GE Interlogix Concord Security System User manual

)
*(,QWHUORJL[
S t a t u s
F e a t u r e s
p r e s s b o t h
L i g h t s
S y s t e m
A w a y
Q u i c k E x i t
O f f
N o D e l a y
p r e s s b o t h
p r e s s b o t h
T e s t S y s t e m W e e k l y
S i l e n t
S t a y
D
*
7
0 #
8
B
A
4
1
56
23
B y p a s s
e n u
C9
P r o g r a m U s e r S e t t i n g s
p r e s s 0 - 9 f o r o t h e r e n t r i e s .
P r e s s 1 f o r O F F ; p r e s s 2 f o r O N ;
P r e s s # t o s e l e c t o p t i o n o r a c c e p t e n t r y .
0 6
0 7
0 5
0 4
1 3
1 4
1 2
1 1
A r m t o S T A Y
Q u i c k G u i d e
D i s a r m S y s t e m / C a n c e l A l a r m
i f d e s i r e d .
2
0 1
0 2
0 3
3
1
0 8
0 9
1 0
P r e s s t o d e s e l e c t o p t i o n o r c a n c e l e n t r y .
C l o s e a l l p r o t e c t e d d o o r s a n d w i n d o w s .
P r e s s 3 C O D E .
E x i t p r e m i s e s t h r o u g h d e l a y d o o r .
2
3
1
P r e s s 2 C O D E .
C l o s e a l l p r o t e c t e d d o o r s a n d w i n d o w s .
P r e s s 4 t o a r m d e l a y d o o r s i n s t a n t l y ,
A r m t o A W A Y
Z o n e / S e n s o r N u m b e r
P r e s s 1 C O D E . 2
1
P r e s s A o r B t o s c r o l l t h r o u g h m e n u s .
M a k e s u r e s y s t e m i s d i s a r m e d .
2
1
P r e s s 7 1 t o t u r n C H I M E o n o r o f f .
M a k e s u r e s y s t e m i s d i s a r m e d .
2
1
T u r n C H I M E O n / O f f
P r e s s B Y P A S S C O D E S e n s o r N o .
A r m s y s t e m t o d e s i r e d l e v e l .
y p a s s S e n s o r s
S y s t e m i s O K
S t a t u s
F e a t u r e s
p r e s s b o t h
L i g h t s
S y s t e m
A w a y
Q u i c k E x i t
O f f
N o D e l a y
p r e s s b o t h
p r e s s b o t h
T e s t S y s t e m W e e k l y
S i l e n t
S t a y
D*
7
0 #
8
B
A
4
1
56
23
B y p a s s
e n u
C9
A r m e d
R e a d y
Installation Instructions
466-1512-01 Rev F
August 2003
Concord Security System
(Software Version 3.1)
Part Numbers:
60-792-01-95R
60-734-01
60-801-01
ZZZ*(,QWHUORJL[FRP

Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by GE Interlogix can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the affected equipment and the panel receiver to separate outlets, on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
ACTA Part 68
This equipment complies with Part 68 of the FCC Rules. Located on this equipment is a label that contains, among other information, the FCC registration num-
ber and the ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
FCC Part 68 Registration No. B4ZUSA-25644-AL-E
The REN is used to determine the maximum number of devices that may be connected to your telephone line. Excessive RENs on a telephone line may result in
devices not ringing in response to an incoming call. In most areas, the sum of all device RENs should not exceed five (5.0). To be certain of the number of
devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2001, the
REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal
point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and require-
ments as adopted by ACTA. A compliant telephone cord and modular plug is provided with this product. It is designed to be connected to a compliant modular
jack that is also compliant. See the Installation Instructions for details.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment
(telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly
installed RJ31X jack that is electrically in series and ahead of all other equipment attached to the same telephone line. Proper installation is depicted in the fol-
lowing diagram. If you have any questions concerning these instructions, consult your local telephone company or a qualified installer about installing an RJ31X
jack and alarm dialing equipment for you.
If this equipment causes harm to the telephone network, the telephone company may temporarily disconnect your service. If possible, you will be notified in
advance. When advance notice is not practical, you will be notified as soon as possible. You will also be advised of your right to file a complaint with the FCC.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. You will be
given advance notice in order to maintain uninterrupted service.
If you experience trouble with this equipment, please contact the company that installed the equipment for service and/or repair information. The telephone com-
pany may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure that the equipment is not malfunctioning.
This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs
Patent Information
This product and the use of this product may be covered by one or more of the following patents: 5,805,063, 5,872,512 5,942,981, 5,686,896, 5,686,885,
4,855,713. Except expressly provided herein, the purchase of this product shall not constitute a license or otherwise provide a right to practice a method covered
by any of the identified patents. GE Interlogix hereby grants the purchaser of this product a limited, non-exclusive license to practice the methods patented in the
identified patents solely with products manufactured, sold or licensed by GE Interlogix. This license grant does not extend to the use of unlicensed, third party
products with this product.
N e t w o r k
S e r v i c e
P r o v i d e r ' s
F a c i l i t i e s
Telephone
L i n e
N e t w o r k
D e m a r c a t i o n
P o i n t
Telephone
A n s w e r i n g
S y s t e m
F a x a c h i n e
C o m p u t e r
Telephone
Telephone
A l a r m D i a l i n g
E q u i p m e n t
R J 3 1 X
J a c k
U n u s e d
R J - 1 1 J a c k
U n u s e d
R J - 1 1 J a c k
C u s t o m e r P r e m i s e s E q u i p m e n t a n W i r i n g

