GE SG Series User manual

Critical Power
Modifications reserved
Page 2/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Model:
SG Series 10 - 20 - 30 - 40 UL S0
Issued by
Product Document Department –Riazzino - CH
Approved by:
R & D Department –Riazzino - CH
Date of issue:
11/20/2013
File name:
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070
Revision:
7.0
Identification No.:
1024195
Up-dating
Revision
Concerns
Date
2.0
Modified Section 3.8.4 & 5 –Power connection dual input utility
08/25/2004
3.0
House-style GE Consumer & Industrial
01/30/2006
4.0
ECN 1251: GE Digital Energy –Power Quality / Table DC current rating
11/12/2008
5.0
ECN 1348 –Soft 3.30 & DSP 10.0
12/15/2009
6.0
ECN1548 - Safety Rules
02/25/2011
7.0
ECN 2079 (EPO for RPA Parallel System)
Customer Interface Board / SNMP card & GE Critical Power template
11/20/2014
COPYRIGHT © 2014 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not
necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.

Critical Power
Modifications reserved
Page 3/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE.
We trust that the use of the SG Series 10-20-30-40
Uninterruptible Power Supply system, developed and
produced to the highest standards of quality, will
give you complete satisfaction.
Please read carefully the Installation Guide, which
contains all the necessary information and describes
all you need to know about the installation of the
UPS.
Thank you for choosing GE !
START-UP AND COMMISSIONING
A GE GLOBAL SERVICES FIELD ENGINEER must perform start-up and
commissioning of the UPS.
Please Contact GE. GLOBAL SERVICES at least two weeks prior to schedule
start-up and commissioning at 1-800-637-1738, or by E-mail at
Distributed in the USA by:
Your service contact:
g
GE Consumer & Industrial SA
General Electric Company
CH –6595 Riazzino (Locarno)
Switzerland
www.gepowerquality.com
g
GE Digital Energy
Power Quality
2501 Pecan Street
Bonham, TX 75418
T: +1 800-637-1738
F: +1 903-640-0533
http://www.gedigitalenergy.com/ups
g
GE Digital Energy
Power Quality
830 West 40th Street
Chicago, IL 60609
24/7 T: 800-637-1738
24/7 T: 773-299-6600
F: 866-765-3595

Critical Power
Modifications reserved
Page 4/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Preface
Congratulations on your choice of a SG Series 10-20-30-40 Uninterruptible Power Supply
(UPS). It will help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the
switches, the meaning of the system events related to the front panel indication, and
provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the
installation site, and it provides weight, dimensions and procedures for moving, installing
and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE assumes no responsibility or liability for any losses or damages resulting from the use
of the information contained in this document.
NOTE!
SG Series 10-20-30-40 is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and Battery System.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed
only for parallel system.

