GE ML Series 350 User manual

GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094
GE Digital Energy
Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
Instruction manual
350 revision: 1.2
Manual P/N: 1601-9091-A4
GE publication code: GEK-113509C
Copyright © 2009 GE Multilin
*1601-9086-A4*
350
Feeder Protection System
Feeder protection and control
Courtesy of NationalSwitchgear.com

© 2009 GE Multilin Incorporated. All rights reserved.
GE Multilin 350 Feeder Protection System instruction manual for revision 1.2.
350 Feeder Protection System, EnerVista, EnerVista Launchpad, and EnerVista SR3 Setup
are registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9091-A4 (June 2009)
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Table of Contents
1. INTRODUCTION Overview ........................................................................................................ 1 - 1
Cautions and warnings ............................................................................... 1 - 2
Description of the 350 Feeder Protection System.................................. 1 - 3
350 order codes ............................................................................................ 1 - 6
Specifications................................................................................................ 1 - 7
Password security....................................................................................................................1 - 7
Protection specifications ......................................................................................................1 - 7
Data capture ..............................................................................................................................1 - 8
Control specifications.............................................................................................................1 - 9
Inputs specifications...............................................................................................................1 - 10
Outputs specifications ...........................................................................................................1 - 11
Power supply specifications................................................................................................1 - 11
Communications specifications........................................................................................1 - 12
Testing and certification .......................................................................................................1 - 12
Physical specifications...........................................................................................................1 - 13
Environmental specifications .............................................................................................1 - 13
2. INSTALLATION Mechanical installation............................................................................... 2 - 1
Dimensions..................................................................................................................................2 - 2
Product identification .............................................................................................................2 - 2
Mounting ......................................................................................................................................2 - 3
Unit withdrawal and insertion............................................................................................2 - 6
Electrical installation................................................................................... 2 - 7
Terminal identification ...........................................................................................................2 - 8
Phase sequence and transformer polarity...................................................................2 - 9
Current inputs ............................................................................................................................2 - 9
Ground and sensitive ground CT inputs ........................................................................2 - 9
Zero sequence CT installation............................................................................................2 - 10
Control power ............................................................................................................................2 - 11
Trip and Close output relays ...............................................................................................2 - 11
Contact inputs ...........................................................................................................................2 - 13
Serial communications..........................................................................................................2 - 14
IRIG-B .............................................................................................................................................2 - 15
3. INTERFACES Front control panel interface..................................................................... 3 - 2
Description ..................................................................................................................................3 - 2
Display ...........................................................................................................................................3 - 3
Working with the Keypad .....................................................................................................3 - 3
LED status indicators..............................................................................................................3 - 5
Relay messages ........................................................................................................................3 - 6
Target messages.....................................................................................................................3 - 6
Self-test errors..........................................................................................................................3 - 7
Flash messages.......................................................................................................................3 - 8
Software setup.............................................................................................. 3 - 10
Quick setup - Software interface ......................................................................................3 - 10
EnerVista SR3 Setup Software............................................................................................3 - 10
Hardware and software requirements.........................................................................3 - 11
Installing the EnerVista SR3 Setup software..............................................................3 - 11
Connecting EnerVista SR3 Setup to the relay ............................................................3 - 14
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Configuring serial communications...............................................................................3 - 14
Using the Quick Connect feature ....................................................................................3 - 15
Configuring Ethernet communications ........................................................................3 - 16
Connecting to the relay........................................................................................................3 - 17
Working with setpoints and setpoint files....................................................................3 - 18
Engaging a device..................................................................................................................3 - 18
Entering setpoints...................................................................................................................3 - 18
File support ................................................................................................................................3 - 20
Using setpoints files...............................................................................................................3 - 20
Downloading and saving setpoints files......................................................................3 - 20
Adding setpoints files to the environment..................................................................3 - 20
Creating a new setpoint file...............................................................................................3 - 21
