Function description
The GAT Access 6600 reads 1D barcodes, 2D barcodes (e.g., QR-codes)
and RFID data carriers and verifies the information before granting or
denying access.
To read barcode tickets the terminal is equipped with a CMOS barcode
reader. The large reading slot provides comfortable access for reading
barcode tickets of different shapes and sizes. Remove the reading slot
module and it becomes possible to read barcodes that are opened on a
mobile phone display.
If RFID data carriers are also used in the facility, it is possible to identify
system users using their data carriers. The user simply holds their data
carrier next to the circular reading field on the front of the terminal.
Authorisation information is indicated by the large, clearly visible traffic light
LEDs on top of the terminal and next to the display. Further user guidance
to indicate authorisation is provided by LEDs in the RFID scan field and
barcode reading slot as well as an acoustic signal.
Highlights
•Activation of turnstiles, doors, etc., via relay outputs
•Feedback inputs
•Reading slot for barcode tickets (removable)
•1D barcodes and 2D barcodes (e.g., QR-codes)
•Barcode tickets of almost any standard size possible
•Mobile tickets - 1D and 2D barcodes received by mobile phones
•Print@Home tickets - tickets printed at home on A4 or US letter paper
•Clearly visible LED light for indication of rates and status information
(various colours)
•Illuminated, circular scan field for RFID data carriers
•Secure data transmission between reader and data carrier
•Robust plastic enclosure with safety glass
•For outdoor use
•Mounting on tubular holder
Application
The GAT Access 6600 is a stylish terminal for access control in leisure
facilities such as public swimming pools, indoor and outdoor water facilities
and attraction parks. The terminal is mounted directly onto turnstiles or
similar access control hardware and provides convenient operation for
the facility guests. Identification at the terminal is achieved either with
barcode tickets (1D and 2D) or with contact-free RFID data carriers
(Radio Frequency Identification).
The clear interface guides the user through the various, well-structured
levels. Different versions of the terminal are available (see order
information) to provide compatibility with different RFID technologies.
The GAT Access 6600 is suitable for a variety of applications and is
designed to operate in indoor and outdoor areas.
1
Valid as from June 16
th
2015 • Technical data subject to modifications without notice!
DB_GAT-ACCESS6600--EN_11.indd • PartNo.: 822630
www.gantner.com
Description PartNo.
Manual GAT Access 6200/6350/6500 EN
Installation, configuration and operating instructions in
english
169028
GAT Access 6600
Access Control Terminal with RFID and Barcode
Description Part No.
GAT Access 6600 F
Access control terminal with barcode and contact-free
RFID reader for MIFARETM data carriers
641225
GAT Access 6600 ISO
Access control terminal with barcode and contact-free
RFID reader for ISO 15693 data carriers
716026
GAT Access 6600 B
Access control terminal with barcode and contact-free
RFID reader for LEGIC®data carriers
715934
Order information
Accessories
Description Part No.
GAT Holder 6010 L
Tubular holder for mounting the GAT Access 6600 onto
a turnstile, stainless-steel, Ø 30 mm
142019
GAT NET.Power Supply 100-240V
Power supply unit for supplying the GAT Access 6600
Output 24 VDC / 1.7 A
AC connector: IEC 60320 C7 connector
DC connector: GAT NET.Lock Molex connector
369434
GAT NET.Power Cord EU
GAT NET.Power Cord UK
GAT NET.Power Cord AUS
GAT NET.Power Cord US
GAT NET.Power Cord IND
Power cord for the GAT NET.Power Supply 100-240V
with applicable power plug (see country code)
494181
494282
511474
636835
636734
Nominal voltage: 12/24 VDC SELV LPS
Permitted input voltage: 10 to 26 VDC SELV LPS
Input current: 1.2 A
Data storage: Internal flash memory for configuring
and booking memory, data preser-
vation min. 10 years
RFID reader types: See order information
Control elements: - RFID reader
- Barcode reader
Display elements: - Full graphics monochrome display
with white LED background lighting,
resolution 128 x 128 pixels,
visible area 65 x 65 mm
- Barcode reader slot
- RFID reader (illuminated)
- Integrated LED light for rate and
status display, different light-colours
- Acoustic signal
Barcode reader: CMOS reader
reads 1D and 2D barcodes,
also possible with smartphone displays
Host interface: Ethernet 10/100 Mbit/s and RS 485
Software integration: GAT DIRECT.Connect
Signal inputs: 4 x optocouplers (configurable)
- Input voltage: 0 to 30 VDC
ULow < 2 VDC, UHigh > 6 VDC
- Input current: 4.5 mA
Signal outputs: 4 x relays (configurable NO/NC)
- Switching voltage DC: max. 30 V SELV
- Switching voltage AC: max. 15 V SELV
- Continuous current: max. 1.8 A
- Switching power: max. 54 W, 27 VA
Connection terminals: 0.5 to 1.5 mm2
Housing material: Plastic with safety glass front
Dimensions (housing): approx. 280.6 x 194 x 135.5 mm
(approx. 8.21 x 7.64 x 5.33 inch)
Permitted ambient temperature: -25 to +50°C (-13 to 122 °F)
Storage temperature: -25 to +70°C (-13 to 158 °F)