i
Contents
About This Manual 1
Special Installation Requirements .............................................................................................................. 1
UL Listed Installations............................................................................................................................ 1
SIA System Requirements...................................................................................................................... 2
Central Station Reporting ....................................................................................................................... 4
UL Canada Listed Installations............................................................................................................... 4
California State Fire Marshall Listed Installations................................................................................. 4
Planning the Installation 4
Standard Panel ............................................................................................................................................ 4
SuperBus 2000 Touchpads.......................................................................................................................... 5
SuperBus 2000 RF Receivers ..................................................................................................................... 5
Power Line Carrier Card............................................................................................................................. 5
Phone Supervision Card.............................................................................................................................. 5
Supervised Wireless Siren .......................................................................................................................... 5
SuperBus 2000 Phone Interface/Voice Module.......................................................................................... 5
SnapCards ................................................................................................................................................... 5
SuperBus 2000 8Z Input Module (HIM) .................................................................................................... 6
SuperBus 2000 4-Relay Output Module (HOM)........................................................................................ 6
Interrogator 200 Audio Verification Module.............................................................................................. 6
SuperBus 2000 Cellular Backup Module ................................................................................................... 6
SuperBus 2000 Energy Saver Module (ESM)............................................................................................ 6
SuperBus 2000 Automation Module .......................................................................................................... 6
SuperBus 2000 Wireless Gateway Module ................................................................................................ 6
Installing the System 6
Determine the Panel Location..................................................................................................................... 7
Total System Power and Wire Length Guidelines...................................................................................... 7
Mounting the Panel..................................................................................................................................... 9
Identify Panel Components 10
Installing Antennas ................................................................................................................................... 10
Connecting the Panel to Earth Ground ..................................................................................................... 11
Installing the Optional Power Line Carrier Card (60-755)....................................................................... 11
Installing the Optional Phone Supervision Card (60-789)........................................................................ 11
Installing Optional SnapCards.................................................................................................................. 12
Connecting Detection Devices to Panel Zone Inputs ............................................................................... 12
Connecting Intrusion Detection Devices.............................................................................................. 12
Connecting 2-Wire Smoke Detectors ................................................................................................... 12
Connecting 4-Wire Smoke Detectors ................................................................................................... 13
Connecting Speakers................................................................................................................................. 14
15-Watt Speaker (13-060)..................................................................................................................... 14
Hardwire Interior Speaker (60-528) ..................................................................................................... 14
Connecting Piezo Sirens........................................................................................................................... 15
Exterior Sirens ...................................................................................................................................... 15
Interior Sirens ....................................................................................................................................... 15

ii
Installing Supervised Wireless Sirens (60-736-95) .................................................................................. 16
Connecting an Interrogator 200 Audio Verification Module (60-677)..................................................... 17
Connecting Alphanumeric and Fixed Display Touchpads ....................................................................... 17
Installing SuperBus 2000 Modules........................................................................................................... 18
SuperBus 2000 RF Receiver (60-764-01-95R-16Z/32Z/MAX)........................................................... 18
SuperBus 2000 Phone Interface/Voice Module (60-777-01)................................................................ 19
SuperBus 2000 Energy Saver Module (60-620-01) ............................................................................. 20
SuperBus 2000 8Z Input Module (60-774)........................................................................................... 20
SuperBus 2000 4-Relay Output Module (60-770)................................................................................ 20
SuperBus 2000 Cellular Backup Module ................................................................................................. 21
SuperBus 2000 Automation Module (60-783-02).................................................................................... 21
SuperBus 2000 Wireless Gateway Module (60-861) ............................................................................... 21
Setting Device Address on SuperBus 2000 Devices ................................................................................ 22
Installing an RJ-31X Phone Jack (13-081)............................................................................................... 22
Connecting the Phone Line to the Panel with a DB-8 Cord..................................................................... 22
Connecting the AC Power Transformer ................................................................................................... 23
Powering Up the Panel ............................................................................................................................. 23
Programming the Panel 24
Entering Program Mode............................................................................................................................ 24
Touchpad Button Programming Functions............................................................................................... 24
Moving Through Program Mode Tiers and Menus .................................................................................. 25
Programming Tier 1 Menu Items.............................................................................................................. 26
Programming Tier 2 Menu Items.............................................................................................................. 27
Using Shortcut Numbers....................................................................................................................... 27
Security Menu....................................................................................................................................... 27
Phones Menu......................................................................................................................................... 30
Phone Options Menu ............................................................................................................................ 35
Timers Menu......................................................................................................................................... 39
Light Control Menu .............................................................................................................................. 41
Touchpad Options Menu....................................................................................................................... 42
Reporting Menu.................................................................................................................................... 43
Siren Options Menu.............................................................................................................................. 48
Sensors Menu........................................................................................................................................ 49
Audio Verification Menu ...................................................................................................................... 51
Accessory Modules Menu .................................................................................................................... 53
Onboard Options Menu ........................................................................................................................ 56
Exiting Programming Mode ..................................................................................................................... 58
Entering User Programming Mode........................................................................................................... 58
Time and Date Menu ............................................................................................................................ 58
User Codes Menu.................................................................................................................................. 59
Options Menu ....................................................................................................................................... 61
Set Up Schedules Menu........................................................................................................................ 62
Attach Schedules to Events Menu ........................................................................................................ 63
Attach Lights to Sensors Menu............................................................................................................. 65
System Version Menu........................................................................................................................... 65
Downloader Programming........................................................................................................................ 66
ToolBox Downloader Programming..................................................................................................... 66
Testing the System 66