Upgrading setpoint files to a new revision .................................................................3 - 22
Printing setpoints and actual values .............................................................................3 - 23
Printing actual values from a connected device .....................................................3 - 24
Loading setpoints from a file.............................................................................................3 - 25
Upgrading relay firmware ...................................................................................................3 - 25
Loading new relay firmware..............................................................................................3 - 25
Advanced EnerVista SR3 Setup features ......................................................................3 - 27
Flexcurve editor .......................................................................................................................3 - 27
Transient recorder (Waveform capture).......................................................................3 - 28
Protection summary..............................................................................................................3 - 31
Password security ..................................................................................................................3 - 32
4. ACTUAL VALUES Actual values overview ............................................................................... 4 - 1
A1 Status ........................................................................................................ 4 - 3
Clock...............................................................................................................................................4 - 4
Contact inputs...........................................................................................................................4 - 4
Output relays .............................................................................................................................4 - 4
Logic elements ..........................................................................................................................4 - 5
Virtual inputs ..............................................................................................................................4 - 5
Remote inputs ...........................................................................................................................4 - 5
Remote outputs ........................................................................................................................4 - 5
Contact inputs summary......................................................................................................4 - 6
Output relays summary........................................................................................................4 - 6
Logic elements summary.....................................................................................................4 - 6
GOOSE status.............................................................................................................................4 - 6
GOOSE HDR status ..................................................................................................................4 - 6
A2 Metering ................................................................................................... 4 - 8
A3 Records ..................................................................................................... 4 - 9
Event records.............................................................................................................................4 - 9
Transient records.....................................................................................................................4 - 13
Clear event record...................................................................................................................4 - 13
Clear transient record............................................................................................................4 - 13
Clear thermal capacity record...........................................................................................4 - 14
A4 Target messages..................................................................................... 4 - 15
5. QUICK SETUP -
FRONT CONTROL
PANEL
Quick Setup settings .................................................................................... 5 - 3
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6. SETPOINTS Setpoints Main Menu ................................................................................... 6 - 1
Setpoint entry methods.........................................................................................................6 - 2
Common setpoints ..................................................................................................................6 - 3
Logic diagrams..........................................................................................................................6 - 4
Setting text abbreviations....................................................................................................6 - 4
S1 Relay setup............................................................................................... 6 - 5
Clock...............................................................................................................................................6 - 5
Password security....................................................................................................................6 - 7
Access passwords..................................................................................................................6 - 8
Communications ......................................................................................................................6 - 10
RS485 interface .......................................................................................................................6 - 10
Modbus........................................................................................................................................6 - 11
IEC 60870-5-103 serial communication ......................................................................6 - 12
IEC60870-5-104 protocol....................................................................................................6 - 12
DNP communication.............................................................................................................6 - 14
IEC 61850 GOOSE communications...............................................................................6 - 14
Event recorder ...........................................................................................................................6 - 15
Transient recorder ...................................................................................................................6 - 16
Front panel ..................................................................................................................................6 - 18
Installation...................................................................................................................................6 - 18
S2 System Setup ........................................................................................... 6 - 19
Current sensing.........................................................................................................................6 - 19
Power system.............................................................................................................................6 - 20
Breaker..........................................................................................................................................6 - 20
User curve....................................................................................................................................6 - 21
Flexcurves™................................................................................................................................6 - 21
S3 Protection ................................................................................................. 6 - 22
Current elements......................................................................................................................6 - 24
TOC curves.................................................................................................................................6 - 25
Phase timed overcurrent protection .............................................................................6 - 32
