GE IAC51A User manual

INSTRUCTIONS
TIME-OVERCURRENT RELAYS
TYPES
IAC51A
IAC52A
IAC51B
IAC51R
IAC52
B
GENERAL
_
ELECTRIC
GEH-1753J

GEH-1753
Time
Overcurrent
Relays
Type
IAC
2
TOP
PIVOT
________
'-
TAP
PLUG
-----~~1f~II
..
~~~~~
....
--~~~;=:
SEAL-IN
UNIT
HOLDING COIL
/""---TAP
BLOCK
SEAL-IN
~--"--_f_':-=Hrr_TI
ME
DIAL
TARGET-
._------+::-:
SEAL-IN UNIT
STATIONARY
CONTACT, LEFT
SEAL-IN
UNIT
STATIONARY
CONTACT,
RIGHT
SEAL
-IN
MOVING
CONTACT
ASSEMBLV--
-, •
It
'III
"'M"~
Io;f'S
~
,!"'$T"'t.lLl1Qlt,fa
_:
I
ll1i~
•
""""'lO-V!>
UN!T
l-~
~~,
,_.
=
!I
DISK
AND
SHAFT
LOWER
JEWEL
SCREW
<&.1
A -
(8006996)
Front
View
B -
(8006997)
Rear
Vie,,,
DISK
DRAG
"---1--
MAGNET
Figure
1.
The
1nduction
lnit
for
Type
lAC
Relayso

TIME-OVERCURRENT
TYPE
lAC RELAYS
INTRODUCTION
Type
Contact
Instantaneous
AC
Trip
Induction
Outline
&
Internal
Circuits
Unit
IAC51A(-)A One
NQ
IAC51B(-
)A
One
Yes
IAC51R(-
)A
One
Yes
IAC52A(-)A Two
No
IAC52B(-
)A
Two
Yes
The
Type
lAC
relays
comprise
a
group
of
relays
that
are
employed
to
protect
against
overcurrent
on
single-phase
and
polyphase
circuits.
The
various
relays
in
this
lAC
group
are
identified
by
model
numbers,
and
the
relays
differ
in
the
number
of
circuits
they
close,
the
length
of
time
delay
and
features
that
are
determined
by
the
characteristics
of
the
protected
circuit.
These
relays
consist
of
an
induction
unit
or
an
induction
unit
with
an
instantaneous
unit
which
Unit
Unit
Panel
Drilling
Connection
No
One
Fig.
18
Fig.
11
No
One
Fig.
18
Fig.
12
Yes
One
Fig.
18
Fig.
13
No
One
Fig.
18
Fig.
14
No
One
Fig.
18
Fig.
15
permits
instantaneous
tripping
for
extremely
high
currents,
or
an
induction
unit
with
an
a-c
tripping
unit
for
use
where
d-c
power
is
unavailable
or
a-c
tripping
is
preferred.
Since
practically
all
lAC
relays
are
composed
of
various
combinations
of
the
above
-
that
is,
the
induction
unit,
the
instantaneous
unit
and
the
a-c
tripping
unit
-
they
are
for
con-
venience,
described
separately
in
the
following
text.
The
above
table
indicates
the
units
comprising
each
type
and
also
lists
the
internal
connections
and
out-
line
and
panel
drilling
diagrams.
INDUCTION
UNIT
INTRODUCTION
The
induction
unit
is
the
basic
unit
in
all
lAC
relays.
Fig.
1
shows
the
induction
unit
mounted
in
the
cradle.
These
units
are
of
the
induction-disk
construction
type.
The
disk
is
actuated
bya
current
operating
coil
on a
laminated
U-magnet.
The
disk
shaft
carries
the
moving
contact
which
completes
the
alarm
or
trip
circuit
when
it
touches
the
station-
ary
contact
or
contacts.
The
disk
shaft
is
restrained
by a
spiral
spring
to
give
the
proper
contact-closing
current
and
its
motion
is
retarded
by a
permanent
magnet
acting
on
the
disk
to
give
the
correct
tilne
delay.
There
is
a
seal-in
unit
mounted
on
the
front
to
the
left
of
the
shaft.
This
unit
has
its
coil
in
series
and
its
contacts
in
parallel
with
the
main
contacts
such
that
when
the
main
contacts
close
the
seal-in
unit
picks
up
and
seals
in.
When
the
seal-in
unit
picks
up,
it
raises
a
target
into
view
which
tatches
up
and
remains
exposed
until
released
by
pressing
a
button
beneath
the
lower
left
corner
of
the
cover.
APPLICATIO
N
The
induction
unit
is
the
main
unit
in
all
lAC
relays,
supplying
the
inverse
time
delay
character-
istics
of
the
relay
and
sounding
an
alarm
or
tripping
the
breakers
for
overload
currents
which
cause
it
to
close
its
contacts.
OPERATING
CHARACTERISTICS
The
induction
unit
may
have
one
or
two
circuit-
closing
contacts
which
close
as
the
current
increases
to
the
pick-up
value
as
set
on
the
tap
block.
The
time
delay
in
closing
the
contacts
is
determined
by
the
setting
of
the
time
dial
(Fig.
1).
The
time-current
characteristics
are
shown
in
Fig.
2.
