GE BAKER HUGHES DPS 5000 Series User manual


© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | i
Safety
The manufacturer has designed this sensor to be safe when operated using the procedures
detailed in this manual. Do not use this sensor for any other purpose than that stated.
This publication contains operating and safety instructions that must be followed for safe
operation and to maintain the sensor in a safe condition. The safety instructions are either
warnings or cautions issued to protect the user and the equipment from injury or damage.
Use qualified*personnel and good engineering practice for all procedures in this publication.
Toxic Materials
There are no known toxic materials used in this sensor.
Maintenance
The sensor must be maintained using the manufacturer’s procedures and these should be
carried out by authorized service agents or the manufacturer’s service departments.
www.gemeasurement.com
For technical advice contact the manufacturer.
WARNING Do not apply pressure greater the maximum safe working
pressure to the sensor.
* A qualified technician must have the necessary technical knowledge, documentation, special test
equipment and tools to carry out the required work on this equipment.

ii | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
Symbols
Abbreviations
The abbreviations in this publication are as follows:
Symbol Description
This equipment meets the requirements of all relevant European safety directives. The
equipment carries the CE mark.
This symbol, on the equipment, indicates a warning and that the user should refer to the
user manual.
Do not dispose of this product as household waste. Use an approved organization that
collects and/or recycles waste electrical and electronic equipment. For more information,
contact one of these:
- Our customer service department: www.gemeasurement.com
- Your local government office.
Abbreviation Description
a Absolute (Pressure version)
ADC Analogue-to-Digital Converter
A/F Across the Flats (Dimension data)
AP Applied Pressure
ASCII American Standard Code for Information Interchange
°C Celsius (Degrees)
CAN Controller Area Network
CANopen A set of standards that defines the operation of devices across a CAN system.
CiA CAN in Automation international users and manufacturers group (CiA e.V.)
COB Communication Object (CAN Message): Data is sent across a CAN Network inside
a COB.
COB-ID COB-Identifier. Identifies a COB uniquely in a Network and determines the priority
of the COB.
d Differential (Pressure version)
DC Direct Current
DPS Digital Pressure Sensor
EEC European Economic Community
EMC Electromagnetic Compatibility
EN European Norm
°F Fahrenheit (Degrees)

© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | iii
FP Floating Point
FS Full-scale. Refers to a full-scale value from a transducer or instrument.
FV Field Value
g Acceleration of Gravity
g Gauge (Pressure version)
gGram
Hz Hertz
ID Identifier
kbits/s Kilobits per second
LSS Layer Setting Services
Max Maximum
mbar Millibar
MIL-STD Military Standard
Min Minimum
mm Millimetre
ms Millisecond
MΩMegohm
NMT Network Management: One of the service elements of the CAN Application Layer
NPT National Pipe Taper (a thread standard)
PDO Process Data Object
PIN Personal Identification Number
psi Pound-force per square inch
PV Process Value
SDO Service Data Object
SDS Sales Data Sheet
SI Système International
S/N Serial Number
UNF Unified Fine (a thread standard)
V dc Volts Direct Current
Abbreviation Description

iv | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.

© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | v
Contents
1. Introduction 1
1.1 Applications 1
1.2 Summary of Facilities 1
1.3 Summary of the CANopen Set of Functions 2
2. Installation 3
2.1 Example CAN bus System 3
2.2 Installation – Before Starting 3
2.3 Installation – Procedures 4
2.3.1 Pressure Connections (Absolute) 4
2.3.2 Electrical Connections 4
2.3.3 Completing the Installation 4
3. Operation 5
3.1 Start Operating 5
3.2 Procedures 5
3.3 Quick Start 6
3.4 Primary Objects 6
3.5 To Change the Operation - Node ID and Baud Rate 6
3.6 To Change the Operation - Objects: 0x1000 - 0x1FFFF 6
3.6.1 0x100C to 0x100E - Error Control: Node Guarding Option 6
3.6.2 0x1017 – Error Control: Heartbeat Option 6
3.6.3 0x1010 01 – To Save Changes to the Data Dictionary 7
3.6.4 0x1011 01 – To Re-apply the Factory Values 7
3.6.5 0x1800 02 – The PDO Transmission (Type or Period) 7
3.6.6 0x1A00 – The Data in the ‘Transmit PDO’ 7
3.6.7 0x1F80 - NMT Start-up 7
3.7 To Change the Operation – Objects: 0x2000 – 0x2FFFF 8
3.7.1 0x210C– Node ID 8
3.7.2 0x210D – Bit Rate 8
3.7.3 0x2200 – To Change the Calibration Data 8
3.7.4 0x2201 to 0x2203 – The Last Calibration Year, Month, Day 8
3.7.5 0x2204 to 0x2206 – The Next Calibration Year, Month, Day 8
3.7.6 0x2207 – The Pressure Calibration Gain 9
3.7.7 0x2208 – The Pressure Calibration Offset 9
3.7.8 0x2209 – The Temperature Calibration Gain 9
3.7.9 0x220A – The Temperature Calibration Offset 10
3.7.10 0x220D to 0x2218 – The Filter System 10
3.7.11 0x2304 – The Tag for the Type of Data 10
3.8 To Change the Operation – Objects: 0x6000 – 0x6FFFF 10

