GE Digital Energy LP 11 User manual

GE Consumer & Industrial
Power Protection
OPERATING MANUAL
Digital Energy™ LP 11
Uninterruptible Power Supply
3-5-6-8-10 kVA

OPERATING MANUAL Digital Energy LP 3/5/6/8/10-11 UPS
LX-DOC File: OPM_LPE_11X_3K0_10K_1GB_V041
Manual version 4.1 Software version R2.11
OPERATING MANUAL
Digital Energy™ LP 11
Uninterruptible Power Supply
3-5-6-8-10 kVA
Preface
We thank you for selecting a General Electric Digital Energy™ LP Series Uninterruptible Power Supply
(UPS) and recommend that you read these instructions carefully before installation and start-up of the UPS.
Please keep this manual in a safe place for future reference and carefully read the important safety instructions
in chapter 1 before installation of this device.
© 2006 by GE Industrial Systems
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety,
without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
OPM_LPE_11X_3K0_10K_1GB_V041 1GE DE LP 11 UPS: User manual 4.1 (GB)

OPM_LPE_11X_3K0_10K_1GB_V041 2GE DE LP 11 UPS: User manual 4.1 (GB)
CONTENTS
1 IMPORTANT SAFETY INSTRUCTIONS...................................................................3
1.1 Save these instructions
1.2 General
1.3 Installation
1.4 Storage
1.5 Batteries
2 INTRODUCTION .......................................................................................................5
2.1 Description
2.2 Warranty
3 FUNCTIONAL EXPLANATION..................................................................................6
3.1 Principles of operation
3.2 Normal conditions
3.3 Utility failure
3.4 Automatic bypass switch
3.5 Manual bypass switch
4 INSTALLATION..........................................................................................................8
4.1 Transport
4.2 Unpacking
4.3 Package contents
4.4 Location
4.5 Installation
4.5.1 LP 3/5/6-11: standard installation procedure
4.5.2 LP 3/5/6-11: installation of Digital Energy™ LP battery extension pack(s)
4.5.3 LP 8/10-11: standard installation procedure
4.5.4 LP 8/10-11: installation of Digital Energy™ LP battery extension pack(s)
4.5.5 LP-11 series: 2 / 3 / 4 parallel operating units – additional info
5 OPERATION.............................................................................................................16
5.1 Description of front and rear panel
5.2 Start-up
5.3 Use
5.3.1 Information menu
5.3.2 Status and alarm menu
5.3.3 Service menu
5.3.4 Set-up menu
5.4 Test screens
5.4.1 Battery test, general
5.4.2 Quick battery test
5.4.3 Deep battery calibration test
5.5 Other features
5.5.1 Shutdown
5.5.2 Start without batteries
5.5.3 Sleep and wake-up
5.5.4 Overload protection in bypass mode
5.5.5 ECO-Mode
5 5.6 Auto restart
5.5.7 Superior battery management
6 INTERFACING FEATURES.....................................................................................29
6.1 RS232/Contact interface
6.2 Emergency shutdown
6.3 Relay card (optional)
6.4 SNMP interface (optional)
7 OPTIONAL FEATURES...........................................................................................30
7.1 Extended runtime versions
7.2 Plug-in cards
7.3 RPA-facility (Redundant Parallel Architecture)
8 MAINTENANCE .......................................................................................................31
8.1 General
8.2 Cooling fan
8.3 Batteries
8.4 Safety
8.5 Storage
8.6 Recycling the UPS at the end of service life
9 TROUBLESHOOTING.............................................................................................32
10 SPECIFICATIONS....................................................................................................33
APPENDIX: INSTALLATION DRAWINGS