Critical Power
Modifications reserved
Page 5/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Table of contents Page
1SAFETY RULES ................................................................................................................................................. 6
2LAYOUT............................................................................................................................................................. 9
2.1 LAYOUT SG SERIES 10 & 20................................................................................................................................................................... 9
2.2 LAYOUT SG SERIES 30 & 40.................................................................................................................................................................10
3INSTALLATION............................................................................................................................................... 11
3.1 TRANSPORT .................................................................................................................................................................................................11
3.1.1 Dimensions and weight ........................................................................................................................................................................ 11
3.2 DELIVERY ......................................................................................................................................................................................................12
3.3 STORAGE.......................................................................................................................................................................................................12
3.3.1 Storage of the UPS .................................................................................................................................................................................. 12
3.3.2 Storage of battery ................................................................................................................................................................................... 12
3.4 PLACE OF INSTALLATION......................................................................................................................................................................13
3.4.1 UPS location ............................................................................................................................................................................................... 13
3.4.2 Battery location ........................................................................................................................................................................................ 15
3.5 VENTILATION AND COOLING..............................................................................................................................................................16
3.6 UNPACKING.................................................................................................................................................................................................17
3.7 ELECTRICAL WIRING ...............................................................................................................................................................................19
3.7.1 Utility input connection ......................................................................................................................................................................... 19
3.7.2 Input/output over current protection and wire sizing............................................................................................................. 20
3.7.3 Battery over current protection and wire sizing........................................................................................................................ 21
3.8 WIRING CONNECTION ...........................................................................................................................................................................24
3.8.1 Power connections.................................................................................................................................................................................. 24
3.8.2 Power connection with common input utility of SG Series 10 & 20 .................................................................................. 27
3.8.3 Power connection with common input utility of SG Series 30 & 40 .................................................................................. 28
3.8.4 Power connection dual input utility of SG Series 10 & 20 ...................................................................................................... 29
3.8.5 Power connection dual input utility of SG Series 30 & 40 ...................................................................................................... 31
3.8.6 Battery connection of SG Series 10 & 20....................................................................................................................................... 33
3.8.7 Battery connection of SG Series 30 & 40....................................................................................................................................... 34
3.8.8 Set-up for SG Series 10-20-30-40 when functioning as frequency converter ............................................................. 35
3.9 RPA PARALLEL SYSTEM CONNECTION...........................................................................................................................................36
3.9.1 Power wiring of parallel units............................................................................................................................................................. 36
3.9.2 Parallel control bus connection......................................................................................................................................................... 37
3.9.3 Control bus cable location................................................................................................................................................................... 39
4CUSTOMER INTERFACE................................................................................................................................ 41
4.1 CUSTOMER INTERFACE..........................................................................................................................................................................41
4.1.1 Serial Port J3 .............................................................................................................................................................................................. 42
4.1.2 Output free potential contacts .......................................................................................................................................................... 42
4.1.3 Programmable input free contacts ................................................................................................................................................. 43
4.1.4 Gen Set Signaling (GEN ON)................................................................................................................................................................. 43
4.1.5 AUX external Maintenance Bypass.................................................................................................................................................. 43
4.1.6 Auxiliary Power Supply (APS) 24 Vdc ............................................................................................................................................... 43
4.1.7 “EPO - Emergency Power Off” command connection............................................................................................................. 44
5NOTES............................................................................................................................................................. 46
5.1 NOTES FORM ..............................................................................................................................................................................................46

Critical Power
Modifications reserved
Page 6/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
1SAFETY RULES
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 10-20-30-40 that should be followed
during installation and maintenance of the UPS and battery.
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- End user must follow applicable regional occupational safety codes/regulations during installation,
operation and equipment maintenance. This may require additional field marking or labeling defining
appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our Technical Support for product specific information.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.

Critical Power
Modifications reserved
Page 7/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch
them.
6Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.

Critical Power
Modifications reserved
Page 8/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may
occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) –GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.

Critical Power
Modifications reserved
Page 9/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
2LAYOUT
2.1 LAYOUT SG Series 10 & 20
Fig. 2.1-1 SG Series 10 & 20 general view
Fig. 2.1-2 SG Series 10 & 20 general view with open doors
Fig. 2.1-3 SG Series 10 & 20 general view with optional 5th harmonic filter
and removed protection panels
1Opening for top cable entry
2Opening for bottom cable entry
3Terminals for Utility input and load
output
4Terminals for external Battery
connection
5Battery Shelf
CR Connectivity Rack
XA Terminals for 24Vdc Auxiliary
Power Supply connection
XB Terminals for EPO connection
SGT5000_030-040_UPS_GE_02a
SGT5000_010-020_UPS_GE_03
SGT5000_010-020_UPS_GE_04
4
1
2
5
CRXA XB
3

Critical Power
Modifications reserved
Page 10/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
2.2 LAYOUT SG Series 30 & 40
Fig. 2.2-1 SG Series 30 & 40 general view
Fig. 2.2-2 SG Series 30 & 40 general view with open doors
Fig. 2.2-3 SG Series 30 & 40 general view with optional 5th harmonic filter
and removed protection panels
1Opening for top cable entry
2Opening for bottom cable entry
3Terminals for Utility input and load
output
4Terminals for external Battery
connection
CR Connectivity Rack
XA Terminals for 24Vdc Auxiliary
Power Supply connection
XB Terminals for EPO connection
SGT5000_030-040_UPS_GE_02a
SGT5000_030-040_UPS_GE_03
Q1 Q2
ON
OFF
OFF
ON
SGT5000_030-040_UPS_GE_04
4
1
3
2XBXA CR
OFF
ON
OFF
ON

