GE AF-600 FP Series User manual

GE Consumer & Industrial
Electrical Distribution
AF-600 FPTM
LonWorks
Operating Instructions
The instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be
desired or should particular problems arise which are not covered suciently for the purchaser’s purposes, the
matter should be referred to the GE company.
AF-600 FP is trademark of the General Electric Company.
GE Consumer & Industrial
41 Woodford Avenue
Plainville, CT 06062
www.geelectrical.com/drives
130R0464 *MG12T102* DET-627a

1Copyright
1.1 Copyright
1.1.1 Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to GE. By accepting and using this manual the user agrees that the information contained herein will be used
solely for operating equipment from GE or equipment from other vendors provided that such equipment is intended for communication with GE equipment over
a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
GE does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical, hardware or
software environment.
Although GE has tested and reviewed the documentation within this manual, GE makes no warranty or representation, neither expressed nor implied, with respect
to this documentation, including its quality, performance, or fitness for a particular purpose.
In no event shall GE be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained
in this manual, even if advised of the possibility of such damages. In particular, GE is not responsible for any costs, including but not limited to those incurred as
a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third
parties.
GE reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former or present
users of such revisions or changes.
It has been assumed that all devices will be sitting behind a firewall that does packet filtering and the environment has well-implemented restrictions on the
software that can run inside the firewall. All nodes are assumed to be "trusted" nodes.
AF-600 FP LonWorks
1
1

2 Safety
2.1 Safety
2.1.1 Safety Note
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency converter
or network may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this manual, as well as
national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected and
that the necessary time has passed before removing motor and mains plugs.
2. The [STOP/RESET] key on the keypad of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a safety
switch.
3. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be protected
against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is set by par. F-10 Electronic Overload . If this function is desired, set par. F-10 Electronic Overload to data value
[Electronic Thermal Overload trip] (default value) or data value [Electronic Thermal Overload warning]. Note: The function is initialized at 1.16 x rated
motor current and rated motor frequency. For the North American market: The Electronic Thermal Overload functions provide class 20 motor overload
protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been
disconnected and that the necessary time has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external
24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair
work.
Installation at high altitudes
Installation at high altitude:
380 - 500 V, unit sizes 1x, 2x and 3x: At altitudes above 2 km, please contact GE regarding PELV.
380 - 500 V, unit sizes 4x, 5x and 6x: At altitudes above 3 km, please contact GE regarding PELV.
525 - 690 V: At altitudes above 2 km, please contact GE regarding PELV.
Warning against Unintended Start
1. The motor canbe brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is connected
to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which data
can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor
connection for kinetic back up. Refer to the Operating Instructions for further safety guidelines.
AF-600 FP LonWorks
3
2

3Introduction
3.1 Introduction
3.1.1 About this Manual
First time users can obtain the most essential information for quick installation and set-up in these chapters:
Introduction
How to Install
How to Configure the System
For more detailed information including the full range of set-up options and diagnosis tools please refer to the chapters:
How to Control the AF-600 FP
How to Access AF-600 FP Parameters
Parameters
Troubleshooting
Echelon®, LonTalk®, Neuron®, LonWorks®and LonMaker®are registered trademarks of the Echelon Corporation.
3.1.2 Technical Overview
The LonWorks communications structure is similar to that of a local area network (LAN) in that messages are continually exchanged between a number of
processors. A LonWorks system is a local operating network (LON). LON technologyoffers a means for integrating various distributed systems that perform sensing,
monitoring, control, and other automated functions. A LON allows these intelligent devices to communicate with one another through a variety of communications
media using a standard protocol.
LON technology supports distributed, peer-to-peer communications. That is, individual network devices can communicate directly with one another without the
need for a central control system. A LON is designed to move sense and control messages which are typically very short and which contain commands and status
information that trigger actions. LONperformance is viewed in terms of transactions completed per second and response time. Control systems do not require
vast amounts of data, but they do demand that the messages they send and receive are absolutely correct.
Data are transported by means of standard network variable types (SNVTs) which provide a well- defined interface for communication between devices from
different manufacturers. Functional profiles defining the functionality and network variables for a particular family of devices (e.g. frequency converters, pumps
etc.) are also available, and supported by the LonWorks option.
3.1.3 Assumptions
These operating instructions assume, that the GE LonWorks option is used in conjunction with a GE AF-600 FPfan & pump drive. It is also assumed that the installed
controller supports the interfaces described in this document and that all the requirements stipulated in the controller, as well as the frequency converter, are
strictly observed along with all limitations therein.
3.1.4 Hardware
This manual relates to the LonWorks option OPCLON.
AF-600 FP LonWorks
5
3

