .....................................................................................................................................36
2.8.1: ANN-BUS Wiring.............................................................................................................................36
2.8.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................36
2.8.1.2 Wiring Configuration ..............................................................................................................38
2.8.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................39
2.8.2: ANN-BUS Device Addressing..........................................................................................................39
2.8.3: GFANN-80 Remote Fire Annunciator..............................................................................................40
2.8.4: Specifications....................................................................................................................................40
2.8.5: Installation.........................................................................................................................................40
2.8.5.1 Mounting .................................................................................................................................40
2.8.5.2 Opening/Closing Annunciator ................................................................................................40
2.8.5.3 Wiring GFANN-80 to FACP ..................................................................................................41
2.8.6: GFANN-S/PG Serial/Parallel Printer Interface Installation..............................................................43
2.8.6.1 Specifications ..........................................................................................................................43
2.8.6.2 PRN Printer Installation ..........................................................................................................43
2.8.6.2.1 Connecting PRN Printer .......................................................................................................44
2.8.6.2.2 Setting Printer Options .........................................................................................................44
2.8.7: GFANN-I/O LED Driver Module.....................................................................................................45
2.8.7.1 GFANN-I/O Board Layout .....................................................................................................45
2.8.7.2 Specifications ..........................................................................................................................45
2.8.7.3 GFANN-I/O Connection to FACP ..........................................................................................46
2.8.7.4 GFANN-I/O Module LED Wiring ..........................................................................................47
2.8.8: GFANN-LED Annunciator Module..................................................................................................48
2.8.8.1 GFANN-LED Board Layout ...................................................................................................48
2.8.8.2 Specifications ..........................................................................................................................48
2.8.8.3 Mounting/Installation ..............................................................................................................48
2.8.8.4 GFANN-LED Connection to FACP .......................................................................................49
Table of Contents

GF505 & GF510 P/N: 53164:A 03/26/07 5
Table of Contents
2.8.9: GFANN-RLY Relay Module.............................................................................................................50
2.8.9.1 GFANN-RLY Board Layout ..................................................................................................50
2.8.9.2 Specifications ..........................................................................................................................50
2.8.9.3 Mounting/Installation ..............................................................................................................50
2.8.9.4 GFANN-RLY Connection to FACP .......................................................................................51
SECTION 3: Programming ..................................................................................................................................52
3.1: User Programming ......................................................................................................................................52
3.2: Initial Power-up...........................................................................................................................................53
3.3: Programming Screens Description..............................................................................................................53
3.4: Programming and Passwords ......................................................................................................................53
3.5: Master Programming Level.........................................................................................................................55
3.5.1: Input Zones........................................................................................................................................56
3.5.2: NAC (Notification Appliance Circuit)..............................................................................................63
3.5.2.1 Enabled ....................................................................................................................................64
3.5.2.2 NAC Coding ...........................................................................................................................64
3.5.2.2.1 Two Stage Operation ...........................................................................................................65
3.5.2.2.2 Synchronized NAC Operation .............................................................................................65
3.5.2.3 Silence .....................................................................................................................................66
3.5.2.4 Auto Silence ............................................................................................................................67
3.5.2.5 Silence Inhibited .....................................................................................................................67
3.5.3: Relays................................................................................................................................................67
3.5.4: System Setup.....................................................................................................................................69
3.5.4.1 Timers .....................................................................................................................................70
3.5.4.1.1 PAS (Positive Alarm Sequence) Delay ................................................................................70
3.5.4.1.2 Pre-signal Delay ...................................................................................................................70
3.5.4.1.3 Waterflow Delay ..................................................................................................................71
3.5.4.1.4 AC Loss Delay .....................................................................................................................71
3.5.4.2 Banner .....................................................................................................................................72
3.5.4.3 Time-Date ...............................................................................................................................73
3.5.4.3.1 Time .....................................................................................................................................73
3.5.4.3.2 Date ......................................................................................................................................74
3.5.4.3.3 Clock Format ........................................................................................................................74
3.5.4.3.4 Daylight Savings Time .........................................................................................................74
3.5.4.4 Trouble Reminder ...................................................................................................................75
3.5.4.5 Charger Disable .......................................................................................................................75
3.5.5: Option Modules................................................................................................................................75
3.5.5.1 ANN-BUS ...............................................................................................................................76
3.5.5.1.1 ANN-BUS Enabled ..............................................................................................................76
3.5.5.1.2 BUS Modules .......................................................................................................................76
3.5.5.1.3 Auto-Configure ....................................................................................................................77
3.5.5.1.4 ANN-S/PG Options Screen ..................................................................................................78
3.5.5.1.5 GFANN-I/O LED Zone Assignments ..................................................................................79
3.5.5.1.6 ANN-80 Options Screen ......................................................................................................80
3.5.5.2 ANN-RLY Options Screen .....................................................................................................81
3.5.5.3 Onboard DACT .......................................................................................................................82
3.5.5.3.1 Primary Phone ......................................................................................................................82
3.5.5.3.2 Secondary Phone ..................................................................................................................83
3.5.5.3.3 Central Station ......................................................................................................................83
3.5.6: History...............................................................................................................................................95
3.5.6.1 View Events ............................................................................................................................95
3.5.6.2 Erase History ...........................................................................................................................95
3.5.7: Walktest.............................................................................................................................................96
3.5.8: Clear Program ...................................................................................................................................97
3.5.9: Password Change..............................................................................................................................97
3.6: Maintenance Programming Level...............................................................................................................98