iii
Basic System Commands.......................................................................................................................... 66
Testing Zones/Sensors .............................................................................................................................. 67
If a Wireless Sensor Does Not Test ...................................................................................................... 67
Testing Phone Communication................................................................................................................. 67
Testing Central Station/Pager Communication......................................................................................... 68
Testing Outputs and Sirens ....................................................................................................................... 68
Testing Light Control................................................................................................................................ 69
Testing the Energy Saver Module (ESM)................................................................................................. 69
Changing Fixed Display LCD Touchpad Chime and Trouble Beep Tones.............................................. 69
Adjusting Touchpad Display Contrast...................................................................................................... 70
Testing Audio Verification Module (AVM) Communication................................................................... 70
Testing Cellular Backup Communication................................................................................................. 70
Troubleshooting 72
Appendix A: System Planning Worksheets 78
Appendix B: Reference Tables 86
Cross-Zoning ............................................................................................................................................ 87
Appendix C: Settings 96
Specifications 101
System Wiring Notes 102
6HFRQG6WUHHW1RUWK
1RUWK6DLQW3DXO01
7HFKQLFDO6XSSRUW
)
*(,QWHUORJL[
(,QWHUORJL[&RQFRUGLVDWUDGHPDUNRI (,QWHUORJL[6XSHU%XVDQG7RROER[
DUHUHJLVWHUHGWUDGHPDUNVRI (,QWHUORJL[$OORWKHUWUDGHPDUNVDUHSURSHUWLHVRIWKHLU
RZQHUV
$OOULJKWVUHVHUYHG

Concord
1
About This
Manual
This manual provides information for planning, installing, programming, and testing this security
system. When necessary, this manual refers you to other documentation included with compati-
ble peripherals.
Planning sheets are included for you to record hardware layout and software programming set-
tings.
About the User’s Guide
The User’s Guide (466-1513-01) contains user worksheets that should be filled out during the
installation and programming of the system. With two partition systems, a User’s Manual for
each partition is suggested.
Special Installation Requirements
This security system can be used as a fire warning system, an intrusion alarm system, an emer-
gency notification system, or any combination of the three.
Some installations may require configurations dictated by city/state codes, insurance, or Under-
writer’s Laboratories (UL). This section describes the various component and configuration list-
ings.
UL Listed Installations
This section describes the requirements for UL Listed installations.
Basic System
• Control Panel (60-734-01 Hybrid or 60-792-01-95R Integrated)
• Backup Battery 12V 4 AH (60-681) or 12V 7 AH (60-680)
•SuperBus
®2000 Fixed Display Touchpad (60-820), 2x16 LCD Touchpad (60-746-01), 2x20
LCD Touchpad (60-803), or 2x20 VFD Touchpad (60-804)
• Standard Class II 24 VAC, 30 VA Power Transformer (60-761), Class II 24 VAC, 30 VA
Line Carrier Power Transformer (60-762), or Standard Class II 24 VAC, 50 VA Power
Transformer (60-778), Class II 24 VAC, 50 VA Line Carrier Power Transformer (60-779)
• Interior Speaker Siren (60-528), Exterior Speaker Siren (13-060), Slim Line Hardwire Inte-
rior Siren (60-483-01) or Hardwire Exterior Siren (13-046) per partition
Basic system may also include a SuperBus 2000 RF Receiver (60-764-01-95R-16Z) or
(60-764-01-95R-32Z) or (60-764-01-95R-MAX).
Household Burglary Alarm System Unit (UL 1023)
Basic system, plus:
• Hardwire Magnetic Contact (13-068 or 13-071) or Wireless Learn Mode Door/Window Sen-
sor (60-362)
• Immediate Beeps set to on
• UL 98 Options set to on
• Receiver Failure set to on (if wireless devices are used)
• Siren Verify set to on
• Exit Delay set to 60 seconds
• Quick Exit set to off
• Siren Timeout set to 4 minutes or more
• Entry Delay set to 45 seconds or less
• RF TX Timeout set to 24 hours (if system includes a built in or SuperBus 2000 RF Receiver
and wireless smoke sensors)
• Extended Delay set to off
• Sleep Time set to off
• Two Trip Error set to off
• Alarm Verify set to off
• Disable Trouble Beeps set to off
Household Fire Warning System (UL 985)
Basic system, plus:

Concord 2
• Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400,
or 2400TH learned into sensor group 26 or Sentrol (ESL) models 429AT, 521B or 521BXT
learned into sensor group 26
• Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26
• Immediate Beeps set to on
• UL 98 Options set to on
• Receiver Failure set to on (if wireless devices are used)
• Siren Verify set to on
• RF TX Timeout set to 4 hours (if system includes a built in or SuperBus 2000 RF Receiver
and wireless smoke sensors)
• Sleep Time set to off
• Siren Timeout set to 4 minutes or more
• Two Trip Error set to off
• Disable Trouble Beeps set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to 90 mA (during
normal standby conditions) using a 4.0 AH battery, or 190 mA (during normal standby condi-
tions) using a 7.0 AH battery.
SIA System Requirements
Note
UL requirements take prior-
ity over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic System on page
1, plus:
• If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
Shortcut # Function Programming
Page
Reference
Testing
Page
Reference
Default
Setting
Required Setting
0004 SIA False Alarm
Reduction
28 66 On On
partition 1: 0013
partition 2: 0023
Exit Extension 29 66 On On
partition 1: 0014
partition 2: 0024
Auto Stay Arming 29 66 On On
partition 1: 0017
partition 2: 0027
Duress Code 30 66 Disabled Disabled
02005 Dialer Abort 36 66 On On
02006 Dialer Abort Delay 36 66 30 Sec. 15-45 sec.
02007 Cancel Message 36 66 On On
02009 Call Wait Cancel 37 66 Disabled On if reporting to central station and
customer has call waiting service
partition 1: 0310
partition 2: 0320
Entry Delay 40 66 30 sec. 30-240 sec.
partition 1: 0311
partition 2: 0321
Exit Delay 40 66 60 sec. 45-184 sec.
06014 Swinger Limit 45 66 1 1
1100 Smoke Verify 57 66 Off On if smoke alarms are programmed
into system
N/A Cross Zoning 85 66 Disabled Enabled for zones with a high
probability of false alarms