Protective type: IP X3
Protective class: III
Weight: approx. 2 kg (4.4 lbs)
2www.gantner.com
Technical data
Typical application
Dimensions
1. LED Light for tariff and status display (different colours)
2. Monochrome display
3. Status LEDs
4. Illuminated, circular RFID scan field
5. Inset for barcode tickets (removable for larger barcodes or smartphones)
6. Tubular holder, Ø 30 mm (not included in scope of supply
Valid as from June 16
th
2015 • Technical data subject to modifications without notice!
DB_GAT-ACCESS6600--EN_11.indd • PartNo.: 822630
135.5 mm (5.33“)
280.6 mm (8.21“)
194 mm (7.64“)
2
1 1
4
3
5 5
6 6
Turnstile
GAT Access 6600
Power supply
Data carrier
Network
3
www.gantner.com
Mounting and installation instructions
In order to mount the GAT Access 6600 onto a turnstile, a tubular
mounting holder with 30 mm Ø is used (e.g., a GAT Holder 6010 L). The
connecting cables are fed through the tubular holder and into the housing.
Opening the housing
The housing of the GAT Access 6600 must be opened to install the tubular
holder. Unscrew and remove the 4 housing screws on the rear part while
firmly holding the front part of the GAT Access 6600 to prevent it from
falling. After the screws are removed, the front part can be lifted away.
Two clamps inside the housing are used to fasten the tubular holder. The
lower clamp (1) is directly accessible and can be loosened accordingly to
allow the tubular holder to be inserted.
In order to gain access to the second clamp (2), the electronics (3) must
be removed. Loosen the two screws as indicated in the figure below (4)
and swing the electronics 90 ° forward (5).
Attachment of the tubular holder and cable installation
Insert the GAT Access 6600 onto the tubular holder (7) until the stop (6)
is reached.
Tighten the screws of the two clamps (1) + (2) firmly so that the GAT
Access 6600 is secure and cannot be removed from the tubular holder.
Feed the connecting cables through the tubular holder. Connect the
cables to the screw terminals (see next page). Use cable ties to secure
the cabling to the holes provided in the retaining strip (8).
Remount the electronics in their original position and fasten the 2 screws
(4). Take care not to damage the connecting cable.
Close the housing by placing the front part of the housing onto the
rear part and secure them with the 4 screws. Take care to ensure the
housing gasket is correctly inserted into the joint between the front
and rear part and not damaged during this process.
Valid as from June 16
th
2015 • Technical data subject to modifications without notice!
DB_GAT-ACCESS6600--EN_11.indd • PartNo.: 822630
1
2
3
4
3
4
4
3
3
5
2x
2
6
7
6
1
7
8
7
6
8
7
8
Valid as from June 16
th
2015 • Technical data subject to modifications without notice!
DB_GAT-ACCESS6600--EN_11.indd • PartNo.: 822630
4www.gantner.com
Electrical connections
TCP/IP with external power supply
Network
Ethernet (default) or RS 485 bus connection.
Attention: Both interfaces must not be operated at the same time!
Only connect the A and B signal lines when using RS 485 bus connection.
Do not use the COM terminal.
Power supply
DC power supply that complies with SELV (safety extra low voltage) and
LPS (limited power source). See technical data for details. GANTNER
offers the GAT NET.Power Supply 100-240V to supply the GAT Access
6600. When using the GAT NET.Power Supply 100-240V the provided
power plug must be cut off and the cabling terminated onto the “VIN +”
and “GND” screw terminals (see details in diagram above).
The two “VIN +” terminals are internally directly connected. The voltage
input is protected against reverse polarity.
Recommended cables
Ethernet: min. CAT 5 (STP) for 100 MBit
RS 485: min. CAT 5 (STP), power supply via 2 wire pairs
Relay outputs
For activation of devices such as turnstiles, etc., each relay provides
NC (normally closed) and NO (normally open) operation. The permitted
switching power levels (see technical data) must never be exceeded.
Optocoupler inputs
Potential free inputs for status detection. An input voltage must be applied
to activate the input. This voltage can be supplied by the terminal‘s power
source or from an external power source. Please observe the maximum
permitted input voltage and current (see technical data).
Safety instructions
- This device must be installed by qualified personnel only.
- The applicable safety and accident prevention regulations
must be observed.
- Safety devices must not be removed.
- Please observe the technical data of the device specified
on the data sheet.
- The device must be disconnected from the power supply
prior to installation, assembly or dismantling.
TCP/IP
GAT Access 6600
Power supply unit
GAT NET.Power Supply 100-240V
A
B
+24 VDC
0V24
COM
RS 232/USB
to PC/Server
M
LBL
M+
M-
RX
TX
HF+
HF-
V+
Motor Peripheral Antenna 2
Key 1 Key 2 Key 3 Key 4
M+
M-
RX
TX
HF+
HF-
V+
Motor Peripheral Antenna 2
Internal electronics
black
white
red
red
black
green
MOLEX-Cut-off power plug
VIN+ ... black + white line
GND ... black
e.g. Turnstile
Motor control
Feedback contact
Mains power
Interface converter
ISK 200
Mains power