RATINGS
The
induction
element
is
designed
to
use
any
one
of
three
operating
coils,
each
having
a
different
combination
of
taps
as
follows:
4,
5~
6,
8,
10,
12
and
16
amperes;
1.5,
2.0,
2.5,
3.0,
4.0,
5.0
and
6.0
amperes;
0.5, 0.6,
0.8,
1.0,
1.2,
1.5
and
2.0
am-
peres.
Tilese
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possihle
contingency
to
be
met
in
connection
with
installation,
operation
or
maintenance.
Should
further
information
he
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
purchaser's
purposes,
the
matter
should
be
referred
to
the
General
Electric
Company.
To
the
extent
required
the
products
described
herein
meet
applicable
ANSI,
IEEE'
and
NEMA
standards;
but
JlO
such
assurance
is
gi
ven
wi
th
respect
to
local
codes
and
ordinances
because
they
vary
greatly.
3

GEH-1753
Time
Overcurrent
Relays
Type lAC
4
20
10
S
•
7
I
~
II
Z
o 4
~
III
3
2;i
~
2
1
.S
.S
.1
.1
.11
.4
.3
.2
.1
.All
.DB
.07
.01
.05
.04
.03
.02
.01
~
1\ \
\\1\.
\\.
I\.'\.
1\,
1\.'\
l"'-.
\\
I\.'-,
_"'-.
:"-
'\
'\ '\
"-
\ '\.
'\
I\.
'"
"-
\. "-
."
,
"'-.
'\
"-
""
I'-..
\
~
1"'-
"-
r--
.......
I'-..
i"-
f'...
I'--.
\.
"-
"-I"-
r--
.....
'"
i'
f'...
r--~
l'----
\
"-
['-,1'-
f'-.
........
1'--1'-
~
r-.::
r--
r-......
r-
f'-
f'....
t-
1-",
10
f--
~
I"
l"
f'-.
1'1'-
~
.............
r-..
r-......
r-
t"'-t--
9
t'-
I'--
r-.
t-
r-
I-
I'-t"'-
8
f"
I"-r--
1'--1'
r-..
r-
t--.
l-
t-- 7
f--
"
"-
r---
r::--,
f--
'\.
......
I'-.
-......
---
r-
I~
f--
I"-
~t--
t"'-t--
II)
CJI
f--
"-
I"--
..............
---
I"-
IV
c
I\,
'"
I'-
I"---t--
1"-4
.-
f--
-
I--
I-
"-
.............
t-
-
f--
"
l"
--. 3
Q)
"-
r--
r-
(f)
f--
I
.......
I--
.......
1-,....
1"-2
-
I--
r--",
----
c
.-
I--
r---.
--
r--
r-
0
r-
t-r-
I--
r--- I
Q)
t--
l"-
E
f--
rl"-
~
.-
t-
.1
.1
.1
.8
.8
1 2 3 4
II
• 1
••
10
20
30 40 50 80
7080
DO!
MULTlPLES
OF
RELAY
TAP
SETTING
Fig.2.
(088880269
[3)
Time-current
Curves
of
Type
lAC
Relays
with
Inverse-time
Characteristics

The
current-closing
rating
of
the
contacts
is
30
amperes
for
voltages
not
exceeding
250
volts.
The
current-carrying
ratings
are
affected
by
the
selection
of
the
tap
on the
target
and
seal-in
coil
as
indicated
in
the
following
table:
DUAL
RATED
0.2/2.0 0.6/2.0
0.2
2.0
0.6
2.0
Carry
30
amps
for
(sec)
0.05
2.2
0.5
3.5
Carry
10
amps
for
(sec)
0.45
20
5.0
30
Carry
continuously
(amp)
0.37
2.3
1.2
2.6
Minimum
operating
(amp)
0.2
2.0
0.6
2.0
Minimum
dropout
(amp)
0.05
0.5
0.15
0.5
DC
resistance
(ohms)
8.3
0.24
0.78 0.18
60
hertz
impedance
(oh'TIs) 50
0.65
6.2
0.65
50
hertz
impedance
(ohms)
42
0.54
5.1
0.54
If
the
tripping
current
exceeds
30
amperes,
an
auxiliary
relay
should
be
used,
the
connections
being
such
that
the
tripping
current
does
not
pass
through
the
contacts
or
the
target
and
seal-in
coils
of
the
protective
relay.
48
45
4.
39
}6
,
3J
--
30
¥
0
/
V
l 27
T
A
" 24
E
21
18
15
12
9
6
I VL
~
~
V/
V
~
/ V
/;
V
I
~
/I
V
,
~
:::::::::
~
~
::::-
3
0
~
-
~
~
Time
Overcurrent
Relays
Type lAC GEH-1753
BURDENS
Burdens
for
the
standard
coils
are
given
in
the
following
table.
These
are
calculated
burdens
at
five
amperes
based
on
burden
of
minimum
tap.
Volt-ampere
burdens
for
the
lowest
tap
on
any
of
the
three
coils
can
be
determined
for
any
value
of
current,
up
to
20
times
tap
setting,
from
Fig.
3.
Coil
Amperes
4-16
1.5-6.0
0.5-2.0
I
/
/
/
/
/ /
'i
/
/'
/'
/ V
/
./
L V
V
f-;:::
~
::--
~
~
-
--:::::
""""'"
Freq.
60
.....
50
'"
60
50
25
60
50
25
60
50
25
TAP
RANGE
.5-2.0
TAP
25"']
RANGE
60~
1.
5-6.
0
50",
ANPS.