Concord
3
The following table describes non-programmable (hard coded) system operation as required to
meet ANSI-SIA CP-01 and is provided only for your reference.
Commercial Burglary Alarm System Unit (Grade C UL 1610)
Basic system using Control Panel 60-801-01 plus:
• Hardwire Magnetic Contact (13-068 or 13-071) or Wireless Learn Mode Door/Window
Sensor (60-499)
• SAW PIR Sensor (60-639-95R), Crystal PIR Sensor (60-703-95R), or DS924i PIR Sensor
(60-511-01-95)
• Immediate Beeps set to on
• UL 98 Options set to on
• Receiver Failure set to on (if wireless devices are used)
• RF TX Timeout set to 4 hours
• 24-Hour Tamper set to on
• System Tamper set to on
• Auto Phone Test set to on
• Phone Test Freq. set to 1
• Next Phone Test set to 1
• Siren Verify set to on
• AC Failure set to on
• Exit Delay set to 120 seconds or less
• Quick Exit set to off
• Two Trip Error set to off
• Alarm Verify set to off
• Disable Trouble Beeps set to off
• Phone Number must be programmed
• High Level Rpts set to on
• Low Level Rpts set to on
• Comm. Failure set to on
• Extended Delay set to off
• Sleep Time set to off
• Siren Timeout set to 4 minutes or more
UL 1610 24-Hour Backup
• Same as UL 1023 & 985
UL 1635 Digital Alarm Communicator System
Note
For UL 1635 installations,
Entry Delay plus Dialer
Abort Delay must not
exceed 60 seconds.
Same as UL 1023, 985 & 1610 plus:
• AC Failure set to on
• Phone Number must be programmed
• Low CPU Battery set to on
• Next Phone Test set to 1
• Phone Test Freq. set to 1
• High Level Rpts set to on
• Low Level Rpts set to on
• Comm. Failure set to on
• RF Tx Timeout set to 4 hours
Function Operation
Disarm During Entry Delay Enter Code Only (or 1 + CODE)
Cancel Alarm Enter Code Only (or 1 + CODE)
Abort Annunciation Enabled
Cancel Report Annunciation Enabled

Concord 4
Central Station Reporting
The panel has been tested with the following central station receivers using SIA and Contact ID
reporting formats:
• CS-5000 Central Station Receiver
• Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2
UL Canada Listed Installations
This section describes the requirements for CUL (UL Canada) Listed installations.
Canadian Standards CSA Certified Accessories
Residential Burglary Alarm System Unit (ULC-S309)
Basic system as described for “UL 1023 Listed Installations” plus:
• Hardwire Magnetic Contact (13-068 or 13-071) or Wireless Learn Mode Door/Window Sen-
sor (60-362)
• Siren Timeout set to 5 minutes or more
Residential Fire Warning System Control Unit (ULC-S545-M89)
Basic system as described for “UL 985 Listed Installations” plus:
• Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400,
2400TH learned into Sensor Group 26, or Sentrol (ESL) models 429AT, 521B, or 521BXT
learned into sensor group 26
• Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26
• Immediate Trouble Beeps set to on
Note
For 24-hour backup, exter-
nal power drain is limited to
90 mA (during normal
standby condition) using a
4.0 AH battery, or 190 mA
continuous using a 7.0 AH
battery.
• RF TX Timeout set to 4 hours (if system includes SuperBus 2000 RF Receiver and wireless
smoke sensors)
California State Fire Marshall Listed Installations
Same as Household Fire Warning System (UL 985), plus:
• SMOKE VERIFY must be set to off
Planning the
Installation
This section describes system capabilities to help you get familiar with the system. “Appendix
A” provides planning sheets with tables that let you record the hardware and programming con-
figuration of the system. Fill in all necessary information ahead of time to help prepare for sys-
tem installation.
When planning the installation, keep in mind that the panel has the following capabilities (depen-
dent upon devices used):
• Up to 16 SuperBus 2000 Devices (maximum of 4 RF receivers)
• Up to 96 wireless or hardwired zones
Standard Panel
The following describe the basic panel (out-of-box) hardware capabilities.
•Power: Input for an AC step-down, plug-in style transformer.
•Auxiliary Power Output: Output that supplies 8.5 to 13.5 VDC with up to 1 amp (with
panel powered by 30 VA transformer) or 2 amps (with panel powered by 50 VA transformer)
for bus devices and hardwired detectors, such as smoke and motion detectors.
•Bus A and B: Input and output that provides communication between bus devices and the
panel.
•Siren Driver: Output that can drive an 8-ohm load and provides intrusion and fire alarm
sounds for partition 1.
•2 Onboard Outputs: Open-collector outputs that can be set up to activate other signalling
devices, based on system events.
•Microphone Input: Input used for 2-way audio when used in conjunction with the Interro-
gator 200 Audio Verification Module.