Phase instantaneous overcurrent protection ...........................................................6 - 35
Ground/Sensitive Ground timed overcurrent protection.....................................6 - 37
Ground/Sensitive Ground instantaneous overcurrent protection...................6 - 40
Neutral timed overcurrent protection...........................................................................6 - 43
Neutral instantaneous overcurrent protection ........................................................6 - 46
Cable Thermal Model..............................................................................................................6 - 49
S4 Control ...................................................................................................... 6 - 53
Change setpoint group..........................................................................................................6 - 54
Virtual inputs...............................................................................................................................6 - 56
Logic elements...........................................................................................................................6 - 57
Breaker control..........................................................................................................................6 - 63
Cold load pickup .......................................................................................................................6 - 64
Breaker failure ...........................................................................................................................6 - 67
Autorecloser................................................................................................................................6 - 69
S5 Inputs/Outputs ........................................................................................ 6 - 74
Contact inputs ...........................................................................................................................6 - 74
Output relays..............................................................................................................................6 - 75
Output Relay 1 "Trip" .............................................................................................................6 - 76
Output Relay 2 "Close"..........................................................................................................6 - 78
Auxiliary Output Relays 3 to 6...........................................................................................6 - 80
Critical Failure Relay #7 .......................................................................................................6 - 81
Virtual inputs...............................................................................................................................6 - 83
Remote inputs............................................................................................................................6 - 84
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
7. MAINTENANCE M1 Relay information .................................................................................. 7 - 2
M3 Breaker maintenance............................................................................ 7 - 3
Trip coil..........................................................................................................................................7 - 3
Close coil ......................................................................................................................................7 - 6
Breaker trip counter................................................................................................................7 - 9
M4 Breaker monitor ..................................................................................... 7 - 11
Courtesy of NationalSwitchgear.com

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–1
350 Feeder Protection System
Chapter 1: Introduction
Digital Energy
Multilin
Introduction
1.1 Overview
The 350 is a microprocessor-based relay for primary and backup over-current protection
of medium and low voltage distribution feeders. The relay is also suitable for providing
over-current protection for small and medium size motors, transformers, generators, and
distribution bus-bars. The small footprint and the withdrawable option make the 350 relay
ideal for panel mounting on either new or retrofit installations. The combination of proven
hardware, a variety of protection and control features, and communications, makes the
relay ideal for total feeder protection and control. Equipped with serial (RS485), USB, and
Ethernet ports, and a wide selection of protocols such as Modbus, DNP3.0, IEC 60870-5-
103, 60870-5-104, GOOSE, the 350 relay is the best-in-class for MCCs, SCADA and inter-
relay communications. The 350 relay provides excellent transparency with respect to
power system conditions and events, through its four-line 20-character display, as well as
the EnerVista SR3 Setup program. Conveniently located LEDs provide indication of relay
operation, alarm, and pickup, as well as breaker, and relay status.
The 350 relay provides the following key benefits:
• Withdrawable small footprint – saves on rewiring and space.
• Multiple protection groups with the added flexibility of switching through a wide
selection of overcurrent protection and control features.
• Fast setup (Quick Setup) menu for power-system setup and a simple overcurrent
protection configuration.
• Large four-line LCD display, LEDs, and an easy-to-navigate keypad.
• Multiple communication protocols for simultaneous access when integrated into
monitoring and control systems.
Courtesy of NationalSwitchgear.com

1–2 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CAUTIONS AND WARNINGS CHAPTER 1: INTRODUCTION
1.2 Cautions and warnings
Before attempting to install or use this device, it is imperative that all caution and danger
indicators in this manual are reviewed to help prevent personal injury, equipment damage,
or downtime. The following icons are used to indicate notes, cautions, and dangers.
Figure 1-1: Note icons used in the documentation
The standard note icon emphasizes a specific point or indicates minor problems that may
occur if instructions are not properly followed.
The caution icon indicates that possible damage to equipment or data may occur if
instructions are not properly followed.
The danger icon provides users with a warning about the possibility of serious or fatal
injury to themselves or others.
NOTE
CAUTION
DANGER
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–3
1.3 Description of the 350 Feeder Protection System
CPU
Relay functions are controlled by two processors: a Freescale MPC5554 32-bit
microprocessor measures all analog signals and digital inputs and controls all output
relays; a Freescale MPC5202B 32-bit microprocessor controls all the Ethernet
communication protocols.
Analog Input Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the
source instrument transformers. The analog signals are then passed through a 960 Hz low
pass anti-aliasing filter. All signals are then simultaneously captured by sample and hold
buffers to ensure there are no phase shifts. The signals are converted to digital values by a
12-bit A/D converter before finally being passed on to the CPU for analysis.
Current is sampled thirty-two times per power frequency cycle. These ‘raw’ samples are
calibrated in software, then placed into the waveform capture buffer, thus emulating a
fault recorder. The waveforms can be retrieved from the relay via the EnerVista SR3 Setup
software for display and diagnostics.
Phasors, Transients, and Harmonics
Current waveforms are processed twice every cycle with a DC Offset Filter and a Discrete
Fourier Transform (DFT). The resulting phasors have fault current transients and all
harmonics removed. This results in an overcurrent relay that is extremely secure and
reliable; one that will not overreach.
Processing of AC Current Inputs
The DC Offset Filter is an infinite impulse response (IIR) digital filter, which removes the DC
component from the asymmetrical current present at the moment a fault occurs. This is
done for all current signals used for overcurrent protection. This filter ensures no overreach
of the overcurrent protection; unfortunately, the filter also causes slower overcurrent
response times (0 to 50 ms) for faults marginally over the pickup level.