vi | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
3.8.1 0x6120 to 0x6124 – The Scale Data for Pressure and Temperature
Output 10
3.8.2 0x6131 01 – The Units for the Pressure Output 11
3.8.3 0x6148 – The Local Limits (Minimum Pressure and Temperature) 11
3.8.4 0x6149 – The Local Limits (Maximum Pressure and Temperature) 11
3.9 To Monitor the Operation – Objects: 0x1000 – 0x1FFFF 12
3.9.1 0x1001 – The Status of the Unit 12
3.10 To Monitor the Operation – Objects: 0x2000 – 0x2FFFF 12
3.10.1 0x2006 – The Count: Pressure is More than the Limit 12
3.10.2 0x2007 – The Count: Pressure is Less than the Limit 12
3.10.3 0x2008 – The Count: Temperature is More than the Limit 13
3.10.4 0x2009 – The Count: Temperature is Less than the Limit 13
3.11 To Monitor the Operation – Objects: 0x6000 – 0x6FFFF 13
3.11.1 0x6130 01/0x6130 02 – The Pressure and Temperature 13
3.11.2 0x6150 – The Pressure and Temperature Status 13
4. Maintenance 15
4.1 Maintenance Tasks 15
4.2 Maintenance – From the Software 15
4.2.1 The Status of the Unit 15
4.3 Maintenance – Cleaning 16
4.4 Maintenance – Calibration 16
4.4.1 Calibration – Equipment 16
4.4.2 Two-Point Pressure Calibration – Procedure 16
4.4.3 Two-Point Pressure Calibration – Results 17
4.5 Approved Service Agents 17
Appendix A. CANopen Object Dictionary 19
A.1 Communication Segment 19
A.1.1 Object 1000h: Device Type 19
A.1.2 Object 1001h: Error Register 20
A.1.3 Object 1003h: Pre-defined Error Field 20
A.1.4 Object 1005h: COB-ID SYNC 21
A.1.5 Object 1007h: Synchronous Window Length 21
A.1.6 Object 1008h: Manufacturer Device Name 21
A.1.7 Object 100Ch: Guard Time 22
A.1.8 Object 100Dh: Life Time Factor 22
A.1.9 Object 1010h: Store Parameter Field 23
A.1.10 Object 1011h: Restore Default Parameters 23
A.1.11 Object 1012h: COB-ID Time Stamp 24
A.1.12 Object 1014h: COB-ID EMCY 24
A.1.13 Object 1015h: Inhibit Time Emergency 25
A.1.14 Object 1017h: Producer Heartbeat Time 25
A.1.15 Object 1018h: Identity Object 26

© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | vii
A.1.16 Object 1019h: Synchronous Counter Overflow Value 27
A.1.17 Object 1800h to 1803h: Transmit PDO Communication Parameter 1
28
A.1.18 Object 1A00h to 1A03h: Transmit PDO Mapping Parameter 1 28
A.1.19 Object 1F80h: NMT Start-up 30
A.2 Manufacturer Segment 30
A.2.1 Object 2003h: Current Time 30
A.2.2 Object 2004h: Acquisition Time 31
A.2.3 Object 2005h: Acquisition Interval 31
A.2.4 Object 2006h: Pressure Span Overflow Count 31
A.2.5 Object 2007h: Pressure Span Underflow Count 32
A.2.6 Object 2008h: Temperature Span Overflow Count 32
A.2.7 Object 2009h: Temperature Span Underflow Count 32
A.2.8 Object 210Ch: Node ID 33
A.2.9 Object 210Dh: Bit Rate 33
A.2.10 Object 2200h: Calibration Access Pin 33
A.2.11 Object 2201h: Last Calibration Year 34
A.2.12 Object 2202h: Last Calibration Month 34
A.2.13 Object 2203h: Last Calibration Day 34
A.2.14 Object 2204h: Next Calibration Year 35
A.2.15 Object 2205h: Next Calibration Month 35
A.2.16 Object 2206h: Next Calibration Day 35
A.2.17 Object 2207h: Pressure Gain 36
A.2.18 Object 2208h: Pressure Offset 36
A.2.19 Object 2209h: Temperature Gain 36
A.2.20 Object 220Ah: Temperature Offset 37
A.2.21 Object 220Dh: FIR Samples Size 37
A.2.22 Object 220Eh: FIR Sample Data 37
A.2.23 Object 2210h: FIR2 Sample Data 38
A.2.24 Object 2212h: FIR3 Sample Data 38
A.2.25 Object 2214h: FIR4 Sample Data 38
A.2.26 Object 2216h: FIR5 Sample Data 39
A.2.27 Object 2217h: Selected FIR Filter 39
A.2.28 Object 2218h: FIR Pre-scaler 39
A.2.29 Object 2300h: PDCR Min Pressure 41
A.2.30 Object 2301h: PDCR Max Pressure 41
A.2.31 Object 2302h: PDCR Type 41
A.2.32 Object 2304h: PDCR Text 41
A.3 Device Profile Segment 42
A.3.1 Object 6100h: AI Input FV 42
A.3.2 Object 6101h: AI Input Unit 43
A.3.3 Object 6110h: AI Sensor Type 43
A.3.4 Object 6120h: AI Input Scaling 1 FV 44
A.3.5 Object 6121h: AI Input Scaling 1 PV 45
A.3.6 Object 6122h: AI Input Scaling 2 FV 46
A.3.7 Object 6123h: AI Input Scaling 2 PV 46

viii | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
A.3.8 Object 6124h: AI Input Offset 47
A.3.9 Object 6130h: AI Input PV 48
A.3.10 Object 6131h: AI Physical Unit PV 49
A.3.11 Object 6148h: AI Span Start 50
A.3.12 Object 6149h: AI Span End 50
A.3.13 Object 6150h: AI Status 51
Appendix B. Alternative Pressure Units 53
Appendix C. Bibliography 55

Applications
© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | 1
1. Introduction
The transducers in the DPS 5000 series measure absolute pressure or gauge to produce fast,
accurate pressure data through a Controller Area Network (CAN) bus interface. All these
transducers include:
• CANopen software standards.
• Digital output.
• CAN bus serial communications interface.
Note: The prerequisites for this instruction manual are prior knowledge of the CANopen
protocols and standards. See Appendix C., “Bibliography,” on page 55 for more details.
1.1 Applications
The DPS 5000 series is for automated systems using a CAN bus network and CANopen
software standards. The pressure transducers in the DPS 5000 series are ideal for automated
systems with:
• A large amount of digital pressure data.
• A high level of accuracy over a wide temperature range.
• A sophisticated level of software control.
1.2 Summary of Facilities
Because all the transducers in the DPS 5000 series use CANopen software standards, each
transducer includes a CANopen Object Dictionary. Use the CANopen Object Dictionary to do
these primary tasks:
• Monitor the current pressure and temperature data.
• Tag the type of data. For example: Oil-mbar, H2O-mbar.
• Read the factory defined operating data. For example, the pressure range, and the
type of sensor.
• Set the update frequency for the pressure and temperature data.
• Set the pressure units.
• Monitor the current status.
• Read and set the last and next calibration date.
• Set new calibration values.
• Set local pressure and temperature limits for use with the internal out-of-limit
counters.
• Monitor the number of times the pressure is not in the specified limits.
• Monitor the number of times the temperature is not in the specified limits.
• Restore all the factory default values for the CANopen Object Dictionary.