Critical Power
Modifications reserved
Page 11/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3INSTALLATION
3.1 TRANSPORT
Forklift
Crane
Fig. 3.1-1 UPS cabinets moving
Transport UPS only in upright position!
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the center of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.
Move the UPS in it’s original package to the final
destination site.
Do not stack other packages on top: This could damage
the UPS.
If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS.
NOTE !
Check for sufficient floor and elevator
loading capacity.
3.1.1 Dimensions and weight
Fig. 3.1.1-1 UPS cabinet dimensions
Dimensions SG Series 10-20-30-40
(W x D x H)
26.78 x 31.50 x 70.90 inches
680 x 800 x 1,800 mm
Weight SG Series 10-20-30-40
UPS rating
kVA
UPS without battery
UPS with battery
Weight
lbs / kg
Floor loading
lbs/sq.ft - kg/m2
Weight
lbs / kg
Floor loading
lbs/sq.ft - kg/m2
SG Series 10
735 / 333
126 / 613
1,121 / 508
192 / 934
SG Series 20
763 / 346
131 / 637
1,169 / 530
200 / 975
SG Series 30
970 / 440
166 / 809
–
–
SG Series 40
1,147 / 520
196 / 956
–
–
P.S.: Weights including the 5th harmonic filter.
SGSU_030-040_UPS dimensions_GE_01aUS
W
D
H

Critical Power
Modifications reserved
Page 12/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.2 DELIVERY
When delivered, inspect the package integrity and the physical conditions of the cabinets carefully.
In case of any damage sustained during transport, immediately inform the carrier and contact your
local Service Center.
A detailed report of the damage is necessary for any insurance claim.
NOTE !
A DAMAGED UPS MUST NEVER BE INSTALLED OR CONNECTED TO UTILITY OR
BATTERY!
3.3 STORAGE
3.3.1 Storage of the UPS
The UPS is carefully packed for transport and storage so that it is in perfect condition when installed.
Never leave a UPS outside the building and don’t store other packages on the top of the UPS.
It is advisable to store the UPS in its original package in a dry, dust-free room, away from chemical
substances, and with a temperature range not exceeding -13°F (-25°C) to 131°F (55°C).
In case the battery is included please refer to Section 3.3.2.
Some important functions of the UPS, such as the customized functions, are defined by parameters
stored in a RAM memory.
A small backup battery located on the Control Unit board supplies the RAM.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized
Service Center before putting the UPS into operation.
3.3.2 Storage of battery
When the delivery includes a maintenance free battery, keep in mind that they are subject to self-
discharge and therefore you must recharge the battery.
The storage time without battery recharge depends on the temperature of the storage site.
The optimal room temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed
the range -4°F (-20°C) to 104°F (40°C).
Recharge stored maintenance free battery every:
6 months when the storage temperature is 68°F (20°C)
3 months when the storage temperature is 86°F (30°C)
2 months when the storage temperature is 95°F (35°C)

Critical Power
Modifications reserved
Page 13/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.4 PLACE OF INSTALLATION
3.4.1 UPS location
WARNING !
A QUALIFIED ELECTRICAL CONTRACTOR must carry out the installation and cabling
of the UPS.
If optional cabinets and accessories are included with the UPS, please refer to those
accompanying manuals for installation and operating instructions.
It is important to have a clean, dust-free environment provided with proper ventilation and air-
conditioning to keep the ambient temperature within the specified operating range.
The recommended air inlet temperature is from 68°F (20°C) to 77°F (25°C) (max. 104°F / 40°C).
Refer to Section 3.5.
Check for sufficient floor load capacity before installing the UPS and the battery.
Refer to Section 3.1.1.
For battery installation follow the local codes and the recommendation of the battery supplier.
NOTE !
Temperature is very important for valve-regulated batteries (maintenance free).
Operation at temperatures higher than 77°F (25°C) will reduce battery life.
The SG Series 10-20-30-40 UPS can radiate radio frequency energy.
Although some RFI filtering is inherent to the UPS there is no guarantee that the UPS will not influence
sensitive devices such as cameras and monitors that are positioned close by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
A single-phase power outlet (120Vac) should be provided near the UPS for connection of power tools,
test equipment or connectivity devices. This outlet must be grounded.
Positioning of the UPS SG Series 10-20-30-40
Fig. 3.4.1-1 SG Series 10-20-30-40 clearances
The rear panel of the UPS may be mounted flush to a
wall or other structure.
Clearance around the front of the unit should be
sufficient to enable free passage of personnel with the
doors fully open, and to allow sufficient airflow to the
door vents.
Check Section 110-26(A) of the NEC code for specific
requirements.
Recommended minimum clearance between ceiling
and top of the UPS should be 16” (400 mm) for proper
cooling air exhaust.
In case of additional cabinets (external batteries or
input, output transformers) these can be placed on
either side of the cabinet.
SGSU_030-040_UPS disposition_GE_01a
16" / 400mm
Min.

