
Power Circuit Breakers, GEK-731O
gage the stationary bar in the equipment enclosure.
The opening of these fingers against the force of the
springswill cause a noticeablyhigher load require-
ment in the racking effort. This will very quickly
fali off to a lesser force requirement to the end of
travel, at which point a stop will be encountered.
About three handle turns will be required between
the peak force requirement and reaching the stop
which ends the movement. Upon reaching the stop,
the handle should be removed without any rever-
sal of the handle motion. Approximately 24 turns
on the handle are required for the complete rack-
ing cycle.
15. The first time the breaker is introduced into
the enclosure, it should be completely withdrawn
and the marks of the disconnect fiagers on the
grease on the stationary bars examined. These
tracks marks should indicate no less than 1/4-inch
engagement. The maximum amount that can be
attained is g/16-inctr.
BREAKER WITHDRAWAL
1. Trip the breaker open, hold in the trip but-
ton, and move the sliding cover in the escutcheon
aside to the right.
2. Engage the racking handle and crank in a
counterclockwise direction.
3. ApproximateLy 24 turns of the handle wiII
complete the racking-out operation and bring the
breaker to the disconnected position. This will be
shown on the indicator in the compartment and will
be evident to the person operating the mechanism
because a stop will be encountered beyond which no
further movement can be made. Towards the end
of the racking cycle, the "closing spring interlock"
willbe activated. This willcause theclosing spring
to discharge, but will not close the breaker.
4. To withdraw the breaker completely, open the
latches onthe ends ofthe rails, and pull thebreaker
out of the compartment. The breaker may now be
Iifted off the rails by the lifting device.
STATIONARY BREAKERS
Stationary breakers are intended for separate
mounting on a framework or switchboard panel, or
in an enclosure of the customerts own design and
construction. They are the same breaker unit as
the drawout type; however, they do not have the
drawout features, namely, the racking mechanism
and automatic disconnects and interlocks.
Careful consideration should be given to the se-
lection of a location for mounting stationary break-
ers. They should be situated so that they can be
easily reached for operation and maintenance, with
enough surrounding free space so that working in
the area is not troublesome. If it is possible, the
Iocation chosen should bedry andclean andnot sub-
ject to extreme variations of temperature.
Mounting the breaker involves bolting the frame
of the breaker to its supporting structure within the
switchboard or enclosure, making power connec-
tions tothebreaker studs, andmaking control power
connections to the breaker terminal board and arx-
iliary switch terminals, if these are required. Four
mountingholes are required forthe hardware which
fastens the frame to its support.
These mounting holes must all be in the same
vertical plane. If they are not, strain may be im-
posed on the breaker structure which could ad-
versely a-ffect the operation of the breaker. The
ouiline drawing which is furnished with the breaker
gives information on preparing a mounting structure
and a cover or door suitable for preventing access
to live parts of the breaker.
Another requirement of the supporting structure
for the breaker is that it be rigid enough to with-
stand the forces that result from high momentary
and short-circuit currents to which thebreaker may
be subjected. Connectingbus or cable must also be
supportedadequately to resist these forces. points
of support for buswork or cable must be close
enough to the breaker so that no appreciable strain
is imposed on the breaker's studs.
Manual breakers must be located so that clear-
ance is provided for the sweep of the handle when it
is operated. This requirement will be 11 inches
to the right from the centerline of the breaker, or
2-l/2 arches beyond the right edge of the breaker
frame.
Since eachupper studof thebreaker is composed
of two separate members, the connections to the
stud must provide a solid connection across the two
parallel stud members, as well as an external con-
nection. All stationary breakers will be shipped
with connector bars already fastened to both upper
and lower studs. These bars will accommodate
cable connectors or busbars. If an external bar
connects across both halves of the upper studs, the
connectorb:rrs may bedispensed with. hthis case,
the end of the connecting bus should extend in to-
wards the breaker base no more than 5/8-inctr be-
yond the centerline of the fastener hole.
Control connections on stationary breakers are
made to a terminal board located in the upper left
frontarea of thebreaker (front view). The terminal
board may have 6, 10 or 14 points. This will be
governedby the requirements of the control scheme.