Concord
5
•8 Supervised Hardwire Zones: Inputs for various hardwired detectors. Zone 8 can be set
up in programming to accept 2-wire smoke detectors.
•Built-In SuperBus 2000 Receiver (60-792-01-95R only): Allows use of up to 16 or 32
319.5 MHz. crystal and/or SAW Learn Mode wireless sensors and touchpads. Also allows
supervision of Supervised Wireless Sirens.
•Phone Line Connection: Allows panel to communicate with central monitoring station and/
or pagers.
SuperBus 2000 Touchpads
The following describes the different touchpads that can be used for system programming and
operation.
•SuperBus 2000 Fixed Display Touchpad: Provides operation control and user-program-
ming access (not installer/dealer programming). Displays system messages and indicates
system status.
•SuperBus 2000 2x16 LCD Touchpad: Provides complete system programming and opera-
tion control. Displays system messages that prompt users for information when needed and
indicates system status.
•SuperBus 2000 2x20 LCD Touchpad: Provides complete system programming and opera-
tion control. Large display shows system messages that prompt users for information when
needed and indicates system status.
•SuperBus 2000 2x20 VFD Touchpad: Provides complete system programming and opera-
tion control. Large fluorescent display shows system messages that prompt users for infor-
mation when needed and indicates system status.
SuperBus 2000 RF Receivers
These receivers expand system wireless zone capacity by 16, 32, or the maximum zones allowed
by the panel. The receivers are compatible with all 319.5 MHz. crystal and SAW Learn Mode
wireless sensors, touchpads, and Supervised Wireless Sirens. You may connect up to 4 receivers
to the panel.
Power Line Carrier Card
Adding this card (which requires that the panel be powered using a Power Line Carrier Trans-
former) adds the following capabilities to the system:
• Allows the use of Supervised Wireless Sirens.
• Allows the use of X10 Powerhouse Lamp Modules for light control and light activation dur-
ing alarms.
Phone Supervision Card
Adding this card allows the panel to check for the correct phone line voltage (partition 1 only),
upon dialing the central station/pager number. The panel can also be programmed to check the
phone line voltage automatically.
Supervised Wireless Siren
Supervised Wireless Sirens plug into any standard electrical outlet and produce status and alarm
sounds. The panel sends signals to the siren through the Power Line Carrier Card and Line Car-
rier Power Transformer, through the AC electrical wiring.
The siren has a built-in transmitter that is used for supervising with the panel. With the siren
transmitter learned into panel memory (panels with receivers), the siren can notify the panel if it
is unplugged, stops receiving panel signals, or has a low backup battery.
SuperBus 2000 Phone Interface/Voice Module
This module allows system access and control using touch-tone telephones, on- or off-site. The
module includes an output for a speaker that sounds system status and alarm voice messages.
SnapCards
The following SnapCards expand the system as described:
•8Z Input SnapCard: Provides eight additional hardwire zone inputs, of which two are ded-
icated for using two wire smoke detectors.

Concord 6
•4 Output SnapCard: Provides four form C relay outputs that can be set up to activate other
signalling devices, based on system events, schedules, or direct control.
•4Z Input/2 Output Combo SnapCard: Provides three hardwire zone inputs, one two wire
smoke detector loop, and two outputs that can be set up to activate other signalling devices,
based on system events, schedules, or direct control.
SuperBus 2000 8Z Input Module (HIM)
Provides eight additional hardwire zone inputs.
SuperBus 2000 4-Relay Output Module (HOM)
Provides four form C relay outputs that can be set up to activate other signalling devices, based
on system events.
Interrogator 200 Audio Verification Module
Adding this module allows central station operators to listen-in and talk to occupants on the pre-
mises to verify the emergency when an alarm report is received.
SuperBus 2000 Cellular Backup Module
Provides central station communication (cellular transmission) a backup to regular phone line(s).
SuperBus 2000 Energy Saver Module (ESM)
Provides a money-saving and convenient way to monitor and control temperatures. The ESM
uses low- and high-temperature limits to save energy by overriding the existing HVAC thermo-
stat. When the ESM is on, temperature limits determine when the heat or air-conditioning turns
on. When the ESM is off, the HVAC thermostat controls heat and air-conditioning.
SuperBus 2000 Automation Module
Provides a connection to a compatible home automation device.
SuperBus 2000 Wireless Gateway Module
Allows users to control and monitor the status of their system from the alarm.com internet web-
site. A wireless data transceiver on the module provides the link to a wireless 2-way paging net-
work for website access.
Installing the
System
This section describes how to install the system control panel. Before starting the installation,
plan your system layout and programming using the worksheets provided in Appendix A.
Installing the system consists of the following:
• Determining the Panel Location
• Determining Total System Power and Wire Length Guidelines
• Mounting the Panel
• Identifying Panel Main Components
• Installing the Optional Power Line Carrier Card
• Installing Optional SnapCards
• Connecting Detection Devices to Panel Zone Inputs
• Connecting Speakers
• Connecting Piezo Sirens
• Connecting an Interrogator 200 Audio Verification Module
• Connecting Alphanumeric and Fixed Display Touchpads
• Installing SuperBus 2000 Modules
• Installing an RJ-31X Phone Jack
• Connecting the Phone Line to the Panel with a DB-8 Cord
• Connecting the AC Power Transformer
• Powering Up the Panel

Concord
7
Note
(A) Class 2, Class 3, and
power-limited fire alarm cir-
cuits must be installed using
FPL, FPLR, FPLP, or substi-
tute cable permitted by the
National Electrical Code
ANSI/NFPA 70. Wire that
extends beyond the cable
jacket must be separated
from all other conductors by
a minimum of 1/4-inch or by
a nonconductive barrier.
OR
(B) Class 2, Class 3, and
power-limited fire alarm cir-
cuit conductors must be
installed as Class 1 or higher
circuits.
Determine the Panel Location
Before permanently mounting the panel, determine panel location using the following guidelines:
• Centrally locate the panel with relation to detection devices whenever possible, to help
reduce wire run lengths and labor.
• Locate the panel where the temperature will not exceed 120°F (49°C) or fall below 32°F
(0°C).
• Avoid running wires parallel with electrical wiring or fixtures such as fluorescent lighting, to
prevent wire runs from picking up electrical noise.
• Mount the panel at a comfortable working height (about 45 to 55 inches from the floor to the
bottom of the panel, as shown in Figure 1).
Figure 1. Determining Panel Location
• Leave space to the left and right of the panel for wiring, phone jack, and mounting optional
modules.
• For wireless panels or hardwire panels that include a SuperBus 2000 RF Receiver, allow at
least 9 inches above the panel cabinet for antennas.
• Allow at least 24 inches in front of the panel to open the panel door.
Total System Power and Wire Length Guidelines
Power
The panel can supply up to 1 amp (1,000 mA) when powered by the 24 VAC, 30 VA transformer
or up to 2 amps (2,000 mA) when powered by the 24 VAC, 50 VA transformer for system
devices.
Wire Length
The total system wire length allowed can vary depending on devices powered by the panel, the
wire length between devices and the panel, and the combined wire length of all devices.
Table 1 describes the maximum wire length allowed between compatible devices and the panel,
including the maximum current draw of each device.
Table 1: Maximum Device Wire Length and Current Draw
Device Max. Wire Length
to Panel
Max. mA
Draw
SuperBus 2000 2x16 LCD Alphanumeric Touchpad 22 ga.—300 ft.
18 ga.—750 ft. 90 mA
SuperBus 2000 2x20 LCD Alphanumeric Touchpad 22 ga.—250 ft.
18 ga.—600 ft. 120 mA
SuperBus 2000 2x20 VFD Alphanumeric Touchpad 22 ga.—250 ft.
18 ga.—600 ft. 120 mA
PANEL
19.25"
12"
12"
21"
45-55"
9"
Antenna
Area
Phone Jack and
Optional Module
Mounting Area
Allow at least 24” in
front of the panel to open
cabinet door and access
panel components.
FLOOR

