ST3 1-3kVA Service Manual Rev.1
Allis Electric Page 3 of total 12 September 2006
3. Troubleshooting
3.1 Quick Start
Before any check of UPS, please check the components as listed in the following table. This action could help you find
problem quickly and make sure these components good or not first.
Possible Circuit Block Coded Components Description Failure Mode
BAT FUSE 1K/3K:F1/F2;2K:F1 Fuse Open
I/P FUSE (on PSDR) F3, Fuse Open
2K/3K:D16, D17, REC02
1K:D10, D11, REC1
Diode Short or open
PFC Correction
2K/3K:Q09,1K:Q14 IGBT C-E short or open
2K/3K:Q04, Q05, Q06Q07
1K:Q4, Q6, Q10Q11
MOSFET D-S short or open
Push-Pull Booster
2K/3K:D05, D06, D07, D08
1K:D12, D13, D14, D15
Power Diode Short or open
Inverter 2K/3K:Q13, Q14, Q15, Q16
1K:Q12, Q13
IGBT C-E short or open
Charger module Q2 MOSFET D-S short or open
D10,D11,D12,D13D15 Power Diode Short or open
SPS module Q201 MOSFET D-S short or open
D202,D203 Power Diode Short or open
If the fuse is open, replacing fuse only, DO NOT mean you have solved the problem. General
speaking, fuse open was caused by other failure of components; therefore, you must find the
real defective components and replace them, before restart the UPS.