]
TAP
60"'jRANGE
25",
4-16
50ft.
ANPS.
Tap
Volt-
Imp.
PF
Amps
Ohms
4.0
8.8
0.35
0.29
4.0
8.0
0.32 0.31
4.0
7.5
0.30
0.36
1.5
59.0
2.36
0.26
1.5
52.0
2.08
0.28
1.5
48.0
1.92 0.34
0.5
530.0
21.2 0.26
0.5
470.0
18.8
0.28
0.5 430.0 17.2
0.34
o 4 6 8
10
12
14
16
18
20
MULTIPLES
OF
MINIMUM
TAP
SETTING
SATURATION
CuRVES
AT
VARIOUS
FREQUENCIES
FOR
3
TAP
RANGES
OF
THE
TYPE
IACS1A
RELAY
LOWEST
TAP
USEO
IN
ALL
CASES
Fig.
3.
(K-6306891-1)
Saturation
Curves
for
Lowest
laps
',f
the
Induction
Unit
of
Type
lAC
Relays
\vith
Inverse-time
r,haractcrislics.
5

GEH-1753
Time
Overcurrent
Relays
Type
IAC
50
51
DEVICE FUNCTION NUMBERS FOR USE
WITH
ALL
EXTERNAL DIAGRAMS
Instantaneous Unit
Overcurrent,
Relay,
Type
IAC
51N -Ground
Overcurrent
Relay,
Type lAC
52
Power
Circuit
Breaker
SI
Seal-in
Unit, with
Target
TC
A
!
Trip
Coil
Auxiliary
contact,
closed
when
breaker
closes.
A-C
BUS
1
2
~
.li
~+~
~
j
M.l
d I
~
"
.~
t-
~ ~
rRIPPI~G
-~
}l::1..
~ACTOR-
;
-L
l
~
t;T
-=-
1 1
Fi
6. 5
(K6375668-l)
External
Connections
of
Three
Type IAC51A
Relays
used
in
Conjunction
with
Tripping
Reactors
for
Protection
of
aTThree-Phase
Circuit.
6
A_C
BuS
1"I~rRIP
BUS
W ll::2
ll=l
ill
ll.::l
I-I
28
t t
L
52
#
Fig.
4
(K-6375667-2)
External
Connections
of
Three
Type IAC5lA
Relays
used
for
Phase-to-Phase
and
Ground
Overcurrent
Portection
of
a
3-Phase
Circuit.
A-C
Bus
Fig.
6
(K-6375669-6)
External
Connections
of
Three
Type IAC5lR
Relays
used
for
3-Phase
Circuit
Protection.

Time
Overcurrent
Relays
Type
IAC
GEH-1753
INSTANTANEOUS
UNIT
INTRODUCTION
The
instantaneous
unit
is
a
small
instantaneous
hinge-type
unit
which
may
be
mounted
on
the
right
front
side
of
the
induction
unit
(See
Fig.
7).
Its
contacts
are
normally
connected
in
parallel
with
the
contacts
of
the
main
unit.
Its
coil
is
connected
in
series
with
the
operating
coil
of
the
main
unit.
When
the
current
reaches
apredetermined
value,
the
instantaneous
unit
operates,
closing
the
contact
[ircuit
and
raising
its
target
into
view.
The
target
latches
in
the
exposed
position
until
released
by
pressing
the
button
beneath
the
lower
left-hand
corner
of
the
relay
cover.
APPLICATION
The
instantaneous
unit
is
used
on
certain
IAC
relay
models
to
provide
instantaneous
tripping
for
current
exceeding
a
predetermined
value.
OPERATING
CHARACTERISTICS
The
instantaneous
element
operates
over
a 4
to
1
range
and
has
its
calibration
stamped
on a
scale
;
..
OPEAATING
COIL
..
TARGET
STATIONARY
CONTACTS
Fig.
7.
(8006998)
Type
lAC
Relay
with
an
Instantaneous
Unit.
mounted
beside
the
adjustable
pole
piece.
Time-
current
characteristics
are
shown
in
Fig.
10.
RATINGS
The
instantaneous
unit
is
designed
to
use
either
of two
coils
having
pickup
ranges
of
10
to
40,
and
20
to
80
amperes
respectively.
The
current-closing
rating
of
the
contacts
is
30
amperes
for
voltages
not
exceeding
250
volts.
BURDENS
Burden
data
on
the
instantaneous
unit
coils
are
given
in
the
following
table:
Coil
Freq.
Amp.
Volt
Imp.
Amp
Ohms
10-40
60 5
0.83
0.033
50 5
0.80
0.032
25 5
0.65
0.027
20-80
60 5 0.21
0.008
50 5
0.20
0.008
25 5
0.15
0.007
SHORTING
COIL
---+-+--1:
MAl
N
-~~-.'--f---J
COIL
•
..
-=
Fig.
8.
(8007060)
Type
lAC
Relay
with
an
A-C
Tripping
Unit.
PF
0.95
0.95
0.98
0.95
0.95
0.98
-
7

8
GEH-1753
Time
Overcurrent
Relays
Type
IAC
A-C
TRIPPING
UNI1
INTRODUCTION
The
a-c
tripping
unit
is
a
Type
REA
relay
unit
designed
to
energize
a
circuit
breaker
trip
coil
from
its
assoc
iated
current
transformer
upon
the
operation
of
the
main
unit
of
the
IAC
relay.