Concord 8
Table 2 describes the total system wire lengths allowed when installing systems using unshielded
or shielded cable.
Table 3 describes the minimum current draw of each device when the panel is operating only
from the backup battery. For 24-hour backup, the total current draw of all SnapCards connected
to the panel and devices connected to +12V BUS (panel terminal 4) is limited to 90 mA (during
normal standby condition) using a 4.0 AH battery, or 190 mA (during normal standby condition)
using a 7.0 AH battery.
SuperBus 2000 Fixed Display Touchpad 22 ga.—300 ft.
18 ga.—700 ft. 65 mA
SuperBus 2000 RF Receiver 22 ga.—1,100 ft.
18 ga.—2,800 ft. 30 mA
SuperBus 2000 Phone Interface/Voice Module 22 ga.—40 ft.
18 ga.—120 ft. 600 mA
Power Line Carrier Card N/A 110 mA
4 Input/2 Output SnapCard N/A 185 mA*
8Z Hardwire Zone Expander SnapCard N/A 230 mA*
4 Output SnapCard N/A 130 mA*
SuperBus 2000 8Z Input Module 22 ga.—1,800 ft.
18 ga.—4,000 ft. 35 mA
SuperBus 2000 4-Relay Output Module 22 ga.—350 ft.
18 ga.—900 ft. 180 mA
SuperBus 2000 Energy Saver Module 22 ga.—1,600 ft.
18 ga.—4,000 ft. 20 mA
SuperBus 2000 Cellular Backup Module
Standard Power:
22 ga.—15 ft.
18 ga.—40 ft.
1600 mA
High Power
22 ga.—10 ft.
18 ga.—30 ft.
1900 mA
SuperBus 2000 Automation Module 22 ga.—1,500 ft.
18 ga.—4,000 ft. 35 mA
SuperBus 2000 Wireless Gateway Module 22 ga.—40 ft.
18 ga.—90 ft. 1600 mA
Interrogator 200 22 ga.—3,200 ft.
18 ga.—4,500 ft. 10 mA
Interrogator AVM 22 ga.—110 ft.
18 ga.—260 ft. 300 mA
*Maximum current draw for the SnapCards does not include the load which may be
applied to their auxiliary DC supply.
Table 2: Total System Wire Length Allowed
Wire Type Total System Wire
18-gauge, unshielded
18-gauge, shielded
4,500 ft.
3,000 ft.
22-gauge, unshielded
22-gauge, shielded
3,500 ft.
2,200 ft.
Table 3: Minimum Device Current Draw
Device Min. mA Draw
SuperBus 2000 2x16 LCD Alphanumeric Touchpad 15 mA
SuperBus 2000 2x20 LCD Alphanumeric Touchpad 15 mA
SuperBus 2000 2x20 VFD Alphanumeric Touchpad 15 mA
SuperBus 2000 Fixed Display Touchpad 11 mA
Table 1: Maximum Device Wire Length and Current Draw (Continued)
Device Max. Wire Length
to Panel
Max. mA
Draw

Concord
9
After determining panel location, run all necessary wires to that location using the guidelines in
Table 4.
Mounting the Panel
Use the following procedure to mount the panel to the wall or wall studs.
Make sure you are free of static electricity whenever you work on the panel with the cover
open. To discharge any static, first touch the metal panel chassis, then stay in contact with
the chassis when touching the circuit board. Using an approved grounding strap is recom-
mended.
¾To mount the panel (see Figure 2):
1. Open the panel door and remove the necessary wiring knockouts. Be careful not to damage
the circuit board.
2. Feed all wires through wiring knockouts and place the panel in position against the wall.
3. Level the panel and mark the top and bottom mounting holes.
4. Install anchors where studs are not present.
5. Partially insert screws into the two top mounting hole locations, then hang the panel on the
two screws.
6. Recheck for level, insert the two lower screws, and tighten all four mounting screws.
SuperBus 2000 RF Receiver 27 mA
SuperBus 2000 Phone Interface/Voice Module 25 mA
Power Line Carrier Card N/A
4 Input/2 Output SnapCard 20 mA
8Z Hardwire Zone Expander SnapCard 38 mA
4 Output SnapCard 1 mA
SuperBus 2000 8Z Input Module 18 mA
SuperBus 2000 4-Relay Output Module 12 mA
SuperBus 2000 Energy Saver Module 20 mA
SuperBus 2000 Cellular Backup Module 90 mA
SuperBus 2000 Automation Module 30 mA
SuperBus 2000 Wireless Gateway Module 55 mA
Interrogator 200 10 mA
Interrogator AVM 45 mA
Table 4: Wire Requirements
Device Wire Requirements
AC Power Transformer 2-conductor, 18-gauge, 25 feet max
Earth Ground Single conductor, 16-gauge solid, 25 feet max
Telephone (RJ-31X) 4-conductor
Detection Devices 2- or 4-conductor, 18- to 22-gauge, 300-ohms
max loop resistance including device
Speakers 2-conductor, 22-gauge, 175 feet max
2-conductor, 18-gauge, 440 feet max
SuperBus 2000 Devices 4-conductor, 22- or 18-gauge
Interrogator 200 AVM Power and Microphone 4-conductor, 22-gauge, shielded
2-Wire Smoke Detectors
2-conductor, 22-gauge, 330 feet max
2-conductor, 18-gauge, 830 feet max
(based on 10-ohms max loop resistance plus
a 2k-ohm, end-of-line resistor)
Table 3: Minimum Device Current Draw
Device Min. mA Draw
Caution
!