Table of Contents
6GF505 & GF510 P/N: 53164:A 03/26/07
3.6.1: Input Zones - Enable/Disable............................................................................................................99
3.6.2: History...............................................................................................................................................99
3.6.3: Walktest.............................................................................................................................................100
3.6.4: Time-Date..........................................................................................................................................101
SECTION 4: Operating Instructions ....................................................................................................................102
4.1: Panel Control Buttons..................................................................................................................................102
4.1.1: Acknowledge/Step.............................................................................................................................102
4.1.2: Alarm Silenced..................................................................................................................................102
4.1.3: Drill/Hold 2 Sec ................................................................................................................................102
4.1.4: Reset..................................................................................................................................................102
4.2: LED Indicators ............................................................................................................................................103
4.3: Normal Operation........................................................................................................................................103
4.4: Trouble Operation........................................................................................................................................104
4.5: Alarm Operation..........................................................................................................................................105
4.6: Supervisory Operation.................................................................................................................................106
4.7: Process Monitor Operation..........................................................................................................................107
4.8: Hazard/Tornado Condition Operation.........................................................................................................107
4.9: Medical Alert Condition Operation.............................................................................................................107
4.10: Disable/Enable Operation..........................................................................................................................108
4.11: Waterflow Circuits Operation....................................................................................................................108
4.12: Detector Functions.....................................................................................................................................108
4.13: Time Functions: Real-Time Clock ............................................................................................................108
4.14: Coded Operation........................................................................................................................................108
4.15: Presignal....................................................................................................................................................109
4.16: Positive Alarm Sequence...........................................................................................................................109
4.17: Special System Timers ..............................................................................................................................110
4.17.1: Silence Inhibit Timer.......................................................................................................................110
4.17.2: Autosilence Timer...........................................................................................................................110
4.17.3: Trouble Reminder............................................................................................................................110
4.17.4: Waterflow Retard Timer..................................................................................................................110
4.17.5: Alarm Verification (None or One Minute)......................................................................................111
4.18: Walktest .....................................................................................................................................................111
4.19: Read Status................................................................................................................................................112
4.19.1: Input Zones......................................................................................................................................113
4.19.2: NAC ................................................................................................................................................113
4.19.3: Relays..............................................................................................................................................114
4.19.4: System Settings ...............................................................................................................................114
4.19.5: Timers..............................................................................................................................................115
4.19.6: Daylight Savings.............................................................................................................................115
4.19.7: History.............................................................................................................................................116
4.19.8: Print.................................................................................................................................................116
4.19.9: ANN-BUS.......................................................................................................................................117
4.19.10: Central Station...............................................................................................................................118
4.19.11: Phone Line.....................................................................................................................................118
SECTION 5: Central Station Communications ...................................................................................................119
5.1: Transmittal Priorities...................................................................................................................................120
SECTION 6: Power Supply Calculations .............................................................................................................122
6.1: Overview .....................................................................................................................................................122
6.2: Calculating the AC Branch Circuit..............................................................................................................122
6.3: Calculating the System Current Draw.........................................................................................................123
6.3.1: Overview...........................................................................................................................................123
6.3.2: How to Use Table 6-3 on page 124 to Calculate System Current Draw...........................................123
6.4: Calculating the Battery Size........................................................................................................................125
6.4.1: NFPA Battery Requirements.............................................................................................................125