It
transfers
the
current
from
the
secondary
of
the
current
trans-
former
into
the
trip
coil
and
removes
the
current
from
the
trip
coil
when
the
breaker
trips.
The
tripping
unit
is
mounted
on
the
rear
of
the
frame
opposite
the
tapped
operating
coil
of
the
induction
unit
(see
Fig.
8).
The
operation
of
this
unit
is
illustrated
in
Fig.
9.
The
secondary
current
circulates
through
the
induction
unit
current
coil
and
the
main
coil
of
the
REA
auxiliary
tripping
unit,
returning
through
the
REA
contacts
to
the
current
transformer.
Normally,
most
of
the
flux
generated
by
the
main
REA
coil
passes
through
the
upper
limb
of the
magnetic
structure
and
holds
the
armature
firmly
against
this
limb.
When
the
contacts
of
the
induction
unit
close,
the
shorting
coil
of
the
REA
is
short-circuited
and
current
flows
in
this
coil
by
transformer
action,
causing
a
redistribution
of
flux
which
actuates
the
armature
and
the
REA
contacts.
The
opening
of
the
REA
contacts
causes
the
secondary
current
to
flow
through
the
trip
coil
which
trips
the
breaker.
0.030
0.025
•
~
en
0.0.20
I
&.U
::I
..-
O.Ol~
Q..
:;)
J:
u 0.010
CL
0.005
0 0 1 2 4
CURRENT
TRANS
16S1
BREAKER
TRIP
COIL
L
AC
TRIP
UNIT
NORMALLY
CLOSlO
.-----------.:::1
oc;:;----+------<~
CONT
ACTS
o
At:.
TRIP
UN~T
SHORTlhG
COIL
1--
__
-'
,..._-+_r=~~~r-::::::::t::J
AC
TRIP'
UN
IT
MAIN
COIL
Figo
9
(K-6l54766-2)
Diagram
Illustrating
Operatio~
of
Type
lAC
Relays
having
an
A-C
Tripping
Unit.
OPERATI
NG
TIME
RANGE
FOR
N4Y
PI
CKUP
SETIING
6 7 b 10
MULTIPLES
Of
PICK-UP
Fig.
10 (6306872
[5])
Time-current
Characteristics
of
Original
Instantaneous
Unit

APPLICATION
The
a-c
tripping
unit
is
used
in
Type
IAC
relays
where
a
reliable
direct-current
tripping
source
is
not
available
and
it
is
necessary
to
trip
the
breaker
from
the
current-transformer
secondary.
RATINGS
The
a-c
tripping
unit
has
a
continuous
rating
of
five
amperes
but
will
operate
on a
minimum
current
of 3.5
amperes.
They should be
used
with
three-
ampere
trip
coils.
The
contacts
of
these
units
will
transfer
current
transformer
secondary
current
up
to 100
amperes.
For
applications
where
the
second-
ary
current
exceeds
100
amperes,
the
REAllB
relay,
Time
Overcurrent
Relays
Type
IAC
GEH-1753
which
has
contacts
rated
200
amperes,
can
be
used
in
conjunction
with
IAC
overcurrent
relays.
The
REAllB
is
not
mounted
inside
the IAC
case.
BURDENS
Burdens
of the REA
unit
are
given in
the
following
table:
Frequency
Amp
Impedance
PF
Volt-
in
Ohms
Amperes
60 5 0.49 0.80 12.2
50
5 0.33 0.85 8.4
25
5 0.23 0.62 5.8
RECEIVING, HANDLING AND STORAGE
These
relays,
when not
included
as
a
part
of a
control
panel,
will
be
shipped
in
cartons
designed
to
~rotect
them
against
damage.
Immediately
upon
receipt
of the
relay,
an
examination
should
be
made
for
any
damage
sustained
during
shipment.
If
injury
or
damage
resulting
from
rough
handling
is
evident,
a
claim
should
be
filed
at
once
with
the
transportation
company
and
the
nearest
Sales
Office
of the
General
Electric
Company notified
promptly.
Reasonable
care
should
be
exercised
in
un-
SEAL-IN
~
UNIT
""'-
I
D INDUCTION
UNIT
'"
l 1
f1
1
2 6
INTERNAL CONNECTIONS
(FRONT
VIEW)o=SHORT FINGER
Fig.
11.
(K-6209658-10)
Internal
Connections
fo:
the
Type
IAC51A
Relay
(Front
View).
packing
the
relay
in
order
that
none of
the
parts
are
injured
or
the
adjustments
disturbed.
If
the
relays
are
not
tobe
installed
immediately,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
moisture,
dust,
and
metallic
chips.
Foreign
matter
collected
on the
outside
of
the
case
may
find
its
way
inside
when
the
cover
is
removed
and
cause
trouble
in
the
operation
of
the
relay.
2
INDUCTION
UNIT
INSTANT
UNIT
6
SHORT
FINGER
Fig.
12.
(K-6209661
[11)
Internal
Connections
for
the
Type
IAC51B
Relay
(Front
View)
9

GEH-1753
Time
Overcurrent
Relays
Type
IAC
10
SEAL-IN
iJ
t;
:
1
I
N U
S N
T :
A T
N
T
INDUCTION
Uf'i:-:-
I
~
I
f1
~
I
~
I
2 4 6 8 10
A-C
-;RIP
-
UN
IT
INSTANT.
UU:
Fig.