The Discrete Fourier Transform (DFT) uses exactly one sample cycle to calculate a phasor
quantity which represents the signal at the fundamental frequency; all harmonic
components are removed. All subsequent calculations (e.g. RMS, power, etc.) are based
upon the current phasors, such that the resulting values have no harmonic components.
Protection Elements
All protection elements are processed twice every cycle to determine if a pickup has
occurred or a timer has expired. The protection elements use RMS current, based on the
magnitude of the phasor. Hence, protection is impervious to both harmonics and DC
transients.
Courtesy of NationalSwitchgear.com

1–4 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM CHAPTER 1: INTRODUCTION
Figure 1-2: Single line diagram
Table 1: 350 protection functions
898727A1.CDR
350 RELAY
TRIP
BUS
LOAD
3
1
52
CLOSE
50G/
51G
50P 50N
79
50G 51G
22
21
METERING
TRANSIENT RECORDER
EVENT RECORDER
51N51P CLP
11
4950BF
11 11
1
ANSI device Description
49 Thermal Model
50P Phase Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50G Ground/Sensitive Ground Instantaneous Overcurrent
50BF Breaker Failure
51P Phase Timed Overcurrent
51G Ground Timed Overcurrent
51N Neutral Timed Overcurrent
79 Autoreclose
CLP Cold Load Pickup
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–5
Figure 1-3: 350 Main Menu structure
ACTUAL VALUES
QUICK SETUP
SETPOINTS
MAINTENANCE
ACTUAL VALUES
A1 STATUS
A2 METERING
A3 RECORDS
QUICK SETUP
PH CT PRIMARY
[SENS] GND CT
PH TOC FUNCTION
GND TOC FUNCTION
NTRL TOC FUNCTION
PH IOC1 FUNCTION
GND IOC1 FUNCTION
NTRL IOC1 FUNCTION
PRIMARY
▼
SETPOINTS
S1 RELAY SETUP
S2 SYSTEM SETUP
S3 PROTECTION
S4 CONTROLS
S5 INPUTS/OUTPUTS
▼
MAINTENANCE
M1 RELAY INFO
M3 BKR MAINTENANCE
M4 BKR MONITOR
M6 FACTORY SERVICE
▼
898790.cdr
PHASE TOC
PH TOC PICKUP
PH TOC CURVE
PH TOC TDM
▼
GROUND TOC
GROUND TOC PICKUP
GROUND TOC CURVE
GROUND TOC TDM
▼
NEUTRAL TOC
NTRL TOC PICKUP
NTRL TOC CURVE
NTRL TOC TDM
▼
PHASE IOC1
PH IOC1 PICKUP
GROUND IOC1
GND IOC1 PICKUP
NEUTRAL IOC1
NTRL IOC1 PICKUP
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–7
1.5 Specifications
NOTE
NOTE: Specifications are subject to change without notice.
1.5.1 Password security
PASSWORD SECURITY
Master Reset Password: ..................................8 to 10 alpha-numeric characters
Settings Password:.............................................3 to 10 alpha-numeric characters for local and remote
access
Control Password:...............................................3 to 10 alpha-numeric characters for local and remote
access
1.5.2 Protection specifications
PHASE/NEUTRAL/GROUND TIME OVERCURRENT (51P/51N/51G)
Pickup Level:..........................................................0.04 to 20 x CT in steps of 0.01 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I < 1 x CT
Curve Shape:.........................................................ANSI Extremely/Very/Moderately/Normally Inverse
Definite Time (0.05 s base curve)
IEC Curve A/B/C/Short
IAC Extreme/Very/Inverse/Short
User Curve, FlexCurve™A/B (programmable curves)
Curve Multiplier:...................................................0.5 to 20.0 in steps of 0.1
Reset Time: ............................................................Instantaneous, Linear
Time Delay Accuracy:.......................................±3% of expected inverse time or 1 cycle, whichever is
greater
Level Accuracy:....................................................per CT input
SENSITIVE GROUND TIME OVERCURRENT (51SG)
Pickup Level:..........................................................0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.02 x CT @ I < 0.1 x CT
Curve Shape:.........................................................ANSI Extremely/Very/Moderately/Normally Inverse
DefiniteTime
IEC Curve A/B/C/Short Inverse
IAC Extreme/Very/Inverse/Short Inverse
User Curve, FlexCurve™A/B
Curve Multiplier:...................................................0.5 to 20.0 in steps of 0.1
Reset Time: ............................................................Instantaneous, Linear
Time Delay Accuracy:.......................................±3% of expected inverse time or 1 cycle, whichever is
greater
Level Accuracy:....................................................per CT input
PHASE/NEUTRAL/GROUND INSTANTANEOUS OVERCURRENT (50P/50N/50G)
Pickup Level:..........................................................0.05 to 20 x CT in steps of 0.01 x CT
Dropout Level: ......................................................97 to 99% of Pickup @ I > 1 x CT
Pickup - 0.02 x CT @ I <1 x CT
Time Delay:............................................................0.00 to 300.00 sec in steps of 0.01
Operate Time:.......................................................<30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
<35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
Time Delay Accuracy:.......................................0 to 1 cycle (Time Delay selected)
Level Accuracy:....................................................per CT input
Courtesy of NationalSwitchgear.com

1–8 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG)
Pickup Level (Gnd IOC):.....................................0.005 to 3 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 99% of Pickup @ I > 0.1 x CT
Pickup - 0.002 x CT @ I < 0.1 x CT
Time Delay:............................................................ 0.00 to 300.00 sec in steps of 0.01
Operate Time: ......................................................<30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
<35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
Time Delay Accuracy:.......................................0 to 1 cycle (Time Delay selected)
Level Accuracy:....................................................per CT input
CABLE THERMAL MODEL (49)
Current:.................................................................... Fundamental phasor