1 - Important Safety Instructions
1.1 Save these instructions
This manual contains important instructions that should be followed during installation and maintenance
of the UPS. It also gives all necessary information about the correct use of the UPS.
Full understanding and compliance of the safety instructions and warnings contained in this manual are
the ONLY CONDITION to avoid any dangerous situation during installation, operation and
maintenance work, and to preserve the maximum reliability of the UPS system.
GE refuses any responsibility in case of non-observance, unauthorized alterations or improper use of
the delivered UPS.
Before attempting to install and start up the UPS, carefully read this manual. Keep this manual next to
the UPS for future references. All servicing must be done by qualified personnel. Do not attempt to
service the UPS unless you have had proper training.
CAUTION: By opening or removing covers you run the risk of exposure to dangerous voltages!
While every care has been taken to ensure the completeness and accuracy of this manual, GE
accepts no responsibility or liability for any loss or damage resulting from the use of the information
contained in this document.
This document shall not be copied nor reproduced without the permission of GE.
Due to technical improvements, some of the information contained in this manual may be changed
without notice.
1.2 General
•CAUTION: RISK OF ELECTRIC SHOCK Do not remove the cover, there are no user serviceable parts
inside. All maintenance and service work should be performed by qualified service personnel.
•The UPS contains batteries. The output terminals may be electrically live, even when the UPS is
disconnected from the utility supply. Dangerous voltages may be present during battery operation. The
batteries must be disconnected during maintenance or service work.
•The UPS contains potentially hazardous voltages.
WARNING: This is a Class A-UPS product. In a domestic environment this product may cause radio
interference, in which case the user may be required to take additional measures.
1.3 Installation
•Move the UPS in an upright position and in its original package to the final destination room.
•To lift the UPS, use a forklift or lifting belts with spreader bars.
•Check for sufficient floor and elevator loading capacity.
•Check carefully the integrity of the UPS equipment. In case you note some visible damage, do not
connect any voltage to the UPS but contact the nearest Service Centre.
•This UPS is intended to be used in a controlled indoor environment and free of conductive
contaminants and protected against animal intrusion.
•The UPS should only be powered from a single phase, three wire AC source equipped with an earth
connection.
•Do not install the UPS in an excessively humid environment or near water.
•Avoid spilling liquids or dropping any foreign object into the UPS.
•The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed
40°C. Optimal battery lifetime is obtained if the ambient temperature does not exceed 30°C.
•It is important that the unit has adequate ventilation. Maintain air movement around and through the
unit. Do not block the air vents.
•Avoid placing the unit in direct sunlight or near heat sources.
•Do not plug household appliances such as electric heaters, toasters or vacuum cleaners into the UPS.
The UPS output is intended to be used only for electronic loads such as computers and
telecommunications equipment.
OPM_LPE_11X_3K0_10K_1GB_V041 3GE DE LP 11 UPS: User manual 4.1 (GB)

1.4 Storage
•Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20
and +45°C.
•If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the unit to the mains and switch it on:
- if the storage temperature is within -20 and +30°C, recharge the batteries every 3 months, for 24
hours,
- if the storage temperature is within -20 and +45°C, recharge the batteries every month, for 24 hours.
1.5 Batteries
•NOTE: All maintenance and service work, including battery replacement, should be performed by
qualified service personnel.
•When replacing the batteries, use only the same type and size battery.
•Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and use only insulated tools.
•Avoid charging in a sealed container.
•Never dispose of batteries in a fire: they may explode.
•Do not open or mutilate batteries: their contents may be extremely toxic. If exposed to electrolyte, wash
immediately with plenty of water.
•Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.
OPM_LPE_11X_3K0_10K_1GB_V041 4GE DE LP 11 UPS: User manual 4.1 (GB)

2 - Introduction
2.1 Description
More than ever before, today's advanced electronic equipment, with complex integrated circuits and other
sensitive electronics, needs a stable and continuous AC power supply to operate correctly. While the power
coming from the wall outlet is often unreliable, a GE Digital Energy™ LP UPS provides the security of
completely uninterrupted power.
A compact, truly on-line system, the LP UPS protects your equipment from all forms of power interference,
including complete power failure. A simple and elegant circuit design, together with extensive protection against
abnormal operating conditions (e.g. overload, short circuit, overheating), makes the LP UPS exceptionally
reliable.
Figure 1. The GE Digital Energy™ LP 11 UPS: 3/5/6-11 (front) and 8/10-11 (rear)
2.2 Warranty
GE Digital Energy, operating through its authorized agents, warrants that the standard products will be free of
defects in materials and workmanship for a period of 24 months (12 months for the battery) after the date of
invoice, or such other period as may be specified.
NOTE: This warranty does not cover failures of the product which result from incorrect installation,
misuse, alterations by persons other than authorized agents, or abnormal operating conditions.
OPM_LPE_11X_3K0_10K_1GB_V041 5GE DE LP 11 UPS: User manual 4.1 (GB)