13
(K-6209294-3)
Internal
Connections for the
Type
IAC5lR
Relay (Front
View)
SEAL-IN
UNIT
SI
INDUCTION
2
INDUCTION
UNIT
6
SHORT
FINGER
Fig.
14 (K-6209662
[5])
Internal
Connections
for
the
Type
IAC52A
Relay
(Front
View)

SEAL-IN
UNIT
r1'
2
INDUCTION
UN
IT
INSTANT.
UN
IT
INSTANT.
UNIT
..
r
10
• *
SHORT
FINGER
Fig.
15 (K-6209663
[8])
Internal
Connections
for
the
Type
IAC52B
Relay
(Front
View)
Time
Overcurrent
Relays
Type IAC GEH-1753
TO
TIMER
"STOP"
2
0
6 7
--
--
TC
INDICATING
LIGHT
WHEN
CHECKING
PICKUP
OF
MAIN
UN
IT
--
--
---
TO
INDICATING
LIGHT
WHEt
CHECKING
PICKUP
OF
INSTANTANEOUS
UN
IT
r---
-
---
6 0
3 4 5
0 0 0
8 9
10
x
LA13
TEST
PLUG
VARIABLE
RESISTOR
TO
TIMER
"START"
MIN.
RECQI.t.4ENDED
VOLTS,
120
AT
RATED
FREQUENCY
TO
ACCURATELY
REPRODUCE
RELAY
CHARACTER
I
STI
CS
ALL
TESTS
SHOULD
BE
r,tAOE
WI
TH
RELAY
IN
CASE.
Fig.
16
(K-6154399-7) Testing Connections
for
Type
lAC
Relays such
as
Type
IAC51A
INSTALLATION
LOCATION
The
location
should be
clean
and
dry,
free
from
dust
and
excessive
vibration,
and
well
lighted
to
facilitate
inspection
and
testing.
MOUNTING
The
relay
should
be
mounted on a
vertical
surface.
The outline
and
panel
diagrams
are
shown
in
Figs.
20 and 21.
CONNECTIONS
Internal
connection
diagrams
for
the
various
relay
types
are
shown in
Fig.
11
to 17
inclusive.
Typical
wiring
diagrams
are
given in Fig. 4 to 6
inclusive.
One of the mounting
studs
or
screws
should
be
permanently
grounded by a
conductor
not
less
than
No.
12
B&S
gage
copper
wire
or
its
equivalent.
INSPICTION
At
the
time
of
installation,
the
relay
should
be
inspected
for
tarnished
contacts,
loose
screws,
or
other
imperfections.
If
any
trouble
is
found,
it
should
be
corrected
in the
manner
described
under
MAINTENANCE.
CAUTION:
Every
circuit
in the
drawout
case
has
an
auxi-
liary
brush.
It
is
especially
important
on
current
circuits
and
other
circuits
with
shorting
bars
that
the
auxiliary
brush
be
bent
high enough
to
engage
the
connecting
plug
or
test
plug
before
the
main
brushes
do.
This
will
prevent
CT
secondary
cir-
cuits
from
being
opened.
CONNECTING PLUG
MAIN
BRUSH CONNECTING
BLOCK
NOTE: AFTER ENGAGING AUXILIARY BRUSH,
CONNECTING
PLUG
TRAVELS 1/4 INCH BEFORE ENGAGING THE
MAIN
BRUSH ON
~HE
TERMINAL
BLOCK.
Fig.
17
(8025039) Cross Section
of
Drawout
Case
Showing
Position of Auxiliary Brush.
11

GEH-1753
Time
Overcurrent
Relays
Type lAC
ADJUSTMENTS
TARGET
AND
SEAL-IN
UNIT
For
trip
coils
operating
on
currents
ranging
from
0.2 up
to
2.0
amperes
at
the
minimum
control
voltage,
set
the
target
and
seal-in
tap
screw
in
the
0.2-ampere
tap.
For
trip
coils
operating
on
currents
ranging
from
2
to
30
amperes
at
the
minimum
control
volt-
age,
place
the
tap
plug
in
the
2-ampere
tap.
The
tap
screw
is
the
screw
hol.ding
the
right-
hand
stationary
contact
of the
seal-in
unit.
To
change
the tap
setting,
first
remove
the
connecting
plug.
Then,
take
a
screw
from
the
left-hand
station-
ary
contact
and
place
it
in the
desired
tap.
Next,
remove
the
screw
from
the
other
tap,
and
place
it
in the
left-hand
contact.
This
procedure
is
neces-
sary
to
prevent
the
right-hand
stationary
contact
from
getting
out
of
adjustment.
Screws
should
not
be
in
both
taps
at
the
same
time.
INDUCTION
UNIT
CURRENT SETTING
The
tap
plug
must
not
be
removed
without
first
withdrawing
the
conneCting plug.
The
current
at
which the
contacts
operate
may
be
changed
by
changing
the
position
of
the
tap
plug
in the
tap
block
at
the
top of
the
relay.
Screw
the
tap
plug
firmly
into
the tap
marked
for
the
desired
current
(below which
the
unit
is
not
to
operate).
When
changing
the
current
setting
of
the
unit,
remove
the
connecting
plug
to
short
circuit
the
cur-
rent
transformer
secondary
circuit.
Next,
screw
the tap
plug
into tap
marked
for
the
desired
current
and
then
replace
the
connecting
plug.