Pickup Accuracy:.................................................per current inputs
Timing Accuracy:................................................See graph below
The graph shows the trip time error with respect to the ratio of cable load and thermal
model pickup setting. With a smaller I/Ipkp ratio, the time error tends to be higher, as
accumulated through the logarithmic formula, the measurement error, and the time of
measurement. For higher I/Ipkp ratios, the time to trip is substantially more accurate. Each
point on the graph represents a trip time error, with the I/Ipkp ratio kept constant during
the test.
1.5.3 Data capture
OSCILLOGRAPHY
Buffer size: .............................................................3 s
No. of buffers:......................................................1x192, 3x64, 6x32
No. of channels:..................................................14
Sampling rate:......................................................32 samples per cycle
Triggers: ..................................................................Manual Command
Contact Input
Virtual Input
Logic Element
Element Pickup/Trip/Dropout
Data: ......................................................................... AC input channels
Contact input state
Contact output state
Virtual input state
Logic element state
Data storage:........................................................ Retained for 3 days
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–9
EVENT RECORDER
Number of events:..............................................256
Header: ....................................................................relay name, order code, firmware revision
Content:...................................................................event number, date of event, cause of event, per-phase
current, ground current, sensitive ground current, neutral
current, system frequency, thermal capacity
Data Storage:........................................................RAM - Battery backed-up
CLOCK
Setup:........................................................................Date and time
Daylight Saving Time
IRIG-B:.......................................................................Auto-detect (DC shift or Amplitude Modulated)
Amplitude modulated: 1 to 10 V pk-pk
DC shift: 1 to 10 V DC
Input impedance: 40kOhm ± 10%
RTC Accuracy: ± 1 min / month
1.5.4 Control specifications
LOGIC ELEMENTS
Number of logic elements: .............................8
Trigger source inputs per element: ............3
Block inputs per element: ...............................3
Supported operations: .....................................AND, OR, NOT, Pickup / Dropout timers
Pickup timer:..........................................................0 to 6000 ms in steps of 1 ms
Dropout timer:......................................................0 to 6000 ms in steps of 1 ms
BREAKER CONTROL
Operation:...............................................................Asserted Contact Input, Logic Element, Virtual Input, Manual
Command
Function: .................................................................Opens / closes the feeder breaker
AUTORECLOSE
Reclose attempts:...............................................Up to 4 shots
Time Delay Accuracy:.......................................0 to 3 cycles (AR Dead Time selected)
Elements: ................................................................Inputs, Outputs, Breaker Status (52 status)
BREAKER FAILURE
Pickup Level:..........................................................0.05 to 20.00 x CT in steps of 0.01
Dropout Level: ......................................................97 to 98% of pickup
Time Delay Accuracy:.......................................0 to 1 cycle (Timer 1, Timer 2)
Level Accuracy:....................................................per CT input
BREAKER TRIP COUNTER
Trip Counter Limit (Pickup):.............................1 to 10000 in steps of 1
COLD LOAD PICKUP BLOCKING
Operation:...............................................................Automatically, or by command (asserted Contact Input,
Logic Element, Virtual Input)
Function: .................................................................Block IOC for selected period of time, raise TOC pickup for
selected period of time
Time Delay Accuracy:.......................................0 to 1 cycle (Block Time)
<200 ms (Outage Time)
Courtesy of NationalSwitchgear.com

1–10 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
1.5.5 Inputs specifications
CONTACT INPUTS
Inputs: ......................................................................8
Selectable thresholds:......................................17, 33, 84, 166 VDC
Recognition time:................................................1/2 cycle
Debounce time: ...................................................1 to 64 ms, selectable, in steps of 1 ms
Continuous current draw:...............................2mA
Type: .........................................................................opto-isolated inputs
External switch: ................................................... wet contact
Maximum input voltage: ................................. 300VDC
PHASE & GROUND CURRENT INPUTS
CT Primary: ............................................................1 to 6000 A
Range:......................................................................0.02 to 20 × CT
Input type:.............................................................. 1A or 5A (must be specified with order)
Nominal frequency:...........................................50/60 Hz
Accuracy:................................................................±1% of reading at 1× CT
±3% of reading from 0.2to 20 × CT
±20% of reading from 0.02to 0.19 × CT
CT withstand:........................................................ 1second at 100 × rated current
2seconds at 40 × rated current
continuous at 3 × rated current
SENSITIVE GROUND CURRENT INPUT
CT Primary: ............................................................1 to 600 A