3.1.5 Background Knowledge
The GE LonWorks Option Card is designed to communicate with any system complying with the FTT and 78Kbps LonWorks standard. Familiarity with this technology
is assumed. Issues regarding hardware or software produced by other manufacturers, including commissioning tools, are beyond the scope of this manual and
are not the responsibility of GE.
For information regarding commissioning tools or communication with a non-GE node, please consult the appropriate manuals.
3.1.6 Related Literature for the AF-600 FP
Title
AF-600 FP Drive Operating Instructions - DET-607 for Low Power Drives or DET-608 for High Power Drives
AF-600 FP Drive Design Guide - To be available
AF-600 FP Drive Programming Guide - DET-620
Please also refer to www.geelectrical.com/drives for additional information.
3.1.7 Abbreviations
ACK AC Knowledge
AAmpere
BOOL Boolean
CC Control Card
CTW Control Word
EMC Electromagnetic Compatibility
FTT Free Topology Transceiver
HF High frequency
Hz Frequency in Hertz
I/O Input / Output
IRMS Output Current Mean Value
LED Light Emitting Diode
LON Local Area Network
LSB Least Significant Bit
MAV Main Active Value
MSB Most Significant Bit
MRV Main Reference Value
N/A Not Applicable
PC Personal Computer
PLC Programmable Logic Controller
PNU Parameter Number
RPM Revolutions Per Minute
RTC Real Time Clock
sSeconds
SCPT Standard Configuration Property Types
SNVT Standard Network Variable Type
SINT Signed integer
STW Status Word
VVoltage
VSD Variable Speed Drive
UINT Unsigned integer
UNVT User-defined Network Variable Type
XIF Extended Interface File
AF-600 FP LonWorks
6
3

4 How to Install
4.1 How to install
4.1.1 The LonWorks Option
The LonWorks option is equipped with two termination switches, S300 and S301, enabling double termination when using bus topology.
The push-button switch O400, activates the Service-Pin function.
The LEDs:
LED label Description
MS Service LED (red)
NS Status LED (green)
The neuron ID is printed on the option in text and in barcode (code 39).
AF-600 FP LonWorks
7
4

4.1.2 Cabling
The Free Topology Transceiver (FTT) system is designed to support free topology wiring and accommodates bus, star, loop or any combination of these topologies.
The LonWorks option is equipped with the FT-X1 transceiver for improved EMC performmance. Flexible wiring capability simplifies system installation and makes
it easy to add nodes for system expansion.
The figures below illustrate five different network topologies.
AF-600 FP LonWorks
8
4

4.1.3 Network Termination
Dependent on the type of topology, at least one of the connected nodes must be terminated (52.5Ω). The option has two built-in termination circuits which are
activated by the terminator switches S300 and S301.
If termination is provided elsewhere in the network, the termination switches should be OFF. If a double-terminated bus topology is used, the first and the last
node should be double-terminated (105Ω).
Termination switch positions are shown in the table below.
Termination type S 300 S 301
No termination (factory setting) OFF OFF
Double termination (105 Ω)ONOFF
Single termination (52.5 Ω)ON ON
4.1.4 Connecting the Bus Line
Connect bus wire NET A to terminal 79 and NET B to 80 of the terminal connector.
Terminal Connection
79 NET A*
80 NET B*
61 Drain**
NB!
*Note: For free topology wiring the option is insensitive to the polarity of the bus-terminals.
NB!
**Note: Term. 61 (Drain) offers a RC-junction to ground and should not be used for grounding of shielded cable. Ground the shielded cable at the de-coupling
plate by removing cable insulation at contact point.
4.1.5 Maximum Cable Lengths
Network topology Maximum cable length
Free topology without repeater 500 m
Free topology with one repeater 1000 m
Free topology maximum device-to-device 500 m
Bus topology single terminated 500 m
Bus topology double terminated without repeater 2700 m
Bus topology double terminated with one repeater 5400 m
Bus topology maximum stub length 3 m
Use of the same cable type throughout the entire network is recommended in order to avoid impedance mismatch.
4.1.6 System Specifications
Up to 64 FT-X1/FTT-10 transceivers, are allowed per network segment.
NB!
Note: The Free Topology LonWorks runs at 78 Kbps only.
AF-600 FP LonWorks
9
4