The
pickup
of
the
unit
for
any
current
tap
is
adjusted
by
means
of a
spring-adjusting
ring.
The
ring
may
be
turned
by
inserting
a
screw
driver
in
the
notches
around
the
edge. By
turning
the
ring,
the
operating
current
of
the
unit
may
be
brought
into
agreement
with
the tap
setting
employed,
if
for
some
reason,
this
adjustment
has
been
disturbed.
This
adjustment
also
permits
any
desired
setting
intermediate
between
the
various
tap
settings
to
be
obtained.
The
unit
is
adjusted
at
the
factory
to
close
its
contacts
from
any
time-dial
position
at
a
mini-
mum
current
within five
percent
of
the
tap-plug
setting.
The
unit
resets
at
90
per
cent
of
the
mini-
mum
closing
value.
TIME SETTING
The
setting
of the
time
dial
determines
the
length of
time
the
unit
requires
to
close
its
contacts
when
the
current
reaches
a
predetermined
value.
The
contacts
are
just
closed
when
the
dial
is
set
on
O.
When
the
dial
is
set
on 10,
the
disk
must
travel
the
maximum
amount
to
close
the
contacts
and
there-
fore
thIs
setting
gives
the
maximum
time
setting.
12
The
primary
adjustment
for
the
time
of
opera-
tion
of
the
unit
is
made
by
means
of
the
time
dial.
However,
further
adjustment
is
obtained
by
moving
the
permanent
magnet
along
its
supporting
shelf;
moving
the
magnet
toward
the
disk
shaft
decreases
the
time,
while
moving
it
away
increases
the
time.
If
selective
action
of two
or
more
relays
is
required,
determine
the
maximum
possible
short-
circuit
current
of
the
line
and
then
choose
a
time
value
for
each
relay
that
differs
sufficiently
to
in-
sure
the
proper
sequence
in
the
operatio~
of
the
several
circuit
breakers.
Allowance
must
l\le
made
for
the
time
involved
in opening
each
break~r
after
the
relay
contacts
close.
For
this
reason,
unless
the
circuit
time
of
operation
is
known
with
accuracy,
there
should
be
a
difference
of
about
0.5
second
(at
the
maximum
current)
between
relays
whose
opera-
tion
is
to
be
selective.
EXAMPLE
OF
SETTING
The
time
and
current
settings
of
the
overcurrent
unit
can
be
made
easily
and
quickly.
Each
time
value
shown in
Fig.
2
indicates
the
time
required
for
the
contacts
to
close
with a
particular
time-dial
setting
when the
current
is
a
prescribed
number
of
times
the
current-tap
setting.
In
order
to
secure
any
of
the
particular
time-current
settings
shown
in
Fig.
2,
insert
the
removable
plug
in
the
proper
tap
re-
ceptacle
and
adjust
the
time-dial
to
the
proper
position.
The
following
example
illustrates
the
procedure
in
making
a
relay
setting.
Assume
a
Type
lAC
relay
is
used
in
a
circuit
where
the
circuit
breaker
should
trip
on a
sustained
current
of
approximately
450
amperes;
also,
the
breaker
should
trip
in
1.9
secon<;is ona
short-circuit
current
of 3750
amperes.
Assume
further
that
current
transformers
of
60/1
ratio
are
used.
The
current
tap
setting
is
found by
dividing
the
minimum
primary
tripping
current
by
the
current
transformer
ratio.
In
this
case,
450
divided
by 60
equals
7.5
amps.
Since
there
is
no
7.5-amp
tap,
the
8-amp.
tap
is
used.
To
find
the
proper
time-dial
setting
to give
1.9
seconds
time
delay
at
3750
am-
peres,
divide
3750 by
the
transformer
ratio.
This
gives
62.5
amperes
secondary
current
which
is
7.8
times
the
8-ampere
setting.
By
referring
to
the
time
current
curves
(Fig.
2),
it
will
be
seen
that
7.8
times
the
minimum
operating
current
gives
1.9
seconds
time
delay
when the
relay
is
set
sl1ghtly
above
the
No.6
time-dial
setting.
The
above
results
should
be
checked
by
pleans
of
an
accurate
timing
device.
Slight
readjustment
of
the
dial
can
be
made
until
the
desired
time
is
obtained.
.
Aid
in
making
the
proper
selection
of
relay
settings
may
be
obtained
on
application
to
the
nearest
Sales
Office of
the
General
Electric
Company.

CONTACT ADJUSTMENT
The
contacts
should have
approximately
1/32
inch wipe.
That
is
the
stationary
contact
should
be
deflected
about l;:b
inch
when the
disk
completes
its
travel.
The
contact
wipe
is
adjusted
by
turning
the
screws
in
the
contact
brush
which
regulates
the
position
of the
brush,
in
relation
to the
brush
stop.
For
relays
with two
circuit-closing
contacts,
the
tips
should be in the
same
vertical
plane.
When
the
time
dial
is
moved to a
position
where
the
contacts
just
close,
the
time-dial
scale
should
indicate
zero.
If
this
is
found
incorrect,
and
the
brushes
are
correctly
adjusted,
regulate
the
dial
to
read
zero.
This
is
done by
changing
the
position
of
the
arm
attached
to
the
shaft
which
fS
located
below
the
time
dial.
Loosen
the
screw
which
clamps
the
arm
to
the
shaft
and
turn
the
arm,
relative
to
the
shaft,
until
the
contacts
just
make
at
the
zero
time-
dial
setting.