3 - Functional Explanation
3.1 The Principles of Operation
The UPS stores electric energy in batteries. This allows the UPS to supply output power even when the
incoming utility power is cut off completely.
Energy is stored as Direct Current (DC), while input and output energy must be Alternating Current (AC).
Therefore the UPS contains an input converter (AC to DC) and an output converter (DC to AC). (fig.2)
3.2 Normal Conditions
Under normal conditions, energy from the utility is channelled through the input converter, which supplies the
output converter and the battery charger. The batteries are kept in a fully charged state, and the output
converter synthesizes a completely new AC output sine wave to supply the load (electrical equipment).
TO LOAD
AUTOMATIC
BYPASS
SWITCH
FRONT
PANEL
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
OUTPUT:
PERFECT UPS POWER
1-PHASE
MAINS INPUT
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
INPUT:
MAINS POWER WITH DISTURBANCES
Figure 2. Block diagram of the LP 11 UPS, mains present
3.3 Utility Failure
In the event of a utility power failure (i.e. absent or outside tolerance) the system uses the energy reserve
stored in the battery to continue to produce AC power, ensuring unbroken output (fig. 3). No interruption or
alteration will ever be noticed in the output power.
In the event of an extended utility failure, the output converter will stop when the battery has been discharged.
At this point, the UPS is no longer able to power the connected equipment.
When the utility is re-established within tolerance, the output converter will restart automatically (if stopped, see
above) and will be supplied again by the input converter. The batteries will be recharged, making them ready to
support future power failures.
TO LOAD
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
AUTOMATIC
BYPASS
SWITCH
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
FRONT
PANEL
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
NO INPUT:
MAINS FAILURE (BLACK OUT)
OUTPUT:
PERFECT UPS POWER
Figure 3. Block diagram of the LP 11 UPS, utility failure
OPM_LPE_11X_3K0_10K_1GB_V041 6GE DE LP 11 UPS: User manual 4.1 (GB)

3.4 Automatic Bypass Switch
If the output converter is unable to deliver the demanded output power because of overload or overtemperature,
the automatic bypass switch will automatically transfer the load to the utility. When the situation is corrected the
UPS will switch back to normal operation, i.e. the load is transferred back to the output converter. Though the
automatic bypass switch is shown as a simple mechanical switch in figures 2-5, the transfers are done by
means of thyristors, i.e. electronically, without any interruption of the power supplied to the load.
In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to
protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the
software in order to protect the UPS and connected equipment.
TO LOAD
AUTOMATIC
BYPASS
SWITCH
FRONT
PANEL
1-PHASE
MAINS INPUT
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 4. Bypass operation: automatic bypass
If a power failure occurs during bypass operation, load power is lost. If the UPS functions under overload
conditions it may not be able to protect the load.
3.5 Manual Bypass Switch (Service switch)
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-
position switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly
connected to the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is
possible without interruption of the power supplied to the load.
CAUTION: REFER SERVICE TO QUALIFIED PERSONNEL ONLY.
TO LOAD
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
AUTOMATIC
BYPASS
SWITCH
FRONT
PANEL
1-PHASE
MAINS INPUT
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 5. Bypass operation: manual bypass
OPM_LPE_11X_3K0_10K_1GB_V041 7GE DE LP 11 UPS: User manual 4.1 (GB)