GF505 & GF510 P/N: 53164:A 03/26/07 7
Table of Contents
6.4.2: Selecting and Locating Batteries.......................................................................................................125
APPENDIX A: Ademco Contact ID Format
...................................................................................................................................................................................
Event Code Descriptions ........................................................................................................................................126
A.1: Transmission Format Between DACT and Receiver ................................................................................126
A.2: Ademco Contact ID Typical Printout ........................................................................................................126
APPENDIX B: NFPA Standard-Specific Requirements ...................................................................................131
B.1: Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts ...........................................................................................................137
APPENDIX C: FACP with Keltron .....................................................................................................................138

Notes
8GF505 & GF510 Series PN 53164:A 3/26/2007

GF505 & GF510 Series PN 53164:A 3/26/2007 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standards
• NFPA 72 National Fire Alarm Code
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Gamewell-FCI Documents
Gamewell-FCI Device Compatibility Document Document #52195
411UD Manual Document #50759
411UDAC Manual Document #51073
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
Before proceeding, the installer should be familiar with the following documents.

10 GF505 & GF510 Series PN 53164:A 3/26/2007
GF505 Series Main Circuit Board
DACT Phone Line Jacks
(Nonpower-Limited)
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Special Application Power
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
NC position during
trouble conditionsand
under loss of all power.
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Battery (see note 3)
Basic System Connections
5-Zone Panel
Notification Appliance Circuits (see note 1)
3 Programmable Relays
Alarm* Trouble* Supervisory*
NO NC C
24 VDC, supervised,
nonpower-limited
NO NC CNO NC C NO NC C
(* )Factory default relay programming
Power Supply Connector J15
NAC #1
+
+
+
4
3
FIRE ALARM
AC POWER
TROUBLE
1
4
7
*
231
56
89
0#
ABC DEF
GHI JKL
PRS TUV
QZ_ _/.
CLEAR
ESC
MODE
ST
ENTER
ALARM
DRILL RESET
J12
BATTERY
- +
TB5 TB4 TB8
TB9
J2
J15
J3
JP24
JP31
JP30
J5
J4
J6
J8 J9
TB3
GND PWR
ANN-BUS
A B
RST AUX
PWR
RST/NONRST
AUXPWR
OUT1 OUT2
4XTMF OPT BD
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
2
1
JP43
Class A Converter Module
-
+
+
-
3
2
1
NAC #2
+
+
+
B
+B
-
11
B
+B
-
22
B
+B
-
11
Initiating Device Circuits
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
+
+
+
TB5/
TB7
TB4/
TB6
OUT1/3 OUT2/4
B
+B
-
11 2
B
+B
-
11
OUT OUT
TB2 TB1
J2
Class AConverter Module
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
Style Z (Class A) NAC
Style D (ClassA) IDC
+ - + - + - + - + - + - + -
Important!
Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
- +
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
TB2
Remote
Synchronization
Output (see note 2)
Special Application Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires ELR.4.7K
Primary Phone
Active LED Secondary Phone
Active LED
Primary Secondary
Kiss-off LED
- +
NAC #3
+
+
+
TB7
OUT3 OUT4
NAC #4
+
+
+
B
+B
-
11
B
+B
-
22
+ - + -
J7
Notes:
1. GF505= 3 amps max. per NAC
2. 26 Amp Hour max. for GF505