INSTANTANEOUS
UNIT
Select
the
current
above which
is
desired
to
have
the
instantaneous
unit
operate
and
set
the
ad-
justable
pole
piece
so
that
the
top of hexagon
head
is
even
with
the
desired
calibration
on
the
scale.
To
raise
or
lower
the
pole
piece
loosen
the
locknut
and
turn
it
up
or
down and
then
tighten
in
position.
The
contacts
should
be
adjusted
to
make
at
about
the
same
time
and
to
have
approximately
1/8"
wipe.
This
adjustment
can
be
made
by
loosening
the
screws
holdingthe
stationary
contacts
and
moving
the
contacts
up
or
down
as
required.
A-C
TRIPPING
UNIT
The
a-c
tripping
unit
should
not
require
any
attention
other
than
occasional
cleaning
of
the
con-
tacts.
However,
if
the
adjustment
should be
lost,
it
may
be
restored
as
follows:
Time
Overcurrent
Relays
Type IAC GEH-1753
1. CONTACT ADJUSTMENT
With
the
unit
de-energized,
the
movable
contact
should
lie
against
the
stationary
contact
with
enough
tension
to
always
insure
a good
closed
circuit.
The
movable
contact
brush
should be
free
of
any
kinks.
Also
this
contact
brush
should
not
touch
the
com-
pound
bushing
supported
from
the
top of
the
arma-
ture.
The
brass
backing
strip
should
be
adjusted
to
allow a 1/16-i.nch
contact
gap with
the
contacts
open.
The
compound
bushing
support
should
be
adjusted
to
allow
the
back
of
the
movable
contact
to
just
touch
the
brass
backing
strip
when
the
armature
operates
to
open the
contacts.
The
outer
edge of
the
com-
pound
bushing
should
be
approximately
1/32
-
inch
from
the
inner
edge
of the
stationary
contact
sup-
porting
post.
2. ARMATURE ADJUSTMENT
Loosen
the
two
screws
whichhold
the
armature-
assembly
bracket
to
the
bottom
of
the
frame.
Slide
the
bracket
in
or
out,
whichever
is
necessary,
until
the
armature
just
touches
the
pole
face
of
the
upper
core.
In
this
position,
the
armature
should
be
about
1/32
inch
from
the
pole
face
of
the
lower
core.
Next,
slide
the
bracket
in
until
the
armature
leaf
spring
assumes
a
vertical
position
and
is
spaced
clear
of both
armature
and
the
vertical
tip
of
the
bracket.
With
this
setting,
the
armature
should
be
flush
against
the
pole
face
of both
cores,
and
should
put
enough
pressure
on
the
armature
to
always
re-
turn
it.
flush
against
the
pole
face
of
the
lower
core
after
each
operation
of
the
unit.
This
alignment
is
important
as
a
slight
gap between
armature
andpole
face
of
the
lower
core
after
the
unit
operates
may
cause
contacts
to
open
momentarily,
dropping
the
relay
target
when
the
circuit
breaker
is
reclosed.
Under
these
conditions,
the
momentary
opening of
the
contacts
is
due to the
shock
of
the
armature
being
pulled
in
against
the
pole
face
when
the
lower
coil
is
energized.
Excessive
pressure
on
the
arma-
ture,
caused
by
the
bracket
being
pushed
in
too
far,
will
result
in
too
high a pickup
or
chattering
of
the
movable
contact
during
operation
of
the
unit.
Tighten
the
bracket
screws
securely
after
the
proper
ad-
justment
has
been
obtained.
OPERATION
Before
the
relay
is
put
into
service
it
should
be
given a
check
to
determine
that
factory
adjustments
have not
been
disturbed.
The
time-dial
will
be
set
at
zero
before
the
relay
leaves
the
factory.
It
is
necessary
to
change
this
setting
in
order
to
open
the
relay
contacts.
The
pickup
current
should
be
checked
on one
or
more
of
the
taps
and
the
time
should
be
checked
for
one
or
more
dial
settings.
Recommended
test
connections
for
the
above
test
are
shown
in
Fig.
18.
MAINTENANCE
The
relays
are
adjusted
at
the
factory
and
it
is
advisable
not
to
disturb
the
adjustments.
If,
for
any
reason,
they have
been
disturbed,
the
following
points
should
be
observed
in
restoring
them:
DISK
AND
BEARINGS
The
lower
jewel
may
be
tested
for
cracks
by
exploring
its
surface
with
the
point
of a
fine
needle.
If
it
is
necessary
to
replace
the
jewel
a new
pivot
should
be
screwed
into the
bottom
of
the
shaft
at
the
shaft
at
the
same
time.
The
jewel
should
be
turned
up
until
the
disk
is
centered
in
the
air
gaps,
after
which
it
should
be locked in
this
position
by
the
set
screw
provided
for
this
purpose.
13

GEH-1753
Time
Overcurrent
Relays
Type lAC
CONTACT
CLEANING
For
cleaning
fine
silver
contacts,
a
flexible
burnishing
tool
should
be
used,
This
consists
of a
flexible
strip
of
metal
with
an
etched
roughened
surface,
resembling
in
effect
a
superfine
file.
The
polishing
action
is
so
delicate
that
no
scratches
are
left,
yet
corroded
material
will
be
removed
rapidly
and
thoroughly.