4 - Installation
4.1 Transport
NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading
capacity. Move the UPS in its original package to the final destination room. Do not stack other
package on top.
4.2 Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to
the pallet. Remove the UPS from the pallet.
BE CAREFUL! Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS
from the pallet! Never try to lift the unit by yourself!
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate
measures to avoid damage on vulnerable floors.
4.3 Package Contents
The shipping box contains a LP 11 UPS, a CD-ROM, an RS232 cable, cable clamps, a safety guide and this
manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture, right option slot at
the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator. Inspect the
UPS for damage after unpacking. If any damage is present please notify the carrier and place of purchase
immediately.
4.4 Location
Please refer to sections 1.2 and 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.5 Installation
IMPORTANT:
Before making any connection and switching on the LP UPS, please check the following conditions:
- the voltage and frequency of your utility supply is 220/230/240 Vac and 50/(60) Hz; off-factory the output
of the UPS is set to 230 Vac / 50 Hz,
- the branch circuit supply is protected as follows:
UPS model branch protection
LP 3kVA 16A slow
LP 5/6kVA 25A slow
LP 8kVA 50A slow
LP 10kVA 50A slow
Table 1. external input fuse value
CAUTION: To reduce risk of fire, connect the UPS only to a circuit provided with the fuse
values according to Table 1 above.
- Ensure that the total power requirement of the equipment to be protected does not exceed the rated
output power of the UPS (output power for your unit is indicated on the rating label on the rear panel).
-The UPS must be grounded when in use: Connect the UPS to a single phase, three wire AC source
equipped with an earth connection.
The following sections describe the installation of the LP 11 UPS.
LP 3/5/6-11 UPS: 4.5.1 and 4.5.2
LP 8/10-11 UPS: 4.5.3 and 4.5.4
LP 11 UPS, general: 4.5.5
OPM_LPE_11X_3K0_10K_1GB_V041 8GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.1 LP 3/5/6-11: standard installation procedure
If a battery extension pack is to be installed, please proceed with section 4.5.2.
If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.5.5.
The numbers between (brackets) refer to figure 12 in section 5.1.
BATTERY
DISCONNECTED
EMERGENCY
SHUTDOWN
stand-alone
and RPA card
available
see 4.5.5 / 7.3
see 6.3-4
10
9
87
6
54
3
2
1
1. Make sure that all circuit breakers (7-8-9) are in ‘off’
position (down).
2. Loosen the 3 screws and remove the metal cover (11)
of the I/O terminals.
3. Lead the input/output cables through the swivels of
the metal cover (11).
4. Input (11a). Connect the mains supply wires to the
terminals 2 (Line) and 3 (Neutral) and the ground wire
to terminal 1. Ground connection is essential!
5. Output (11b). Connect the load wires to the terminals
4 (Line) and 5 (Neutral) and the ground wire to
terminal 6. Ground connection is essential!
6. Re-install the metal cover (11). Fasten the cables in the
swivels. Insert the battery fuse in the fuse holder (17)
and close the fuse holder.
7. An emergency shutdown switch can be connected to
connector J3 on the RS232/Contact Interface Card,
between pins 3 and 4. See section 6.2 for more
information.
8. For advanced communication possibilities, the
RS232/contact interface port (12a) can be connected
to a computer system. See section 6.1 for more
information. *
9. The middle ‘option slot’ (13) allows easy installation of
plug-in cards: SNMP Card or Relay Card. See
sections 6.3 and 6.4 for more information. *
10. The right ‘option slot’ (14) allows easy installation of
the RPA-card (Redundant Parallel Architecture). If the
card is already mounted, and if the unit is intended to
be used stand-alone, a bus terminator (delivered with
the unit) has to be placed in one of the two bus
connectors on the card. If the unit will be part of a
parallel system, see sections 4.5.5 and 7.3 for more
information. *
* The data cables can be attached to the cabinet with
tie-wraps, position the tie-wraps in the small holes
(18) underneath the option slots.
11. Connect the utility power to the UPS.
Figure 6. LP 3/5/6
-
11
:
Standard installation procedure 12. For a quick start proceed with section 5.2 ‘Start-up’.
OPM_LPE_11X_3K0_10K_1GB_V041 9GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.2 LP 3/5/6-11: installation of GE Digital Energy™ LP battery extension pack(s)
The numbers between (brackets) refer to figures 12-13 in section 5.1.
Battery extension pack(s) are shipped with all materials
necessary to connect them to the UPS. The pack(s) can
be connected to the DC connector (15) at the rear panel of
the UPS. We recommend to switch off the UPS before
proceeding: be sure that the UPS can be switched off
without causing damage to the load, and turn all circuit
breakers (7-8-9) into ‘off’ position (down).
5
4
3
2
1
1. Open the fuse holders at the rear panel of the UPS
(17) and battery pack (18) and make sure that the
fuses have been removed.
2. UPS rear panel: loosen the 4 screws that hold the
cover of the DC connector (15), and open the cover.
The actual DC socket is fixed to the inner side of the
cover.
CAUTION! The battery voltage is 240Vdc
and is NOT isolated from the mains.
3. Break out a part of the cover: a large part (grey in fig.
7) if your battery extension pack is equipped with a
swivel (19, fig. 13a), otherwise a small part. If
applicable, mount the swivel in the cover.
4. Connect the DC connector of the battery pack (15a)
to the DC socket of the UPS (15). You will hear a click
when the cable is properly installed.
5. If applicable lead the DC cable through the hole on
the left side of the cover. Re-install the cover. Fasten
it with 4 screws.
6. In case of 14Ah battery packs: using the DC
connector of the battery pack (15) you can install a
second, third, etc. pack. 7Ah battery packs cannot be
connected in series.
7. Insert the battery fuse of the UPS (17). Insert the 2
(7Ah) or 4 (14Ah) fuses of the (each) battery pack
(18). Close the fuse holders (17, 18).
8. In order to calculate the available back-up time related
to the actual load, information on the capacity of the
battery set is stored in the UPS. As the total battery
capacity changes when battery extension packs are
installed, the battery capacity must be re-
programmed. See 5.3.4.
In case of a custom-built battery extension set you may
want to install a ‘battery disconnected’ alarm device.
9. Be sure that the UPS is switched off, and
disassemble the RS232/Contact Interface Card (12)
from the unit. If the card is disassembled during
normal operation the UPS will shut down!
Remove the wire from connector J3 (pin 1 and 2).
Install the wiring of a normally closed contact (e.g. an
auxiliary contact of an MCB) to pin 1 and 2. Re-install
the interface card. If the contact is opened, the UPS
will generate an ‘EXTERNAL BATTERY FUSE
FAILURE’. See 5.3.2 for more information.
Figure 7. LP 3/5/6-11:
Installation of battery pack