Concord 10
Figure 2. Mounting the Panel
Identify Panel
Components
Before installing devices and making wiring connections, familiarize yourself with the main
panel components. Figure 3 shows the main component locations for the hardwire circuit board
and the main component locations for the combination hardwire/wireless circuit board.
Figure 3. Hardwire and Combination Hardwire/Wireless Circuit Board Main Components
Installing Antennas
Install the antennas (included with panel) into the inside terminal of each antenna terminal block
on the combination hardwire/wireless panel (see Figure 4).
Figure 4. Installing the Antennas
Knockout Knockout
Mounting
Holes
Mounting
Holes
60734G 10D .D SF
Backup Battery Connections
Red
Black
Power Line Carrier
Card Headers
Micro
Processor
EEPROM
SnapCard
Header
Phone
Supervision
Card Headers
Terminal Strip
Programming
Touchpad
Header
60734
g
2 0 6 . s f
Backup Battery Connections
Antenna Terminal Blocks
RedBlack
Power Line Carrier
Card Headers
Programming
Touchpad
Header
Micro
Processor
EEPROM
Phone
Supervision
Card Headers
SnapCard
Header
Terminal Strip
Connect
To Inside
Terminal

Concord
11
Note
For best results, it is recom-
mended that you crimp a
spade lug on the wire end at
the panel and secure the lug
under the circuit board
screw as shown in Figure 5.
Connecting the Panel to Earth Ground
For maximum protection from lightning strikes and transients, connect the lower-left circuit
board screw to earth ground as shown in Figure 5. Use 16-gauge, solid copper wire from an earth
grounded cold water pipe clamp to the panel.
Figure 5. Connecting the Panel to Earth Ground
Note
The lower header has two
jumpers installed from the
factory that must be
removed before installing
the Power Line Carrier Card.
Leave these jumpers in
place if you are not installing
a Power Line Carrier Card.
Installing the Optional Power Line Carrier Card (60-755)
The Power Line Carrier card lets you add Supervised Wireless Sirens for alarm and status sounds
and X10 Lamp Modules for controlling lights.
Install the card on the header pins as shown in Figure 6. No wiring or programming is necessary.
Figure 6. Installing the Power Line Carrier Card
Installing the Optional Phone Supervision Card (60-789)
The Phone Supervision Card allows the panel to check the phone line voltage (partition 1 only),
upon dialing the central station/pager number. The panel can also be programmed to check the
phone line voltage automatically (see “Line Fail Delay”)
Install the card on the header pins as shown in Figure 7.
Figure 7. Installing the Phone Supervision Card
To Water Pipe
Pipe
Ground Clamp
Power Line Carrier Card
Mounting Location
Jumpers
Terminal Strip
Power Line Carrier
Card Headers
Phone Supervision Card
Terminal Strip
Phone Supervision Card Headers

Concord 12
Installing Optional SnapCards
The SnapCard Header on the right side of the panel allows for the installation of one SnapCard.
Install the desired SnapCard onto the panel SnapCard Header and secure it in place with two
screws, included with the card (see Figure 8).
Connect all necessary input/output wiring using the Installation Instructions included with the
card.
Figure 8. Installing a SnapCard into the Panel Expansion Connector
Note
The panel comes with fac-
tory programmed onboard
hardwire zones. Install
2k-ohm, end of line (EOL)
resistors on all unused fac-
tory programmed onboard
hardwire zones. If you don’t
want to install EOL resistors,
delete any unused zones
from memory. See Table 8
for onboard hardwire zone
factory programming.
Connecting Detection Devices to Panel Zone Inputs
Zone inputs 1 through 8 are supervised using included 2k-ohm, end-of-line resistors at the last
device on each circuit. All eight zones accept either normally open (N/O) or normally closed (N/
C) detection devices.
Connecting Intrusion Detection Devices
Figure 9 shows the typical wiring for N/C and N/O door/window intrusion detection and the typ-
ical wiring for a Detection Systems model DS922 (part no. 13-082) motion detector. The mini-
mum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.5 VDC for UL
listed installations).
Note
When using 2-wire smoke detectors on zone 8, the Two-Wire Smoke setting (in program mode) must be
turned on before entering the LEARN SENSORS menu. See ONBOARD OPTIONS—INPUTS in the section
“Programming the Panel” for complete details.
Figure 9. Connecting N/C and N/O Intrusion Detection and Motion Detector Circuits to the Panel
Connecting 2-Wire Smoke Detectors
Zone input 8 can be set up (in program mode) to accept the following 12 VDC, 2-wire smoke
detectors:
•System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH
Connector
SnapCard
Screw Locations
SnapCard
Header
Panel Terminals
2k Ohm EOL
Resistor 49-454
Normally Open
(N/O) Contacts in
Parallel
2k Ohm EOL
Resistor 49-454
Normally
Closed
(N/C)
Contacts
In Series
Zone 2 GND Zone 3
Panel
Terminals
2k Ohm EOL Resistor 49-454
(Locate at Sensor)
+12
BUS GND Zone
7
Motion
Detector