4.1.7 EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operationof the LonWorks network. Additional EMC information is available
in the AF-600 FP Design Guide.
NB!
Relevant national and local regulations, for example regarding protective earth connection, must be observed.
The LonWorks communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the
other. Normally a distance of 200 mm (8 inches) is sufficient, but maintaining the greatest possible distance between the cables is recommended, especially where
cables run in parallel over long distances. When crossing is unavoidable, the LonWorks cable must cross motor and brake resistor cables at an angleof 90 degrees.
NB!
It is highly recommended to use suitable screened cable for any LonWorks installation!
AF-600 FP LonWorks
10
4

4.1.8 LED Behaviour
MS: Service LED (red)
Situation LED Description
Configured state (Nornal operation) ½ sec. ON, then continously OFF The node is configures and running normally
Non configures state Flashing ½ Hz Node is not configures but has an application.
Proceed with loading node.
Applicationlessstate 1 sec. ON, 2 sec. OFF, then continuosly ON Node has no application, the LonWorks option
needs replacing or reprogramming
Watchdog resets Short flash about each 3 sec. Indicates problem with application. The Lon-
Works option needs replacing
Faulty hardware Steady ON or OFF The LonWorks option needs replacing
NS: Status LED (green)
Situation LED Description
Node configured Steady ON The node is configured and running
normally
Wink service Flashing ½ Hz for 20 sec. Wink service activated in order to
identify node.
AF-600 FP LonWorks
11
4

4.1.9 How to Install Option in Frequency Converter - Open Chassis/IP20
Items required to install a network option in the frequency converter:
-The network option
-Network option adaptor frame for the AF-600 FP. This frame is deeper than the standard frame, to allow space for the network option beneath
-Decoupling plate (only for unit sizes 11 and 12)
AF-600 FP LonWorks
12
4

Instructions:
-Remove keypad panel from the AF-600 FP
-Remove the frame located beneath and discard
-Push the option into place. Two positions are possible, with cable terminal facing either up or down
-Push the network option adaptor frame for the AF-600 FP into place
-Replace the keypad and attach cable
-On unit sizes 11 and 12 with cable terminal facing up: Fasten the cable onto the de-coupling plate (the AF-600 FP top surface has pre-drilled threaded
holes for attaching the de-coupling plate to the unit).
AF-600 FP LonWorks
13
4

5 Configuration of the System
5.1 Configuring the System
5.1.1 How to Configure the LonWorks Network
The LonWorks option card contains a Neuron chip with a unique address. This Neuron ID is a 48 bit number that identifies each Neuron chip manufactured.
Addressing nodes on the LonWorks network is performed at the time of installation using an installation tool or network management tool (e.g. LonMaker).
Addressing requires the retrieval of the Neuron ID for the node.
There are several methods by which the network software can retrieve the Neuron ID and address the node:
1. Service Pin – The push-button service switch sends the Neuron ID over the network.
If the network software prompts the action, press the Service Pin switch (O400) to transmit the Neuron ID over the network. Please refer to the How to
Install section for the location of the Service Pin switch.
2. Query and Wink - Upon receiving a Wink command, both LED’s flashes (½ Hz for 20 sec.) so the installer can locate the node. The option sends out its
Neuron ID over the network in response to the query command.
3. Neuron ID Label – The installer can manually enter the Neuron ID during installation. The Neuron ID can be found on the label of the option in text and
barcode.
Resource Files
A LonMark interface file (.XIF file extension) provides the host processor with device information. Using this file it is possible to design a LonWorks network without
the adjustable frequency converter being physically present. Other resource files are:
• Type file (.typ file extension)
• Format file (.fmt file extension)
• Language description file (.eng, .enu and other file extensions)
The resource files can be downloaded from the web site www.geelectrical.com/drives.
5.1.2 Functional Profiles
LonMark functional profiles are used to describe in detail the application layer interface, including the network variables, configuration properties, and commonly
used control functions.
AF-600 FP LonWorks
15
5