Proceed with 4.5.1 or 5.2.
OPM_LPE_11X_3K0_10K_1GB_V041 10 GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.3 LP 8/10-11: standard installation procedure
If a battery extension pack is to be installed, please proceed with section 4.5.4.
If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.5.5.
The numbers between (brackets) refer to figure 12 in section 5.1.
BATTERY
DISCONNECTED
EMERGENCY
SHUTDOWN
stand-alone
and RPA card
available
see 4.5.5 / 7.3
see 6.3-4
10
9
87
6
5
43
2
1
1. Make sure that all circuit breakers (7-8-9) are in ‘off’
position (down).
2. Loosen the 5 screws and remove the metal plate (11)
that covers the I/O terminals.
3. Input (11a). Connect the mains supply wires to the
terminals 2 (Line) and 3 (Neutral) and the ground wire
to terminal 1. Ground connection is essential!
4. Output (11b). Connect the load wires to the terminals
5 (Line) and 6 (Neutral) and the ground wire to
terminal 4. Ground connection is essential!
5. Use the clamps that came with the unit to attach the
wires to the rear of the cabinet. Position the clamps in
the slots (16).
6. Re-install the metal cover plate (11). Insert the 2
battery fuses in the fuse holder (17) and close the
fuse holder.
7. An emergency shutdown switch can be connected to
connector J3 on the RS232/Contact Interface Card,
between pins 3 and 4. See section 6.2 for more
information.
8. For advanced communication possibilities, the
RS232/contact interface port (12a) can be connected
to a computer system. See section 6.1 for more
information.*
9. The middle ‘option slot’ (13) allows easy installation of
plug-in cards: SNMP Card or Relay Card. See
sections 6.3 and 6.4 for more information.*
10. The right ‘option slot’ (14) allows easy installation of
the RPA-card (Redundant Parallel Architecture). If the
card is already mounted, and if the unit is intended to
be used stand-alone, a bus terminator (delivered with
the unit) has to be placed in one of the two bus
connectors on the card. If the unit will be part of a
parallel system, see sections 4.5.5 and 7.3 for more
information.*
* The data cables can be attached to the cabinet with
tie-wraps, position the tie-wraps in the small holes
(18) underneath the option slots.
11. Connect the utility power to the UPS.
12. For a quick start proceed with section 5.2 ‘Start-up’.
Figure 8. LP 8/10
-
11
:
Standard installation procedure
OPM_LPE_11X_3K0_10K_1GB_V041 11 GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.4 LP 8/10-11: installation of GE Digital Energy™ LP battery extension pack(s)
The numbers between (brackets) refer to figures 12-13 in section 5.1.
Battery extension pack(s) are shipped with all materials necessary to connect them to the UPS. The pack(s)
can be connected to the DC connector (15) at the rear panel of the UPS. We recommend to switch off the UPS
before proceeding: be sure that the UPS can be switched off without causing damage to the load, and turn all
circuit breakers (7-8-9) into ‘off’ position (down).
1. Open the fuse holders at the rear panel of the UPS
(17) and battery pack (18) and make sure that the
fuses have been removed.
5
4
3
2
1
2. UPS rear panel: loosen the 5 screws that hold the
cover of the DC connector (15), and open the cover.
CAUTION! The battery voltage is 240Vdc
and is NOT isolated from the mains.
3. Connect the DC connector of the battery pack (15a)
to the DC socket of the UPS (15). You will hear a click
when the cable is properly installed.
4. Lead the DC cable through the slot in the cover
(bottom-left) and re-install the cover. Fasten it with 5
screws.
5. Use the clamps that came with the unit to attach the
DC cable to the rear of the cabinet. Position the clamp
in the slots (16).
6. In case of 14Ah battery packs: using the DC
connector of the battery pack (15) you can install a
second, third, etc. pack. 7Ah battery packs cannot be
connected in series.
7. Insert the 2 battery fuses of the UPS (17). Insert the 2
(7Ah) or 4 (14Ah) fuses of the (each) battery pack
(18). Close the fuse holders (17, 18).
8. In order to calculate the available back-up time related
to the actual load, information on the capacity of the
battery set is stored in the UPS. As the total battery
capacity changes when battery extension packs are
installed, the battery capacity must be re-
programmed. See 5.3.4.
In case of a custom-built battery extension set you may
want to install a ‘battery disconnected’ alarm device.
9. Be sure that the UPS is switched off, and
disassemble the RS232/Contact Interface Card (12)
from the unit. If the card is disassembled during
normal operation the UPS will shut down!
Remove the wire from connector J3 (pin 1 and 2).
Install the wiring of a normally closed contact (e.g. an
auxiliary contact of an MCB) to pin 1 and 2. Re-install
the interface card. If the contact is opened, the UPS
will generate an ‘EXTERNAL BATTERY FUSE
FAILURE’. See 5.3.2 for more information.
Proceed with 4.5.3 or 5.2.
Figure 9. LP 8/10-11:
Installation of battery pack
OPM_LPE_11X_3K0_10K_1GB_V041 12 GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.5 LP-11 series: 2 / 3 / 4 parallel operating units – additional info
The RPA option (Redundant Parallel Architecture) allows you to create a redundant UPS system in which 2, 3
or 4 LP units operate in parallel. The following should be considered when installing units in parallel.
This section gives additional information on:
- installation (4.5.5.1)
- start-up (4.5.5.2)
- use / maintenance (4.5.5.3)
4.5.5.1 Notes concerning installation of a parallel system
1. All inputs of the UPSs must be supplied from the same phase. This is to enable bypass operation of the
parallel system. All inputs must be individually protected by fuses in the installation. The values of these
fuses should correspond to the values mentioned in section 4.5 table 1.
2. All outputs must be connected together, supplying the load. It is advised to install switches (S 1-4,
fig. 10) in the output wiring, in order to be able to isolate a unit from the remaining system for service and
maintenance purposes. It is advised to make a Neutral-to-Ground bounding in the output junction.
3. The diameter of input and output cables must be according to the table in the installation drawings (see
appendix). Cables with different diameters can cause tripping fuses in the UPS and/or the installation.
4. The length of all input cables from the input junction (Li, fig. 10) to the UPS inputs should be equal.
The same applies to the cables from the outputs to the output junction (Lo, fig. 10). The minimum length of
the input as well as the output cables is 3 meters.
RPA CARD
LP-UP
S
OUT
IN
RPA CARD
LP-UP
S
OUT
IN
RPA CARD
LP-UP
S
OUT
IN
RPA CARD
LP-UP
S
OUT
IN
1-PHASE 3-WIRE INPUT
INPUT JUNCTION
BUS
TERMINATOR
YELLOW NETWORK
CABLES AS DELIVERED
WITH THE UPS
OUTPUT JUNCTION
Li/Lo: LENGTH OF I/O WIRING
- EQUAL FOR EACH UPS
- MINIMUM 3 METERS
S 1-4
SWITCH ALLOWS
ISOLATION OF A UNIT
FROM THE SYSTEM
BUS
TERMINATOR
F 1-4
DISTRIBUTION
FUSE VALUES
A
CCORDING TO
TABLE 1
TO LOAD
Figure 10. Installation of parallel operating LP 11 UPSs
OPM_LPE_11X_3K0_10K_1GB_V041 13 GE DE LP 11 UPS: User manual 4.1 (GB)