Critical Power
Modifications reserved
Page 14/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Openings for input and output cable connections
Fig. 3.4.1-2 Opening on top of the cabinet for input and
cables of SG Series 10 & 20
Fig. 3.4.1-3 Opening on top of the cabinet for input and
cables of SG Series 30 & 40
Fig. 3.4.1-4 Opening on the bottom of the cabinet for input and
output cables SG Series 10-20-30-40
SG Series 10-20-30-40 openings are
provided on the top and the bottom of the
UPS for the connection of input and output
cables.
Pay attention to the position of these
openings, when choosing the placement of
the UPS.
These openings are covered with a
protective plate.
Positioning of the UPS cabinet
SG Series 10-20-30-40 is equipped with
wheels for easy placement of the UPS.
To make the UPS movable on wheels, the
bolts on each leg of the cabinet have to be
turned counter-clockwise, until they are
free from the floor and thus the cabinet
supported on wheels.
After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise,
but the wheels must still touch the floor.
Fig. 3.4.1-4 Bolts for the regulation of the cabinet
The UPS cabinet is free
standing and normally does
not require to be bolted to
the floor.
The UPS cabinet can be fixed
however to the floor by
bolting it with the supporting
blocks to the floor.
The supporting blocks can be
used in different positions (0°
- 360°)
These supporting blocks are
part of the shipping package.
See Fig. 3.4.1-5.
Fig. 3.4.1-5 Fixing of the UPS cabinet on the floor
SGT5000_010-020_UPS view top_01US
31.50"
800mm
9.06"
1.58"
40mm
230mm
9.06"
70mm
2.76"
26.78"
680mm
230mm
Utility input
Output Load
Battery
SGT5000_030-040_UPS view top_01US
31.50"
800mm
13.78"
1.58"
40mm
110mm
4.33"
70mm
2.76"
26.78"
680mm
350mm
Utility input
Output Load
Battery
SGT5000_030-040_UPS view bottom_01US
26.78"
680mm
7.09"
180mm
70mm
2.76" 50mm
1.97"
7.88"
200mm 31.50"
800mm
Utility input
Output Load
To lower
To lift
SGSU_050-080_UPS wheels_01aUS
SGSU_010-020_UPS fixing_01a
0 - 360°

Critical Power
Modifications reserved
Page 15/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.4.1-6 RPA system disposition
In case of parallel system, try to place
the UPS modules in sequence of their
numbers (marked on the packing).
If the units are positioned “side by side”,
the side panels must be mounted on all
units.
3.4.2 Battery location
Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.
The battery can be install immediately adjacent to the UPS (left or right side) or remotely from the UPS.
If the battery is installed remotely from the UPS, a wall mounted DC disconnect device must be installed
within line-of-site to both the UPS and the battery.
The optimal room temperature for Battery location is 68°F (20°C) to 77°F (25°C) and shall never exceed
the range -4°F (-20°C) to 104°F (40°C).
The life of valve-regulated batteries will be reduced by 50% for each additional 18°F (10°C) that the
battery ambient temperature is above 77°F (25°C).
The battery system associated with larger UPS is usually either rack mounted or installed in multiple
battery cabinets.
Installation and assembly must be made according to the local standards and battery system
manufacturer‘s recommendations.
The battery circuit breaker or battery fuse box must be mounted as near as possible to the battery.
NOTE !
Battery installation and connection must be performed by QUALIFIED PERSONNEL
ONLY.
Read all safety instructions before proceeding with the installation.
SGSU_050-080_RPA disposition_GE_01aUS
UPS 1
UPS
3 - 4 - 5 - 6 - 7 - 8
UPS 2