GF505 & GF510 Series PN 53164:A 3/26/2007 11
GF510 Series Main Circuit Board
DACT Phone Line Jacks
(Nonpower-Limited)
e
settable Power - 24 VDC filtered,
wer-limited (0.500 amps maximum)
smoke detectors (IDC).
u
pervision required.
nresettable or Resettable Power
m
per selectable by JP31, 24 VDC filtered,
w
er-limited (0.500 amps maximum)
pervision required. NonresettablePower
t
able for powering annunciators, Resettable
w
er suitable for powering smoke detectors.
nfigure TB9, Terminals 1 & 2
Resettable or Nonresettable Power.
R
esettable Power - jumper JP31
ns 2 & 3.
onresettable Power - jumper JP31 pins 1 & 2
a
s shown).
Special Application Power
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
NC position during
trouble conditions and
under loss of all power.
S
pecial Application
D
C Power Outputs (24 VDC)
o
nsupervised, power-limited circuits
u
pervise with a power supervision relay EOLR-1
Battery (see note 3)
Basic System Connections
10-Zone Panel
Notification Appliance Circuits (see note 1)
3 Programmable Relays
Alarm* Trouble* Supervisory*
NO NC C
24 VDC, supervised,
nonpower-limited
NO NC CNO NC C NO NC C
(* )Factory default relay programming
Power Supply Connector J15
NAC #1
+
+
+
4
3
FIRE ALARM
AC POWER
TROUBLE
1
4
7
*
231
56
89
0#
ABC DEF
GHI JKL
PRS TUV
QZ_ _/.
CLEAR
ESC
MODE
ST
ENTER
ALARM
DRILL RESET
J12
BATTERY
- +
TB5 TB4
TB7
TB6
TB8
TB9
J2 J7
J15
J3
JP24
JP31
JP30
J5
J4
J6
J8 J9
TB3
GND PWR
ANN-BUS
A B
RST AUX
PWR
RST/NONRST
AUXPWR
OUT1 OUT2 OUT3 OUT4
4XTMF OPT BD
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
2
1
JP43
Class A Converter Module
-
+
+
-
3
2
1
NAC #2
+
+
+
B
+B
-
11
B
+B
-
22
NAC #3
+
+
+
NAC #4
+
+
B
+B
-
33
B
+B
-
44
B
+B
-
11
B
+B
-
66
Initiating Device Circuits
IDCs 1 through 5,Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K ,½ watt
End-of-Line Resistor
PN 71252
IDCs 6 through 10, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Initiating Device Circuits
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
+
+
+
TB5/
TB7
TB4/
TB6
OUT1/3 OUT2/4
B
+B
-
11 2
B
+B
-
11
OUT OUT
TB2 TB1
J2
Class AConverter Module
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
Style Z (ClassA) NAC
Style D (Class A) IDC
+ - + - + - + -
+ - + - + - + - + - + - + - + - + - + -
+
m
portant!
Removing Ground Fault
sableJumper JP43 voids UL/NFPA
y
le/Class identifications for circuits.
e
move jumper JP43 only with the
p
proval of the AHJ
A
uthority Having Jurisdiction).
- +
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
TB2
Remote
Synchronization
Output (see note 2)
SpecialApplication Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires ELR.4.7K
Primary Phone
Active LED Secondary Phone
Active LED
Primary Secondary
Kiss-off LED
- +
Notes:
1. GF510 = 3 amps max. per NAC
2. 26 Amp Hour max. for GF510