5. The right option slot (14) at the rear of the unit contains the RPA-card. Before the parallel system
can be put into operation a unique number has to be appointed to each UPS in the system. This can be 0, 1,
2 or 3. Start with 0 for the first unit, 1 for the second, 2 for the third and 3 for the last unit:
- loosen the screws, remove the RPA-card
- set the dipswitch to the appointed number (fig. 11)
- re-install the RPA-card, fasten the screws.
Do NOT install the network cables between the RPA-cards of the units yet!
Figure 11. Appointing a unique
number to each UPS in the system
6. In the UPS many parameters can be set. It is advised to keep the same setting for each parameter
in each UPS in the parallel system. In any case the following parameters are critical and should have equal
settings:
- auto-restart (on/off, see 5.3.3)
- output voltage (220/230/240 Vac, see 5.3.4)
- output frequency (50/60 Hz, see 5.3.4)
It is absolutely required that these parameters are set to the same value. Off factory this is the case. If
you’re not sure that the units have equal settings:
- be sure that the RPA-cards of the units have not been interconnected yet
- be sure that utility power is connected to the UPS
- start each unit individually (see 5.2), check / change the parameters, and switch the unit off again.
7. Interconnect the RPA-cards of the units, using the network cable that came with the UPS. See figure
10 (dotted line). Only use the cables that were delivered with the UPSs! Of the first and the last UPS in the
system only one RPA-socket is used to interconnect the UPSs. A bus terminator must be placed in the other
(free) RPA-socket. The required bus terminators have been delivered with the unit.
4.5.5.2 Notes concerning starting up the parallel system
For starting up the system please refer to section 5.2.
After switching on all units the LP UPSs will show the following display:
AUTORESTART OFF
PRESS ENTER
After pressing on the enter button on one of the units the system will start up. All units will display the standard
screen. The number in the lower right corner indicates the number of the UPS in the system.
LP 5-11
LOAD 40% 2
If the parameters mentioned in 4.5.5.1 step 6 are not set to the same value the UPS will display the following
screen after start-up:
AUTORESTART OFF
SETTING MISMATCH
In this case check and correct the setting of the parameters as mentioned in 4.5.5.1, step 6.
OPM_LPE_11X_3K0_10K_1GB_V041 14 GE DE LP 11 UPS: User manual 4.1 (GB)