Critical Power
Modifications reserved
Page 16/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.5 VENTILATION AND COOLING
Fig. 3.5-1 Installation on plain floor
Fig. 3.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
Air filtration systems could be required when the UPS operates in a dirty environment.
Contact your Dealer or the nearest Service Center for appropriate solutions.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
The below table indicates the heat dissipation at full load at PF = 0.8 lag. and charged battery, up to
3,280 ft (1,000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
UPS rating
kVA
Losses
Cooling air flow
BTU / hr
kW
CFM
m3 / h
SG Series 10
3,036
0.89
135
230
SG Series 20
6,751
1.98
301
512
SG Series 30
8,104
2.37
361
614
SG Series 40
10,808
3.17
482
819

Critical Power
Modifications reserved
Page 17/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.6 UNPACKING
NOTE !
Check for sufficient floor and elevator loading capacity.
Take care not to damage the UPS when moving by forklift.
Remove the cabinet from the pallet with care because of the heavy weight of the
equipment.
The UPS and battery cabinets may be shipped packaged in carton boxes or in wooden crates (if
requested).
Move the cabinets as close as possible to the final location before removing from the pallet.
To unpack the cabinet packaged in Carton Box follow the instructions below:
1
2
Make sure to have sufficient space around
the UPS before you start unpacking.
Cut the three straps “A”fixing the carton box.
Remove package “B”and “C”.
Remove the protection “D” outside the cabinet
and the accessories bag.
Remove the wooden support “E”, which must be
used to hoist the UPS.
Unscrew anchoring bolt “F” from plate on all
four legs.
3
4
Position the fork lift “G” with an opening
between the forks of 33.50” (850mm).
Insert the wooden support “E”underneath
the UPS, paying attention that the 2 guides
“E1”are positioned with the UPS in the center.
Lift the UPS cabinet.
Remove the wooden pallet “H”.
Loosen the 4 screws “I”and remove then the 4
anchoring plates “L”.
Put the UPS down on the floor.
Remove finally the wooden support “E”.

Critical Power
Modifications reserved
Page 18/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
To unpack the cabinet packaged in Wooden Crate follow the instructions below:
1
2
Make sure to have sufficient space
around the UPS before you start
unpacking.
Remove the wooden sides “A”and “B”loosening the
appropriate screws.
Remove the protection “C” outside the cabinet and the
accessories bag.
Remove the wooden support “D”, which must be used
to hoist the UPS.
Unscrew anchoring bolt “E” from plate on all four legs.
3
4
Position the fork lift “F” with an opening
between the forks of 33.50” (850mm).
Insert the wooden support “D”
underneath the UPS, paying attention
that the 2 guides “D1”are positioned
with the UPS in the center.
Lift the UPS cabinet.
Remove the wooden pallet “G”.
Loosen the 4 screws “H”and remove then the 4
anchoring plates “I”.
Put the UPS down on the floor.
Remove finally the wooden support “D”.
Included in the delivery you can find the following parts:
An accessories bag Control Bus cables (only for RPA parallel system)
NOTE !
A damaged UPS must never be installed or connected to mains or battery!
In case of any damage sustained during the transport, immediately inform the
shipping agent!
A detailed report of the damage is necessary for any indemnity claim.
Packing material recycling
GE, in compliance with environment protection, use only environmentally
friendly material.
UPS packing materials must be recycled in compliance with all applicable
regulations.