5.1.3 Drive VSD Profile
The drive VSD Profile describes all GE drive specific network variables.
Input variables
Variable Function Variable Name SNVT type Profile AF-600 FP Par.
Start/Stop nviStartStop SNVT_switch Drive VSD CTW/reference
Control word nviControlword SNVT_state Drive VSD CTW
Reset fault nviResetFaut SNVT_switch Drive VSD CTW
Reference [%] nviRefPcnt SNVT_lev_percent Drive VSD Reference
Reference [Hz] nviRefHz SNVT_freq_hz Drive VSD Reference
CL Setpoint 1 nviSetpoint1 SNVT_lev_percent Drive VSD CL-21
CL Setpoint 2 nviSetpoint2 SNVT_lev_percent Drive VSD CL-22
CL Setpoint 3 nviSetpoint3 SNVT_lev_percent Drive VSD CL-23
Bus feedback 1 nviFeedback1 SNVT_lev_percent Drive VSD O-94
Bus feedback 2 nviFeedback2 SNVT_lev_percent Drive VSD O-95
Bus feedback 3 nviFeedback3 SNVT_lev_percent Drive VSD O-96
Digital/relay outputs nviDigiOutput SNVT_state_64 Drive VSD E-90
Analog output (42) nviAnOut1 SNVT_lev_percent Drive VSD AN-53
Analog output (X30/8) nvi101AnOut1 SNVT_lev_percent Drive VSD AN-63
Analog output (X42/7) nvi109AnOut1 SNVT_lev_percent Drive VSD AO-43
Analog output (X42/9) nvi109AnOut2 SNVT_lev_percent Drive VSD AO-53
Analog output (X42/11) nvi109AnOut3 SNVT_lev_percent Drive VSD AO-63
Setting of RTC nviTimeStamp SNVT_time_stamp Drive VSD K-70
Parameter access command nviParamRequest UNVT_param_request Drive VSD -
AF-600 FP LonWorks
16
5

Output variables
Variable function Variable name SNVT type Profile AF-600 FP Par.
Status word nvoStatusword SNVT_state Drive VSD DR-03
Drive output [%] nvoOutputPcnt SNVT_lev_percent Drive VSD DR-05
Drive output [Hz] nvoOutputHz SNVT_freq_hz Drive VSD DR-13
kWh counter nvoDrvEnrg SNVT_elec_kwh_l Drive VSD ID-02
DC Link Voltage nvoDCVoltage SNVT_volt Drive VSD DR-30
Motor thermal nvoTempMtr SNVT_lev_cont Drive VSD DR-18
Inverter Thermal nvoTempInvrtr SNVT_lev_cont Drive VSD DR-35
Closed loop feedback nvoFeedback SNVT_count_inc_f Drive VSD DR-52
Fanbelt broken nvoBrokenBelt SNVT_switch Drive VSD DR-93
Alarm flag nvoAlarm SNVT_switch Drive VSD DR-90
Warning flag nvoWarning SNVT_switch Drive VSD DR-03
Alarm word nvoAlarmword SNVT_state_64 Drive VSD DR-90 + DR-91
Warning word nvoWarningword SNVT_state_64 Drive VSD DR-92 + DR-93
Extended statusword nvoExtendedStatusword SNVT_state_64 Drive VSD DR-94 + DR-95
Digital inputs nvoDigitInput SNVT_state_64 Drive VSD DR-60
Analog Input (53) nvoAnIn1 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent Drive VSD DR-62
Analog Input (54) nvoAnIn2 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent Drive VSD DR-64
Analog Input (X30/11) nvo101AnIn1 SNVT_volt/SNVT_lev_percent Drive VSD DR-75
Analog Input (X30/12) nvo101AnIn2 SNVT_volt/SNVT_lev_percent Drive VSD DR-76
Analog Input (X42/1) nvo109AnIn1 SNVT_volt/SNVT_temp_p/SNVT_lev_percent Drive VSD LG-30
Analog Input (X42/3) nvo109AnIn2 SNVT_volt/SNVT_temp_p/SNVT_lev_percent Drive VSD LG-31
Analog Input (X42/5) nvo109AnIn3 SNVT_volt/SNVT_temp_p/SNVT_lev_percent Drive VSD LG-32
Parameter access cmd. nvoParamResponse UNVT_param_response Drive VSD -
AF-600 FP LonWorks
17
5