Product Description Product Features
12 GF505 & GF510 Series PN 53164:A 3/26/2007
SECTION 1 Product Description
The GF505 is a five zone FACP (Fire Alarm Control Panel) and the GF510 is a ten zone FACP.
The information in this manual refers to both the GF505 and GF510 unless otherwise specified.
The combination control and digital communicator panels provide reliable fire signaling protection
for small to medium sized commercial, industrial and institutional buildings. The FACP is
compatible with System Sensor’s I3detectors which are conventional smoke detectors that can
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a
supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of
approximately 45oF (refer to System Sensor I3Installation and Maintenance Instructions). In
addition, the control panel is compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to Gamewell-FCI Device Compatibility Document for a
complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays
(factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application
resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery
level and telephone line integrity.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, display alarm
information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate an auxiliary control
function.
The following versions of the GF505/GF510 are available:
Note: Unless otherwise specified, the information in this manual applies to all versions of the
panels.
1.1 Product Features
• Built-inDACT (DigitalAlarmCommunicator/Transmitter)
• Style B (Class B) IDC (Initiating Device Circuit)
GF505 - five programmable IDCs
GF510 - ten programmable IDCs
• Four Style Y (Class B) NAC (Notification Appliance
Circuit) - special application power
• Three programmable Form-C relays
• Built-in Programmer
• Touchtone/Rotary dialing
• Programmable Make/Break Ratio
• Optional Dress Panel DP-51050 (red) or DP-51050W (white)
• Optional Dress Panel DP-51050LED or DP-51050LEDW (white): includes a GFANN-LED
Annunciator module
• Optional Trim Ring TR-CE (red) or TR-CEW (white) for semi-flush mounting the cabinet
• ANN-BUS for connection to optional:
FACP Version Description
GF505 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
GF510 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current

Specifications Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007 13
GFANN-80 Remote LCD Annunciator
GFANN-I/O LED Driver
GFANN-S/PG Printer Module
GFANN-RLY Relay Module
GFANN-LED Annunciator Module
• 80-character LCD display (backlit)
• Real-time clock/calendar with daylight savings time control
• History log with 256 event storage
• Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
• LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
• Piezo sounder for alarm, trouble and supervisory
• 24 volt operation
• Low AC voltage sense
• Alarm Verification
• NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
• Automatic battery charger with charger supervision
• Silent or audible walktest capabilities
• Optional CAC-5X Class A Converter Module for NACs and IDCs
• Optional 4XTMF Transmitter Module
1.2 Specifications
AC Power
GF505 & GF510 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 26 Amp Hour battery for GF505 & GF510 [two 18 Amp Hour
batteries can be housed in the FACP cabinet.]
Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 (and TB6 on GF510 only)
Alarm Zones 1 - 5 on TB 4 (GF505)

Product Description Specifications
14 GF505 & GF510 Series PN 53164:A 3/26/2007
Alarm Zones 6 - 10 on TB6 (GF510 only)
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to Gamewell-FCI Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB71
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 7.0 amps for GF505 & GF510 (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 2 VDC
Refer to Gamewell-FCI Device Compatibility Document for compatible listed devices
1. Total current for resettable power, nonresettable power and Notification Appliance Circuits
must not exceed 7.0 amps.

Controls and Indicators Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007 15
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to Gamewell-FCI Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to Gamewell-FCI Device Compatibility Document for compatible listed devices
Remote Sync Output - TB2
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an
external device for trouble conditions. It can be connected to the trouble bus of a peripheral,
such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012105

Product Description Controls and Indicators
16 GF505 & GF510 Series PN 53164:A 3/26/2007
Function keys:
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
Service/program keys:
• Keys labeled 1 to 9
• * key
• # key
• 0 (recall) key
• 1st Event key
• Clear key
• Escape key
• Mode key
• Four cursor keys (up, down, left and right)
• Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
• Fire Alarm - red LED
• Supervisory - yellow LED
• AC Power - green LED
• System Trouble - yellow LED
• Alarm Silence - yellow LED
• Primary Phone Line Active (on circuit board) - red LED
• Secondary Phone Line Active (on circuit board) - red LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:
• Alarm - on steady
• Trouble - pulse 1 second on and 1 second off
• Maintenance - pulse ½ second on and ½ second off
• Supervisory - pulse ½ second on and ½ second off
• Process Monitor - pulse ¼ second on and ¼ second off
Figure 1.1 Membrane/Display Panel
9050udkypd.cdr