Critical Power
Modifications reserved
Page 19/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.7 ELECTRICAL WIRING
WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL ONLY.
It is the responsibility of the installation technician to ensure that all local and
national electric codes are adhered to.
3.7.1 Utility input connection
NOTE !
Ensure that the AC and DC external isolators are OFF and locked out to prevent their
inadvertent operation.
Do not apply power to the equipment prior to the commissioning by a qualified
service engineer.
Before any other input connection, connect and check the grounding wire.
The UPS has available input terminations for the Rectifier and Bypass.
The unit may be powered from a common input source or dual input sources if desired.
Dual Input Configuration Rectifier & Bypass (recommended)
The Bypass and Rectifier inputs are to be powered from different Utility supplies (F1 and F2 inputs).
In this case, when the Rectifier Input Fuses are opened, the Bypass and the Manual Bypass are
supplied by the other source.
In this case, REMOVE the interconnection links BR1, BR2 and BR3 on the input
terminals or bus bars.
See Fig. 3.8.4-2 for SG Series 10 & 20 and Fig. 3.8.5-2 for SG Series 30 & 40.
Common input Rectifier & Bypass
The same power source is to be used for both Bypass Supply and Rectifier Input (input F3). Bear in
mind that when the Utility Fuses are opened there is a supply failure to the Rectifier as well as to the
Bypass and Manual Bypass.
In this case, the interconnection links BR1, BR2 and BR3 on the input terminals or
bus bars MUST REMAIN CONNECTED.
See Fig. 3.8.4-2 for SG Series 10 & 20 and Fig. 3.8.5-2 for SG Series 30 & 40.
Dual Input Configuration Rectifier & Bypass
Common input Rectifier & Bypass
Fig. 3.7.1-1 Dual Input Configuration Rectifier & Bypass
Fig. 3.7.1-2 Common Input Rectifier & Bypass
1 = Rectifier
2 = Inverter
3= Automatic Bypass
4= Manual Bypass
6 = Load
5 = Utility input
7 = Battery

Critical Power
Modifications reserved
Page 20/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.7.2 Input/output over current protection and wire sizing
The cabling of the UPS system has to be sized according to the UPS power rating.
Sizing of circuit breakers, fuses and cables for Input Utility, Output Load and Battery must meet the
requirements of local and national electrical codes.
Before connecting the UPS, verify that the Utility Voltage and Frequency, the Output Load Voltage and
Frequency and Battery Data (cells number, floating voltage, autonomy) are according to the required
specifications.
Output load configuration may be such that one phase may carry a load current at 100% of that phases
maximum current rating while the other two phases run at 0% or any combination in between.
Ensure that the load does not consist of any equipment that may require high starting currents such as
electric motors, laser printers, etc.
This may cause the UPS to occasionally go into Bypass due to overload conditions
To choose the correct input fuses or circuit breaker, consider the available short-circuit current of the
system up-stream.
Choose the correct fuse or breaker using current data shown in the chart and the appropriate NEC
code.
The ratings indicated in the following chart do not consider any line voltage drop.
In case of optional input transformer the input protective devices should be sized to allow the
transformer magnetization inrush current.
Caution when using four-pole circuit breakers as protection.
A potential problem exists for situations with non-linear loads:
The neutral current could be greater than the phase currents.
The three-phase Utility power supply must be symmetrical with respect to ground, due to the existence
of voltage surge protection devices inside the UPS.
NOTE !
If you use ELCB breaker (Earth Limiting Circuit Breaker) to protect the input
connections, consider the high leakage current generated by the noise suppression
capacitors.
If these ELCB breakers are strictly necessary, we suggest using the largest type
suitable for non-linear current and for delayed operations.
To ensure coordination when the UPS is configured for Separate Bypass and Rectifier Inputs, special care
must be taken in choosing the fuse or circuit breaker ratings installed in the output distribution circuits.
Protective devices on the output of the UPS should be coordinated with the Bypass Input circuit
protection.
Due to the relatively low short circuit capability of the UPS inverter, a short circuit in the load will cause
an immediate transfer to Bypass.
The largest fuse or circuit breaker in the output distribution should be rated at no more than 60% of the
rating of the protective device supplying the Bypass line.
If circuit selectivity is required while the load is fed from the inverter (Bypass Utility not available), the
largest fuse or circuit breaker should be rated at no more than 20% of the UPS output current rating.
Table of contents
Other GE UPS manuals

GE
GE Digital Energy SG Series User manual

GE
GE GT6000 User manual

GE
GE Uninterruptible Power Supply User manual

GE
GE 750 UL S2 User manual

GE
GE Digital Energy User manual

GE
GE 225 User manual

GE
GE Match lite 500 User manual

GE
GE On-line VH Series User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE Digital Energy LP 11 User manual

GE
GE 600 - 1500 VA User manual

GE
GE Power Supply User manual

GE
GE Match User manual

GE
GE Digital Energy VH 700 User manual

GE
GE 400 Series User manual

GE
GE TLE series 600 User manual

GE
GE 8 Series User manual

GE
GE LanPro 11 U User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE GT Series User manual