Range:......................................................................0.002 to 3 × CT
Input type:.............................................................. 1A or 5A (must be specified with order)
Nominal frequency:...........................................50/60 Hz
Accuracy:................................................................±1% of reading at 0.1× CT
±3% of reading from 0.02to 3 × CT
±20% of reading from 0.002to 0.019 × CT
CT withstand:........................................................ 1second at 100 × rated current
2seconds at 40 × rated current
continuous at 3 × rated current
FREQUENCY
Accuracy:................................................................±0.05 Hz
Resolution: .............................................................0.01 Hz
Range:......................................................................40.00 to 70.00 Hz
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–11
1.5.6 Outputs specifications
FORM-A RELAYS
Configuration:.......................................................2 (two) electromechanical
Contact material:................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive):............................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................277 VAC / 10 A
FORM-A VOLTAGE MONITOR
Applicable voltage:.............................................20 to 250 VDC
Trickle current:......................................................1 to 2.5 mA
FORM-C RELAYS
Configuration:.......................................................5 (five) electromechanical
Contact material:................................................silver-alloy
Operate time:........................................................<8 ms
Continuous current:...........................................10 A
Make and carry for 0.2s:..................................30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):.................24 V / 1 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
Break (DC resistive):............................................24 V / 10 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
Break (AC inductive):..........................................720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................277 VAC / 10 A
TRIP / CLOSE SEAL-IN
Relay 1 trip seal-in:.............................................0.00 to 9.99 s in steps of 0.01
Relay 2 close seal-in:.........................................0.00 to 9.99 s in steps of 0.01
1.5.7 Power supply specifications
HIGH RANGE POWER SUPPLY
Nominal:..................................................................120 to 240 VAC
125 to 250 VDC
Range: ......................................................................60 to 300 VAC (50 and 60 Hz)
84 to 250 VDC
Ride-through time: .............................................35 ms
LOW RANGE POWER SUPPLY
Nominal:..................................................................24 to 48 VDC
Range: ......................................................................20 to 60 VDC
ALL RANGES
Voltage withstand: .............................................2 × highest nominal voltage for 10 ms
Power consumption: .........................................15 W nominal, 20 W maximum
20 VA nominal, 28 VA maximum
Courtesy of NationalSwitchgear.com

1–12 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
1.5.8 Communications specifications
SERIAL
RS485 port: ............................................................Opto-coupled
Baud rates: ............................................................up to 115 kbps
Response time: ....................................................1 ms typical
Parity: .......................................................................None, Odd, Even
Protocol:..................................................................Modbus RTU, DNP 3.0, IEC 60870-5-103
Maximum distance:...........................................1200 m (4000 feet)
Isolation: .................................................................2 kV
ETHERNET (COPPER)
Modes: .....................................................................10/100 MB (auto-detect)
Connector: .............................................................RJ-45
Protocol:..................................................................Modbus TCP, DNP3.0, iec 60870-5-104, IEC 61850 GOOSE
ETHERNET (FIBER)
Fiber type: .............................................................. 100 MB Multi-mode
Wavelength:..........................................................1300 nm
Connector: .............................................................MTRJ
Protocol:..................................................................Modbus TCP, DNP3.0, iec 60870-5-104, IEC 61850 GOOSE
Transmit power: ..................................................-20 dBm
Receiver sensitivity: ...........................................-31 dBm
Power budget:......................................................9 dB
Maximum input power:....................................-11.8 dBm
Typical distance: .................................................2 km (1.25 miles)
Duplex:.....................................................................half/full
USB
Standard specification:....................................Compliant with USB 2.0
Data transfer rate: .............................................115 kbps
1.5.9 Testing and certification
CERTIFICATION
ISO: ............................................................................Manufactured under an ISO9001 registered program
CE:..............................................................................Conforms to EN61000-6-2 / EN60255-26 / EN60255-27 /
EN61010-1 / EN60255-5
cULus:.......................................................................Conforms to UL 508 / UL 1053 and C22.2.14-05 (CSA)
UL:..............................................................................