Digital Alarm Communicator/Transmitter Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007 17
1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the
following functions:
• Line Seizure: takes control of the phone lines disconnecting any premises phones
• Off/On Hook: performs on and off-hook status to the phone lines
• Listen for dial tone: 440 Hz tone typical in most networks
• Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary
• For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
• Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
• FLPS-7 for the GF505 & GF510
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050/W) which mounts inside the cabinet and trim-ring (TR-CE/W).
Batteries
The cabinet provides space for two 18 Amp Hour batteries. Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the GF505 and to J7 on the GF510. Note that two Class A Converter
modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
GFANN-80 LCD Annunciator
The GFANN-80 is a remote LCD annunciator which mimics the information displayed on the

Product Description Optional Modules and Accessories
18 GF505 & GF510 Series PN 53164:A 3/26/2007
FACP LCD display.
GFANN-LED Annunciator Module
The GFANN-LED Annunciator Module mounts in the DP-51050LED/W Dress Panel and provides
three LEDs for each zone: Alarm, Trouble and Supervisory.
GFANN-RLY Relay Module
The GFANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
GFANN-S/PG Serial/Parallel Printer Gateway
The GFANN-S/PG module provides a connection for a serial or parallel printer.
GFANN-I/O LED Driver Module
The GFANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050/W Dress Panel
A dress panel DP-51050 (red) or DP-51050W (white) is available as an option. The dress panel
restricts access to the system wiring while allowing access to the membrane switch panel.
TR-CE/W Trim-ring
A trim-ring TR-CE (red) or TR-CEW (white) is available as an option. The trim-ring allows semi-
flush mounting of the cabinet.
Battery Box
The battery box may be used to house two batteries greater than 18 Amp Hour. The battery box
mounts directly below the control panel cabinet, centered to the main circuit board.

Telephone Requirements and Warnings Product Description
GF505 & GF510 Series PN 53164:A 3/26/2007 19
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer: Gamewell-FCI
12 Clintonville Road
Northford, CT 06472
(203) 484-7161
Product Model Number: GF505/GF510
FCC Registration Number: 1W6AL00B10UD
Ringer Equivalence: 0.0B
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Note: This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the inside of the FACP door is a label that contains,
among other information, a product identifier in the format
US:AAAEQ##TXXXX. If requested, this number must be provided to the
telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency
situation. It must be able to do this even if other equipment (telephone, answering system,
computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of
all other equipment attached to the same telephone line. If there are any questions concerning these
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack
and alarm dialing equipment. Refer to "Digital Communicator" on page 31 for an illustration of
the proper installation of this equipment.

Product Description Telephone Requirements and Warnings
20 GF505 & GF510 Series PN 53164:A 3/26/2007
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible.
The opportunity will be given to correct any problems and to file a complaint with the FCC if you
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line.
The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment
is designed to be connected to the telephone network or premises wiring using a compliant RJ31X
male modular plug and compatible modular jack that is also compliant.
This manual suits for next models
1
Table of contents
Other Gamewell Control Panel manuals
Popular Control Panel manuals by other brands

LinkAYL
LinkAYL LK-UP24 Series quick start guide

UPS Aviation Technologies
UPS Aviation Technologies 10 user guide

FAAC
FAAC Estate Swing E-SL 1800 installation manual

DSC
DSC PowerSeries PC1616 user manual

Digital Equipment
Digital Equipment Pro-face FP3700-T41 installation guide

JCM Technologies
JCM Technologies EASY-ROLL user manual

Lennox
Lennox OLT-1X user manual

Potter
Potter PFC-3005T Installation and operation manual

Danfoss
Danfoss OPTYMA Control AK-RC 101 Operation and maintenance guide

Pyronix
Pyronix Atlas LCD user guide

Beckhoff
Beckhoff CP70 Series Installation and operating instructions

Miranda
Miranda iMC-Panel-300 Operator's guide