Chapter 1. Introduction
2 | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
Use a standard CANopen software package to access the contents of the CANopen Object
Dictionary.
1.3 Summary of the CANopen Set of Functions
Function Comment
NMT Slave
Error Control Node Guarding or Heartbeat.
Node ID LSS (DSP-305 V1.0)
Number of PDO 4 transmit PDOs, no receive PDOs.
PDO Modes Event triggered or Remotely requested.
PDO Linking Yes
PDO Mapping Default
Emergency Message Yes
CANopen Version DS-301 V4.01
Framework No
Certified No
Device Profile DSP-404 V1.0
Maximum Baud Rate 1 Mbit/s

Example CAN bus System
© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | 3
2. Installation
This section details installation of the pressure transducer, when complete the pressure
transducer can be prepared for operation (refer to Chapter 3., “Operation,” on page 5).
2.1 Example CAN bus System
Figure 2-1: An Example CAN bus System
This shows the pressure transducers in an example CAN bus system and must have these
items:
• A CAN bus with an applicable input/output device for the signal lines (applicable to
the electrical connection on the pressure transducer).
• Power supply: 5 V dc to 30 V dc.
• All applicable tools to connect the pressure and electrical connections, as detailed in
the applicable system installation manual.
2.2 Installation – Before Starting
Make sure to use the correct pressure transducer (refer to Chapter 1., “Introduction,” on
page 1).
Read all relevant instructions and procedures in the applicable system installation manual.
Read the following installation procedures before installing the pressure transducer.
CANopen
software
package
ShirxmƉiwxliwmkreppmrigsrrigxmsrwsrxliMKXfyw
MefpiwgviirxsMKXQXNsverettpmgefpiievxl
\itviwirxwxlihmƇivirxtviwwyvigsrhmxmsrwmrxlii|eqtpiw}wxiq
Zs{ivwyttp}
CAN_GNDerhziwyttp}
CAN_H
CAN_L
CAN_X

Chapter 2. Installation
4 | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
2.3 Installation – Procedures
Note: Until installation, keep the unit in the original container with all the covers in
position. The container and covers prevent contamination and damage. When not in use,
keep the connections clean at all times, and put the covers on the open connections.
2.3.1 Pressure Connections (Absolute)
Connect the pressure transducer connection to the pressure system and torque tighten the
connection (refer to System Installation Manual).
2.3.2 Electrical Connections
Refer to the sales data sheet or customer specified drawing.
2.3.3 Completing the Installation
Do all the applicable tests and checks (refer to System Installation Manual).
After completing installation, the pressure transducer is ready for use.
WARNING Do not interchange transducers between an oil system
and a system that uses fuel or gas. This can cause an explosion that can
cause death or injury, and/or damage to equipment.
High pressures and temperatures are dangerous (refer to sales data
sheet or customer specified drawing). De-pressurize and allow to cool
components in a system that has high operating pressures and
temperatures.

Start Operating
© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | 5
3. Operation
This section includes:
• The procedures to start and change the operation of the pressure transducer.
• The available data from the pressure transducer.
Note: 0x identifies a hexadecimal value. Object 0x1800 02 = Index 0x1800,
Sub-index 0x02 (refer to Appendix A., “CANopen Object Dictionary,” on page 19).
3.1 Start Operating
After a successful installation (refer to Chapter 3., “Operation,” on page 5) and to start
operating requires:
• A CANopen software package to access the CANopen Object Dictionary.
• Operation of the CANopen network, including the Network Initialization Process (the
Boot-up process) and/or the applicable configuration procedures.
3.2 Procedures
1. Complete the boot-up procedure (defined in the CANopen standard) for the CAN bus
network. After boot-up the pressure transducer enters a “pre-operational” mode and
in this mode responds to SDO and LSS messages.
2. The pressure transducer must be set to its operational state to respond to sync
messages and to be fully operational.
Figure 3-1: Default ‘Transmit PDO’ Operation
Note: This shows how the pressure transducer uses the default values to transmit a
Process Data Object (PDO).
The readings can be filtered by a range of preset finite impulse response (FIR) filters. (refer to
“0x220D to 0x2218 – The Filter System” on page 10).
Use the CANopen software package to receive the PDO and get access to the CANopen
Object Dictionary.
Use the CANopen software package to change these values:
CAN bus SYNC
(Cycle period in ms)
PDO COB-ID = 0x181
Object 0x6130 01:
Pressure Value
Object 0x2004 00:
Acquisition Time