4.5.5.3 Notes concerning use / maintenance of a parallel system
ECO-mode:
If LP units operate in parallel, the ECO-mode feature is not available. See also 5.5.5.
No-load shutdown:
If LP units operate in parallel, the no-load shutdown function is not available.
Manual bypass:
If you want to switch one of the UPSs to bypass operation using the manual bypass switch (switch
is turned into position 2) then all UPSs in the parallel system have to be switched to bypass
operation in order to prevent damage.
Maintenance:
To isolate a unit from the redundant system:
1. Switch off the UPS which has to be isolated,
2. Remove the installation fuse from the input of that UPS (F1-4 in figure 10),
3. Separate the output of the UPS from the output junction (S1-4 in figure 10).
To re-enter the unit into the system:
1. Reinstall the installation input fuse,
2. Connect the output of the UPS to the output junction,
3. Switch on the UPS.
OPM_LPE_11X_3K0_10K_1GB_V041 15 GE DE LP 11 UPS: User manual 4.1 (GB)

5 - Operation
5.1 Description of Front and Rear Panel
1 LCD screen
12a
98717
11b
12
13
14
18
16
11
15
11a
10
11a
11b
10
11
8 97
18
12a
14
13
12
15
17
4 32156 2x16 characters, shows UPS system data, status
messages, settings.
The language is selectable: English, German, French,
Italian, Spanish. Section 5.3.4 describes the selection
procedure.
2-4 Push-buttons
With the button keypads ‘Down’ (2) and ‘Up’ (4) you can
scroll through the several screens, with keypad 'Enter/Reset'
(3) a selection is confirmed. Keypad activity is accompanied
by a short beep. If there is no keypad activity during 20
seconds the LCD screen will return to the default screen
(except for the service screens, see section 5.3.3).
5 LED 'operation' indicates normal operation.
6 LED ‘alarm’, indicates an alarm situation, accompanied by
alarm message(s) on the display and a sounding buzzer.
See section 5.3.2 for more information.
7 Switch ‘UPS on/off’, turns on/off the complete UPS, including
the bypass!
8 MCB ‘Mains on/off’, protection fuse for mains input and
battery charger.
9 MCB ‘Bypass on/off’, fuse to protect the system in case of
severe overload or short circuit in the UPS load.
10 Manual Bypass Switch: 1 = Load on UPS
2 = Load on mains
CAUTION: In position 2, if the input line is
energized, the output is also live regardless the
position of the MCBs ‘mains’ and ‘bypass’.
11 Cover of the I/O terminals, behind it:
11A Input terminals
1 = Ground, 2 = Line, 3 = Neutral
11B Output terminals
3/5/6kVA: 4 = Line, 5 = Neutral, 6 = Ground
8/10kVA: 4 = Ground, 5 = Line, 6 = Neutral
12 RS232/Contact Interface Card, with:
12a - RS232 Interface Port (see section 6.1)
- Emergency shutdown (see 4.5.1 / 4.5.3 and 6.2)
- Battery disconnected, pin 1-2 (can be used for
external signalling).
13 Free option slot for plug-in cards:
- Relay Card (see 6.3)
- SNMP Card (see 6.4)
14 Option slot for RPA Card (Redundant Parallel Architecture).
See 4.5.5 and 7.3.
15 DC socket / connector.
16 Slots to fasten cable clamps.
17 Battery fuse holder.
Figure 12. Front and rear panel
top: LP 3/5/6-11
bottom: LP 8/10-11
18 Holes to fasten data cables.
OPM_LPE_11X_3K0_10K_1GB_V041 16 GE DE LP 11 UPS: User manual 4.1 (GB)

16
15a
18
15
Rear panel of (optional) battery extension pack:
15 DC socket (14Ah only).
15a DC connector
16 Slots to fasten cable clamps.
18 Battery fuse holder(s)
7Ah: 2 fuses
14Ah: 4 fuses
OPM_LPE_11X_3K0_10K_1GB_V041 17 GE DE LP 11 UPS: User manual 4.1 (GB)
Figure 13. Rear panel battery
extension pack (optional)
19
15a
18
15
Rear panel of (optional) battery extension pack,
equipped with swivel:
15 DC socket (14Ah only)
15a DC connector
18 Battery fuse holder(s)
7Ah: 2 fuses
14Ah: 4 fuses
19 Swivel to fasten cable in terminal cover of UPS
Figure 13a. Rear panel battery
extension pack (optional)
equipped with swivel