Concord
13
•ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip
switch settings: 1-on, 2-off)
When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with
120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con-
dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in
Figure 10.
Note
The Two-Wire Smoke set-
ting (in program mode) must
be off when using 4-wire
smoke detectors. See
ONBOARD OPTIONS—INPUTS
in the section “Programming
the Panel” for complete
details.
Figure 10. Connecting 2 and 4-Wire Smoke Detectors to the Panel
Connecting 4-Wire Smoke Detectors
Zone input 8 can be used with 4-wire smoke detectors that latch and remain in the alarm state
until power is removed, then restored to the detector. The panel provides this power interruption
from terminal 23 (2-wire smoke power +), provided that zone 8 is learned into sensor group 26
(fire).
Note
Zone 8 must be learned into
sensor group 26 (fire) for
connected smoke detectors
to reset after canceling a fire
alarm.
Table 5 describes the minimum available panel power. Use only 4-wire smoke detectors that
operate at these power limits. Connect up to five Sentrol (ESL) model 449AT (part no. 13-360)
smoke detectors to panel power and zone 8 input as shown in Figure 10.
Use only the 2-wire smoke detector models described above. Alarm signals from other
detectors may not be processed correctly if the panel has lost AC power and is operating
only from the backup battery.
Caution
!
Panel
Terminals
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
2 2 2 3
Z O N E
8
+ 1 2 V
2 W S K
2 0 2 1
G N D Z O N E
7
+
C
O
. . . . . . . .
+- -
C
O
N
O
N
O
+
C
O
. . . . . . . .
+--
C
O
N
O
N
O
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
Model
449AT
Model
449AT
Zone
8
22 23
+12V
2W SMK
2-Wire 4-Wire
Table 5: Panel Minimum Available Power
Min. Voltage/Max. Current Available
8.3 VDC, up to 30 mA total (combined alarm) current
8.1 VDC, up to 40 mA total (combined alarm) current
7.7 VDC, up to 60 mA total (combined alarm) current
7.4 VDC, up to 80 mA total (combined alarm) current

Concord 14
Connecting Speakers
Note
Install all sirens/speakers
indoors, in a concealed loca-
tion.
The panel provides one siren driver output for intrusion (steady), fire (temporal 3), and auxiliary
(on-off-on-off) alarm sounds. This output trips only for partition 1 alarms.
The output can drive a single 8-ohm speaker or multiple speaker circuit of 8-ohms or higher (as
shown in the following speaker wiring diagrams). Compatible speakers are described under
“Connecting Piezo Sirens”.
15-Watt Speaker (13-060)
For exterior siren applications. Connect the speaker to the panel as shown in Figure 11.
Hardwire Interior Speaker (60-528)
For interior siren applications. Connect the speaker to the panel as shown in Figure 11.
Figure 11. Connecting Interior and Exterior Speakers to the Panel
Connect two units to the panel terminals with speakers in series (16-ohms), as shown in
Figure 12.
Caution
!
To avoid disabling the panel speaker output, do not make speaker connections with the
panel powered up.
Connect only the large speaker to the panel terminals 7 and 8 as shown. The smaller
speaker cannot handle to output of terminals 7 and 8. To avoid damaging the speaker, the
smaller speaker should not be connected to terminals 7 and 8.
Caution
!
Splice
Speaker Speaker
2 8-Ohm Speakers in
Series (16 Ohms) 87
Speaker
Not Used
Panel
Terminals
7788
Exterior Interior

Concord
15
Figure 12. Connecting Two Hardwire Interior Speakers w/Dual Speaker Units to Panel Terminals
Connecting Piezo Sirens
Output 1
Onboard output 1 (OUT 1—terminal 9) is an open-collector (switched path-to-ground), program-
mable output that can handle a maximum of 200 mA current sink. The default setting (01614)
activates the output 15 seconds after a police or fire alarm condition occurs. This allows you to
connect a piezo siren without changing the output configuration number in programming. This
output is typically used for exterior siren application.
Output 2
Onboard output 2 (OUT 2—terminal 10) is an open-collector (switched path-to-ground), pro-
grammable output that can handle a maximum of 200 mA current sink. The default setting
(01710) activates the output for status and alarm tones, allowing for a piezo siren connection
without changing the output configuration number. It is typically used for interior siren applica-
tion.
For more information on output configuration numbers, see “Onboard Options Menu”.
Note
Piezo siren connections to
terminal 10 require a 2k
resistor that can be located
at the panel, since it does
not supervise the circuit. If
using an external power
supply instead of panel ter-
minal 4, the supply voltage
must be limited to 9.5 VDC
maximum and the negative
side of the power supply
must be connected to panel
ground (terminal 3).
Exterior Sirens
Hardwire Exterior Siren (13-046)
Note
This siren is not UL approved for use as an outdoor sounding device.
Connect the siren to panel as shown in Figure 13.
Interior Sirens
Interior Piezo Siren (30-006)
Connect the piezo siren to the panel terminals with a 2k-ohm resistor, as shown in Figure 13.
Not Used
Not Used
Speaker
Panel
Terminals 78
This manual suits for next models
3
Table of contents
Other GE Interlogix Security System manuals

GE Interlogix
GE Interlogix CONCORD Express User manual

GE Interlogix
GE Interlogix 60-792-01-95R User manual

GE Interlogix
GE Interlogix Simon User manual

GE Interlogix
GE Interlogix AS500 Series User manual

GE Interlogix
GE Interlogix CareGard 60-883-95R User manual

GE Interlogix
GE Interlogix CONCORD Express User manual

GE Interlogix
GE Interlogix Simon User manual

GE Interlogix
GE Interlogix Security Simon 60-875 User manual

GE Interlogix
GE Interlogix 60-792-01-95R User manual