Chapter 3. Operation
6 | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
• Values set with the Layer Setting Services (LSS).
• Values in the CANopen Object Dictionary.
3.3 Quick Start
Get the current pressure and temperature values by using object 0x6130:
• Sub-item 01 returns the pressure value in the default pressure units.
• Sub-item 02 returns the temperature in degrees Celsius.
3.4 Primary Objects
The following procedures identify the primary objects that can be changed and monitored.
Refer to Appendix A., “CANopen Object Dictionary,” on page 19 for a complete list.
3.5 To Change the Operation - Node ID and Baud Rate
Use the CANopen Layer Setting Services (LSS) to change these primary objects in the
pressure transducer:
Note: To respond to LSS messages the pressure transducer must be in pre-operational
mode.
• The node ID (default value = 2).
• The baud rate (default value = 250 kbits/s).
In addition, object 0x210C can be used to modify the node ID. Object 0x210D holds the baud
rate.
To make changes to these and other data dictionary objects permanent, save them and cycle
the power to the sensor.
When using the LSS, the device must be identified. Object 0x1018 (identity) contains the
identification data. Refer to Appendix C., “Bibliography,” on page 55.
3.6 To Change the Operation - Objects: 0x1000 - 0x1FFFF
3.6.1 0x100C to 0x100E - Error Control: Node Guarding Option
To use Node Guarding for error control, set applicable values for these objects:
• 0x100C (Guard Time).
• 0x100D (Life Time Factor).
Refer to Appendix C., “Bibliography,” on page 55.
3.6.2 0x1017 – Error Control: Heartbeat Option
To use Heartbeat for error control, set applicable value for this object:
• 0x1017 (Heartbeat Time).

To Change the Operation - Objects: 0x1000 - 0x1FFFF
© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | 7
Refer to Appendix C., “Bibliography,” on page 55.
3.6.3 0x1010 01 – To Save Changes to the Data Dictionary
Use object 0x1010 01 (Store Parameter Field) to save the data dictionary to non-volatile
storage.
Example:
Set the value to 0x65766173 = evas (in ASCII)
Note: This does not overwrite the factory data and the sensor can be returned to its
factory state by using 0x1011 as described below.
3.6.4 0x1011 01 – To Re-apply the Factory Values
Use object 0x1011 01 (Restore Default Parameters) to re-apply all the factory values.
Example:
Set the value to 0x64616F6C = daol (in ASCII)
Having re-applied the factory values, the sensor should be power cycled for the values to be
applied.
3.6.5 0x1800 02 – The PDO Transmission (Type or Period)
Use object 0x1800 02 (Transmission Type) to change the type of PDO transmission or the
period between each PDO transmission (refer to Appendix C., “Bibliography,” on page 55).
3.6.6 0x1A00 – The Data in the ‘Transmit PDO’
Use object 0x1A00 (Transmit PDO Mapping) to change the data sent in the ‘Transmit PDO’
(maximum size = 8 bytes).
To change the transmit PDO, set bit 31 of 0x 1800 1 “COB-ID” to 1 and set 0x IA00 1 to 0.
After changing the PDO the process should be reversed.
Example:
To monitor the current status of the pressure value, set Sub-index 0x02 to
0x61500108 = Object 0x6150 01, 1 byte of data.
3.6.7 0x1F80 - NMT Start-up
Use object 0x1F80 to set the start-up mode of the sensor.
Status Description
0 The value is in the limits of 0x6148 and 0x6149.
1 The value is more than the limit of 0x6149.
2 The value is less than the limit of 0x6148.
Status Description
0 Sensor power-up in pre-operational mode.

Chapter 3. Operation
8 | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
3.7 To Change the Operation – Objects: 0x2000 – 0x2FFFF
3.7.1 0x210C– Node ID
Valid node ID can be in the range 0x01 to 0x7F. Changes to this value do not take effect unless
saved and the power cycled.
3.7.2 0x210D – Bit Rate
The bit rate at which the sensors communicate can be one of the following values:
Changes to the bit rate value does not take effect unless saved and the power cycled.
3.7.3 0x2200 – To Change the Calibration Data
To write new calibration values in objects 0x2201 to 0x220A, set object 0x2200 (Calibration
Access Pin) to 4118.
To prevent accidental changes to the calibration data, set the value to 0 after completing all
the changes.
3.7.4 0x2201 to 0x2203 – The Last Calibration Year, Month, Day
Refer to “0x2200 – To Change the Calibration Data” on page 8. The initial values identify the
date of the factory calibration. After each calibration, set a new date (refer to Chapter 4.,
“Maintenance,” on page 15).
3.7.5 0x2204 to 0x2206 – The Next Calibration Year, Month, Day
Refer to “0x2200 – To Change the Calibration Data” on page 8. The initial values identify the
date of the factory calibration + one year. After each calibration, set a new date (refer to
Chapter 4., “Maintenance,” on page 15).
Value Baud Rate
10 10 kbit/s
20 20 kbit/s
50 50 kbit/s
125 125 kbit/s
250 250 kbit/s
500 500 kbit/s
800 800 kbit/s
1000 1000 kbit/s