5.2 Start-up
The numbers between (brackets) refer to figure 12 in section 5.1.
Note: the UPS can be started on battery power if the mains input voltage is not available or if MCB
‘mains’ is in off-position: simply skip step 1. To prevent accidental discharging of the batteries, it is
however recommended to proceed with step 1 and start the unit only when the mains input voltage is
available.
1. Turn MCB 'mains' (8) and MCB 'static bypass' (9), both on the rear panel, into position ‘on’ (up).
2. Some UPS parameters (e.g. voltage, frequency, LCD language) are user selectable. If you want to
change one or more settings, please refer to section 5.3.4 ‘Set-up Menu’ now. Changing the settings
later is possible, however only after switching off the unit.
3. Turn switch 'UPS on/off' (rear panel, 7) into position ‘on’ (up).
The green LED 'operation' (front panel, 5) will illuminate.
After switching on the UPS performs a self-test and the display (front panel, 1) will show:
SELFTEST
IN PROGRESS
After completion of the self-test the output voltage of the UPS is available and the unit is ready for use.
The display will show the default screen: model and actual load (values are examples)
LP 5-11
LOAD 37%
In case of a system failure the self-test results in a failure message; this message is displayed for 30
seconds before the self-test is repeated automatically. If the faulty situation persists, switch off the UPS
and contact your dealer. See chapter 9 for more information.
4. Though the batteries (the internal energy reserve) were fully charged when the UPS left the factory,
they might have lost some energy during transport and/or storage. It is recommended to allow the UPS to
recharge the batteries for a few hours. This way you ensure that the UPS can provide sufficient runtime in
case of a mains power failure.
5. If not yet switched on, the equipment connected to the UPS can be switched on now; operate as usual.
OPM_LPE_11X_3K0_10K_1GB_V041 18 GE DE LP 11 UPS: User manual 4.1 (GB)

5.3 Use
Once the unit is in operation, there is no need to switch the unit on/off during use.
If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7)
results in a total absence of the output voltage (also the bypass voltage) of at least 5 seconds.
If an emergency shutdown switch has been installed (see 4.5.1 or 4.5.3, step 7) the UPS will stop immediately
when the switch is opened. Restart is only possible after closing the switch and turning the UPS off and on
again with the UPS on/off switch (rear panel, 7).
The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore
the UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.
The menus on the display can be divided into 5 groups:
1 standard screen
2 information menu (5.3.1)
3 status- and alarm menu (5.3.2)
4 service menu (5.3.3)
5 set-up menu (5.3.4)
The standard menu shows UPS model and actual load.
LP 5-11
LOAD 37%
5.3.1 Information menu
When the default screen is displayed the first information screen can be entered by pressing the ‘Up’ key (front
panel, 4). Using the ‘Up’ and ‘Down’ keys (front panel, 4 and 2) you can scroll through several information
screens. After the last information screen the default screen will appear.
The screens display the following information:
Mains voltage and utility frequency, and the power delivered by the mains.
INPUT LINE 226V
2.45kW 50Hz
Output voltages and output frequency, and the power delivered by the UPS
(as % of the nominal UPS rating).
OUTPUT 230V
LOAD 50% 50.0Hz
The temperature near the batteries, the battery voltage and the battery
current (charging: + value, discharging: - value).
BATTERY 23°C
271V 1.9A
The remaining battery runtime (or autonomy) during a mains failure.
AUTONOMY TIME
LEFT 10:30
OPERATING TIME
0YEAR 29DAYS The total operating time of the UPS.
OPM_LPE_11X_3K0_10K_1GB_V041 19 GE DE LP 11 UPS: User manual 4.1 (GB)
Other manuals for Digital Energy LP 11
1
Table of contents
Other GE UPS manuals

GE
GE 1000 VA User manual

GE
GE 750 UL S2 User manual

GE
GE 225 User manual

GE
GE TLE series 600 User manual

GE
GE Match lite 500 User manual

GE
GE Digital Energy LP 33 Series User manual

GE
GE GT6000 User manual

GE
GE Digital Energy LP 11U Instruction Manual

GE
GE Digital Energy GT Series User manual

GE
GE Amersham Imager 600 User manual
Popular UPS manuals by other brands

SynQor
SynQor UPS-1250-270 Series Operator's guide

Marathon
Marathon SuperCap 1000VA user manual

Ever
Ever EASYLINE AVR USB instruction manual

Elektro-Automatik
Elektro-Automatik Guard LCD 2 Series manual

CyberPower
CyberPower AVR Series user manual

Liebert
Liebert Series 300 Installation, operaton & maintenance manual