This manual suits for next models

3

Other Gantner IP Access Controllers manuals

Gantner GAT ACCESS 6100 User manual

Gantner

Gantner GAT ACCESS 6100 User manual

Gantner GAT SLR 7300 User manual

Gantner

Gantner GAT SLR 7300 User manual

Gantner GAT Access 6100 F User manual

Gantner

Gantner GAT Access 6100 F User manual

Popular IP Access Controllers manuals by other brands

HIK VISION DS-K5603-Z quick start guide

HIK VISION

HIK VISION DS-K5603-Z quick start guide

HIK VISION MinMoe DS-K1T671TM-3XF manual

HIK VISION

HIK VISION MinMoe DS-K1T671TM-3XF manual

HIK VISION DS-K3M200 quick start guide

HIK VISION

HIK VISION DS-K3M200 quick start guide

XPR Access EWS-DR Installer manual

XPR Access

XPR Access EWS-DR Installer manual

HIK VISION DS-TMT201-D quick start guide

HIK VISION

HIK VISION DS-TMT201-D quick start guide

UNIONCOMMUNITY Virdi AC-2100 user guide

UNIONCOMMUNITY

UNIONCOMMUNITY Virdi AC-2100 user guide

HIK VISION DS-K1T803F user manual

HIK VISION

HIK VISION DS-K1T803F user manual

HIK VISION DS-K3B601 installation guide

HIK VISION

HIK VISION DS-K3B601 installation guide

UNIONCOMMUNITY FMD10-BLE user guide

UNIONCOMMUNITY

UNIONCOMMUNITY FMD10-BLE user guide

Shuttle BR06S Software Quick Start Guide

Shuttle

Shuttle BR06S Software Quick Start Guide

Tidel IES 50 Installation and startup guide

Tidel

Tidel IES 50 Installation and startup guide

Altronix Trove THWD2 installation guide

Altronix

Altronix Trove THWD2 installation guide

H3C WX1800H series installation guide

H3C

H3C WX1800H series installation guide

Segal MJM-2700 Connection diagram

Segal

Segal MJM-2700 Connection diagram

ADATIS XS Series installation manual

ADATIS

ADATIS XS Series installation manual

Richelieu SAFE-O-TRONIC access 6330084330 manual

Richelieu

Richelieu SAFE-O-TRONIC access 6330084330 manual

Vidos ZS52 user manual

Vidos

Vidos ZS52 user manual

Gallagher C300400 Installation notes

Gallagher

Gallagher C300400 Installation notes

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.