UL listed for USA and Canada, E83849
Courtesy of NationalSwitchgear.com

CHAPTER 1: INTRODUCTION SPECIFICATIONS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 1–13
TYPE TESTS
Relative Humidity Cyclic:.................................IEC 60068-2-30: 55°C at 95% RH
Hot: ............................................................................IEC 60068-2-2 (Hot Start) 16 hours /+85°C
Cold: ..........................................................................IEC 60068-2-1 (Cold Start) 16 hours / -40°C
Dielectric Strength:.............................................IEC 60255-5: 2300 VAC
Insulation Resistance:.......................................IEC 60255-5: >100 MΩ/ 500 VDC / 10 s
Impulse Voltage:..................................................IEC 60255-5: 5 kV / 0.5 J
Sinusoidal Vibration:..........................................IEC 60255-21-1: 2 g, Class 2
Shock and Bump:................................................IEC 60255-21-2: 10 g / 20 g / 30 g, Class 2
Seismic:....................................................................IEC 60255-21-3: 2 g
Damped Oscillatory Burst:..............................IEC 60255-22-1: 1 MHz 2.5 kV / 1 kV
Electrostatic Discharge Immunity - Air
and Direct:.........................................................IEC 60255-22-2: 8 kV / 6 kV
Radiated RF Immunity:.....................................IEC 60255-22-3: 10 V/m (80 MHz to 1 GHz / 1.4 to 2.7 GHz)
Electrical Fast Transient / Burst
Immunity: ..........................................................IEC 60255-22-4: ±4 kV
Surge Immunity:..................................................IEC 60255-22-5: ±2 kV / 1 kV
Conducted RF Immunity:.................................IEC 60255-22-6: 150 kHz to 80 MHz 10 V/m
Radiated RF Emission: ......................................IEC 60255-25: EN55022, Class A
Conducted RF Emission: ..................................IEC 60255-25: EN55022, Class A
Ingress of Solid Objects and Water:...........IEC 60529: IP40 (front), IP10 (back)
Power Frequency Magnetic Field
Immunity: ..........................................................IEC 61000-4-8: 30 A/m, 1000 A/m, Class 5
Pulse Magnetic Field Immunity: ...................IEC 61000-4-9: 1000 A/m
Voltage Dip; Voltage Interruption:...............IEC 61000-4-11: 0%, 40%, 100%
Fast Transient SWC:...........................................IEEE C37.90.1: ±4 kV
Oscillatory Transient SWC: .............................IEEE C37.90.1: ±2.5 kV
Electrostatic Discharge - Air and Direct:..IEEE C37.90.3: ±8 kV / ±6 kV
1.5.10 Physical specifications
DIMENSIONS
Size: ...........................................................................Refer to section 2.1.1
Weight:.....................................................................4.1 kg [9.0 lb]
1.5.11 Environmental specifications
OPERATING ENVIRONMENT
Ambient operating temperature:................–40°C to +60°C [-40°F to +140°F]
Ambient storage / shipping
temperature:....................................................–40°C to +85°C [-40°F to +185°F]
Humidity:.................................................................up to 90% non-condensing
Pollution degree: .................................................2
Installation category:........................................I
Overvoltage category:......................................III
Courtesy of NationalSwitchgear.com
Other manuals for ML Series 350
3
Table of contents
Other GE Relay manuals