5.2 Network Variable Description
5.2.1 - Drive VSD Profile - Input
Start/Stop
Variable
name:
SNVT
type: State: Value: Command:
nviStartStop SNVT_switch 0 (False) Any Stop (0x043C)
1 (True) 0 Running 0% (0x047C)
1 (True) 1-200 Running 0.5 to 100.0%
1 (True) 201-255 Running100%
0xFF (default) Any AUTO (invalid, no action)
This variable sends a Start or Stop command to the frequency converter and a reference (0 - 100 %)
NB!
The reference value of nviStartStop will only be valid if both nviRefPcnt and nviRefHz are = 0
Control Word
Variable
name:
SNVT
type: State:
nviControlword SNVT_state Boolean 1 bit x 16
The input network variable nviControlWord is a 16-bit word providing additional operational control of the frequency converter.
For more information about the Control word, please refer to the GE Drive Control Profile section.
NB!
Please note in the representation of the Control Word in the LonMaker Browser, the LSB is to the far left.
Reset fault
Variable
name:
SNVT
type: State: Value: Command:
nviResetFault SNVT_switch 0 (False) Any No reset
1 (True) Any Reset (0x04B)
0xFF (default) Any AUTO (invalid, no action)
This variable sends a reset command to the frequency converter via bit 7 in the Control Word (0x04BC), see the GE Drive Control Profile section.
AF-600 FP LonWorks
18
5

Reference [%]
Variable
name:
SNVT
type: Value:
nviRefPcnt SNVT_lev_percent Min. Max. Resolution:
-163.840 % +163.830 % 0.005 %
This variable sends the speed reference to the frequency converter. It represents a percentage of the reference range of the frequency converter.
In closed loop operation the reference is interpreted as the setpoint.
Reference [Hz]
Variable
name:
SNVT
type: Value:
nviRefHz SNVT_freq_hz Min.: Max.: Resulution:
0.0 Hz 6,553.5 Hz 0.1 Hz
This variable sends the speed reference to the frequency converter in Hz, in open loop mode.
In closed loop mode it is used as the Set-point.
Closed Loop Set-point 1-3
Variable
name:
SNVT
type: Value:
nviSetpoint1-3 SNVT_lev_percent Min.: Max.: Resulution:
-163.840 % 163.830 % 0.005 %
This variable sends up to 3 different set-points to the frequency converter via the bus.
NB!
Please refer to section Reference Handling for more information
Bus Feedback 1-3
Variable
name:
SNVT
type: Value:
nviFeedback1-3 SNVT_lev_percent Min.: Max.: Resulution:
-163.840 % 163.830 % 0.005 %
This variable sends up to 3 different feedback signals to the frequency converter via the bus.
NB!
For more information on how to manage multiple set-points and feedback sources, please refer to AF-600 FP Programing Guide DET-620.
AF-600 FP LonWorks
19
5
Other manuals for AF-600 FP Series
10
Table of contents
Other GE DC Drive manuals

GE
GE AF-600 FP Series User manual

GE
GE AF-600 FP Series User manual

GE
GE AF-650 GP Series Operating instructions

GE
GE AF-650 GP Series User manual

GE
GE AF-600 FP BACnet User manual

GE
GE 6KLP23001X9A1 User manual

GE
GE D20A6 User manual

GE
GE AV-300i User manual

GE
GE AF-600 FP Series User manual

GE
GE Ecomagination AF-600 FP Operating instructions

GE
GE VAT200 User manual

GE
GE D8R4 User manual

GE
GE AF-650 GP Series User manual

GE
GE AF-60 LP Operating instructions

GE
GE AF-650 GP Series Operating instructions

GE
GE AF-650 GP Series User manual

GE
GE UltraMax User manual

GE
GE Druck DPI 841 User manual

GE
GE Fuji Electric MICRO-SAVER AF-300 User manual

GE
GE AF-650 GP Series Guide