The
flexibility
of
the
tool
insures
the
cleaning
of
the
actual
points
of
contact.
Fine
silver
contacts
should
not
be
cleaned
with
knives,
files,
or
abrasive
paper
or
cloth.
Knives
or
files
may
leave
scratches
which
increase
arcing
and
deterioration
of
the
contacts.
Abrasive
paper
or
cloth
may
leave
minute
particles
of
insulating
abrasive
material
in
the
contacts
and
thus
prevent
closing.
The
burnishing
tool
described
above
can
be
obtained
from
the
factory.
PERIODIC
TESTING
An
operation
test
and
inspection
of
the
relay
at
least
once
every
six
months
are
recommended.
Test
connections
are
shown
in
Fig.
18.
RENEWAL PARTS
It
is
recommended
that
sufficient
quantities
of
renewal
parts
be
carried
in
stock
to
enable
the
prompt
replacement
of
any
that
are
worn,
broken,
or
damaged.
pany,
specify
quantity
required,
name
of
part
wanted,
and
give
complete
nameplate
data.
If
possible,
give
the
General
Electric
Company
requisition
number
on
which
the
relay
was
furnished.
When
ordering
renewal
parts,
address
the
nearest
Sales
Office of
the
General
Electric
Com-
For
a
recommended
parts
list
refer
to
Parts
Bulletin
number
GEF-3883.
HI
SEI94IC
AAlB)'IMSTMTMBUS
"IT
~ERATING
TIME
.025
,,.(I!(}
,
..
\
"-
OPEIlATI
N&
TI
ME
I---
1\
~,
RANGE
FOR
ANY
V-
PI
ClWP
SETT
I
MCi
10
'~
8
0:
.0
~'--
I
5 "-
.00
r--...
-'--
--
I I
1 1
1.5 2 3 5 7 8 9
10
J<lUL
1'1
PlES
OF
PICKUP
Fig.
19
(0208A8695
(l.
J)
Time-Current
Characteristics
for
the
"Hi-G"
Unit
Since
the
last
edition,
Figures
12
and 14
have
been
revised.
14

Time Overcurrent Relays Type
IAC
GEH-1753
SENI-FlUSH--PANEL
LOCHION_
IITG.
~G'
_'_6_~
___
o~~
I
r--------
SURFACE
"'TG.
1
'f=,==:::;~====::::1!
fe--1B
STUDS
FOR
SURFACE
"'Tt..
STUD NU"'BER I
NG
<RONT VIEW
FIG.
-A
A
, 1 3 5
I
iOOO
~9_Q----"
~
DRILL
5
HO
LE
S
/
!
hi
f,
f
--#'--J....jL..
,~
I I
1-
._-.-=::::3
.-
...
0
11<'"
----
~~
;~~~:;;;:::=~I~
:::Y----
"''''
11.----
(\'\0
T
SI
r
:mro-
1
--··-
NUN
..
BE
E.RR.
I
N.G.
.
RE
LAY
.£..t.G._.
...2..YfE......
__
i_A
I AC51A
1
).
__
-
_~c51B
~
___
-
A I AC51C
A I AC52A
B
IAC51R
B
IAC52B
I
OUTLINE
r
10-32
x
J/8
NTG.
SCREW
STUD NU"'BER I
HG
FRONT VI
EW
FIG.
-B
._---
B
II
1 J 5 7 9
1°0000
",-00000
2 4 6 8
10
PANEL
RILLING
SENI-FL
SH
MTG.
FIG.A&B
VIEW SHOWING
ASSEIIBlY
OF
HARDWARE
FOR
SURFACE
"'TG.
ON
STEE l
PANE
LS.
~
DR
ILL
2 HOLES J
DRILL
~
.
'"
""""
r
-¥~-·
lL
~
1
th
_
II<~
"
--y-
"'-~
!;~
"'.L.
.' -
,.
~I
1-8
.
9~r
2~
~1j1
I
B.
f---
2~
--L... 25
L--....!.
5!'
8
4
PANEL
OR
IL
LI
HG
FOR
FIG.S
SURF
.CE "TO. -FROH
VI~.
>'ig.
18
(237C707-1)
Outline
and Panel
Drilling
for
the
Type
IAC51A,
IAC51B, IAC51R,
IAC52A
and
IAC52B
Relays
15

å
åå
å
*( 3RZHU 0DQDJHPHQW
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222
Fax: (905) 201-2098
www.ge.com/indsys/pm
This manual suits for next models
4
Other GE Relay manuals
Popular Relay manuals by other brands

Honeywell
Honeywell TRIPLEAQUASTAT L8151A Installation and operation instructions

Rockwell Automation
Rockwell Automation Allen-Bradley Guardmaster MSR55P installation instructions

Arcteq
Arcteq AQ F205 instruction manual

Doug Fleenor Design
Doug Fleenor Design DMX6REL15A-JBOX manual

PRASTEL
PRASTEL FOTO30SDE quick start guide

Dossena
Dossena DER3/1DL manual

System Sensor
System Sensor i3 Series Installation and maintenance instructions

Airspan
Airspan UGD-D01035 iR460 installation guide

IFM
IFM G1502S Original operating instructions

Hobby Components
Hobby Components SmartRFy HCMODU0145 manual

Devantech
Devantech dS2824 user manual

Novatek-electro
Novatek-electro REV-114 operating manual