To Change the Operation – Objects: 0x2000 – 0x2FFFF
© 2018 Baker Hughes, a GE company – All rights reserved. DPS 5000 Series Instruction Manual-English | 9
3.7.6 0x2207 – The Pressure Calibration Gain
Refer to “0x2200 – To Change the Calibration Data” on page 8. Use 0x2207 (Pressure Gain) to
apply a correction to the compensated source pressure (refer to Chapter 4., “Maintenance,”
on page 15).
Figure 3-2: Pressure Calibration Gain
3.7.7 0x2208 – The Pressure Calibration Offset
Refer to “0x2200 – To Change the Calibration Data” on page 8. Use 0x2208 (Pressure Offset)
to apply a correction to the compensated source pressure (refer to Chapter 4.,
“Maintenance,” on page 15).
Figure 3-3: Pressure Calibration Offset
3.7.8 0x2209 – The Temperature Calibration Gain
Refer to “0x2200 – To Change the Calibration Data” on page 8. Use 0x2209 (Temperature
Gain) to apply a correction to the compensated source temperature.
Figure 3-4: Temperature Calibration Gain
Compensated
source
pressure
Object 0x2207:
Pressure Gain
Object 0x6100 01
Pressure Value
x Gain
correction
Field Value (mbar)
Compensated
source
pressure
Object 0x2208:
ZviwwyviYƇwix
YƇwix
gsvvigxmsr0qfev1
Object 0x6100 01
Pressure Value
Pmiph`epyi0qfev1
Compensated
source
temperature
Object 0x2209:
Temperature Gain
x Gain
correction (°C)
Object 0x6130 02:
Temperature Value
Process Value (°C)

Chapter 3. Operation
10 | DPS 5000 Series Instruction Manual-English © 2018 Baker Hughes, a GE company – All rights reserved.
3.7.9 0x220A – The Temperature Calibration Offset
Refer to “0x2200 – To Change the Calibration Data” on page 8. Use 0x220A (Temperature
Offset) to apply a correction to the compensated source temperature.
Figure 3-5: Temperature Calibration Offset
3.7.10 0x220D to 0x2218 – The Filter System
The DPS 5000 sensor can support a wide range of sample rates and filters to give a choice of
speed and accuracy. There are five filters, preset to a selection of values. Each filter is built of
two parts; a pre-scaler and a group of coefficients. It is beyond the scope of this manual to
describe the creation of these values.
The data dictionary item “Selected FIR Filter” at 0x2217 is used to choose a filter. When
changing to another filter, be aware of the 3 dB settling times below before taking new
values.
3.7.11 0x2304 – The Tag for the Type of Data
Use object 0x2304 (Tag) to identify the type of data that the pressure transducer supplies
(maximum: 10 characters). For example: Oil-mbar.
3.8 To Change the Operation – Objects: 0x6000 – 0x6FFFF
3.8.1 0x6120 to 0x6124 – The Scale Data for Pressure and
Temperature Output
The pressure transducer uses a two-point calibration to calculate the pressure output. The
two-point calibration includes the relation between the Field Value (FV) units and the
Process Value (PV) units. To change the relation between FV and PV, use the scale-factor
Filter Preset Filter Type Cut-off Frequency 3 dB Settling Time
0 No filter. 1400 Hz 0.7 ms
1 Averaging 10 samples. 44.3 Hz 22 ms
2a
a. Factory set default filter setting.
Averaging 50 samples. 8.86 Hz 100 ms
3 Butterworth low pass. 1 Hz 1000 ms
4 Butterworth low pass. 10 Hz 100 ms
5 Butterworth low pass. 17.18 Hz 60 ms
Compensated
source
temperature
Object 0x220A:
^iqtivexyviYƇwix
YƇwix
gsvvigxmsr0M1
Object 0x6130 02:
Temperature Value
Zvsgiww`epyi0M1
Other manuals for BAKER HUGHES DPS 5000 Series
1
Table of contents
Other GE Transducer manuals
Popular Transducer manuals by other brands

Balluff
Balluff BTL6-A301-M-A1-S115 Series user guide

Milltronics
Milltronics PL-590 instruction manual

Automationdirect.com
Automationdirect.com AcuAMP ACT Series installation instructions

MAMAC SYSTEMS
MAMAC SYSTEMS HU-224 installation guide

RDP Group
RDP Group D5 Series Technical manual

MKS
MKS UniMag 971B Operation and installation manual