gefran 40T 72 User manual

40T 72
CONFIGURABLE INDICATOR
Main applications
•Thermostat
•Humidity switch
•Mould cooling units
•Industrial refrigerators
•Air conditioning
•Food processing equipment
Main features
•Faceplate configurable input
•Protected by a personal code
•Configurable by a serial link
•Transmitter power supply incorporated
•Custom thermocouple linearisation
available
•Internal linearisation for engineering
units
•Labels provided for the more common
physical units
•Sampling time and trip intervention
programmable between 15 and
120msec with resolution between
2000 and 8000 steps
•Retransmission of the measured
variable signal
•3 trip points, completely configurable
from the faceplate
GENERAL
Microprocessor based indicator in 72x36
format manufactured with SMT.
The instruments have a lexan membrane
faceplate (guaranteed to IP65) which has
3 keys, a 2, 3 / 4 digit display.
The input signal can be selected from a
wide range of sensors:
• Thermocouples of type J, K, R, S, T, B,
E, N, L GOST, U, G, D, C
• Resistance thermometers Pt100,
Pt100J (japanese standard) 2 / 3 wire
• PTC and NTC themistors
• Linear inputs 0 to 60/12 to 60mV,
0 to 20/4 to 20mA,
0 to 10/2 to 10/0 to 5/1 to 5/0 to 1/0,
2 to1V
The selection is made using the faceplate
keys and correct input contact.
No external shunt or adapter is required.
A digital input (24Vdc/4mA) is available
for resetting, hold, flash, peak handling or
releasing latch. The instruments have a
maximum of 3 outputs that can be
mechanical relays (5A/250V) or logic
outputs (0 to 11Vdc). In alternative to
output 3 a 4 to 20mA output is available
(max. 150Ω) for retransmission of the
measured input signal, or a digital input
(24Vdc/4mA) can be provided which can
be used for resetting, hold, flash, peak
handling or releasing latch.
Finally, a triac can be fitted (as an
alternative to the other two relay outputs)
that can drive resistive loads up to a
maximum of 2,5A at 220V.
The programming of the instrument is
made easy by grouping the parameters in
function blocks (CFG for the alarm
hysteresis, Inp for the inputs, Out for the
outputs...) and by a simplified data entry
menu.
The configuration can be simplified even
further using the PC programming kit
made up of a connection cable and a
menu guide program that runs under
Windows (see data sheet cod.
WINSTRUM).
A configurable personal software
protection code (password protection)
can be used to restrict the levels of
editing and displaying the configuration
parameters.
TECHNICAL DATA
INPUTS
Accuracy 0,2% f.s. ±1digit.
Sampling time 120msec for temperature
sensors, configurable for linear inputs
down to a minimum of 15msec with
reduction of the resolution to 2000 steps.
Configurable decimal point position for
linear inputs, for TC, RTD, PTC and NTC
inputs, only one decimal digit is allowed
in the maximum display range of
-199.9 to 999.9 (4 digit display),
-99.9 to 99.9 (3 digit display with sign),
-9.9 to 9.9 (2 digit display with sign) with
indication of open circuit thermocouple or
RTD, PTC or NTC in open or short circuit,
indication of over- and under-range for
linear inputs.
TC - Thermocouple
Automatic cold junction compensation
(4 digit)
J0 to 1000°C / 32 to 1832°F
K0 to 1300°C / 32 to 2372°F
R0 to 1750°C / 32 to 3182°F
S0 to 1750°C / 32 to 3182°F
T-200 to 400°C / -328 to 752°F
B44 to 1800°C / 111 to 3272°F
E-100 to 750°C / -148 to 1382°F
N0 to 1300°C / 32 to 2372°F
L-GOST 0 to 600°C / 32 to 1112°F
U-200 to 400°C / -328 to 752°F
A - PV display: indication of process variable
B - Label for engineering units
C - “Function” key
D - “Raise” and “Lower” keys
E - Indication of the states of the outputs
Red LED display
IP65 faceplate protection
FACEPLATE DESCRIPTION
G0 to 2300°C / 32 to 4172°F
D0 to 2300°C / 32 to 4172°F
C0 to 2300°C / 32 to 4172°F
custom -1999 to 9999
TC - Thermocouple
(3 digit + sign)
J0 to 999°C / 32 to 999°F
K0 to 999°C / 32 to 999°F
R0 to 999°C / 32 to 999°F
S0 to 999°C / 32 to 999°F
T-200 to 400°C / -328 to 752°F
Bnot available
E-100 to 750°C / -148 to 999°F
N0 to 999°C / 32 to 999°F
L-GOST 0 to 600°C / 32 to 999°F
U-200 to 400°C / -328 to 752°F
G0 to 999°C / 32 to 999°F
D0 to 999°C / 32 to 999°F
C0 to 999°C / 32 to 999°F
custom -999 to 999
(2 digit + sign)
J0 to 99°C / 32 to 99°F
K0 to 99°C / 32 to 99°F
R0 to 99°C / 32 to 99°F
S0 to 99°C / 32 to 99°F
T-99 to 99°C / -99 to 99°F
Bnot available
Enot available
Nnot available
L-GOST 0 to 99°C / 32 to 99°F
U-99 to 99°C / -99 to 99°F
Gnot available
Dnot available
Cnot available
custom -99 to 99
RTD (2 or 3 wire)
(4 digit)
PT100 -200 to 600°C / -328 to 1112°F
JPT100 -200 to 600°C / -328 to 1112°F
(3 digit + sign)
PT100 -200 to 600°C / -328 to 999°F
JPT100 -200 to 600°C / -328 to 999°F
(2 digit + sign)
PT100 -99 to 99°C / -99 to 99°F
JPT100 -99 to 99°C / -99 to 99°F
PTC
990Ω, 25°C
(4 digit and 3 digit + sign)
-55 to 120°C / -67 to 248°F
(2 digit + sign)
-55 to 99°C / -67 to 99°F
NTC
1KΩ, 25°C
(4 digit and 3 digit + sign)
-10 to 70°C / 14 to 158°F
(2 digit + sign)
-10 to 70°C / 14 to 99°F
DC - Linear
With scale configurable within the limits:
-1999 to 9999 (4 digit),
-999 to 999 (3 digit + sign)
-99 to 99 (2 digit + sign)
0 to 60mV / 12 to 60mV
0 to 10V / 2 to 10V
0 to 5V / 1 to 5V
0 to 1V / 0,2 to 1V
0 to 20mA / 4 to 20mA
Input impedance for voltage signals
Ri > 500KΩ, for current signals Ri = 50Ω.
32-segment configurable linearisation can
be used.
Potentiometer
Supply 1V >100Ω
Digital input
Ri = 5,6KΩ(24V, 4mA) isolated to 1500V
Function is configurable as alarm or
memory reset, hold, flash zero, display of
the peak value (max., min. or peak to
peak).
OUTPUTS
Relay
with NO (NC) contacts rated at 5A, 250V
at cosϕ= 1.
Logic (only for Out1 and Out2)
Output, type D 11Vdc, Rout = 220Ω
(6V/20mA).
Triac (for Out1, disabled Out2)
24 to 240Vac ±10%, 2A max
Snubberless, I2t = 128A2sec
A maximum of three trip points can be set
as absolute, deviation or symmetrical
deviation alarms.
The hysteresis of each alarm is
configurable individually.
Alarm masking with exclusion on power
up, with memory, delay and minimum
intervention time.
The trip point may be set at any point on
the scale.
Analogue retransmission
4 to 20mA on max. 60Ω
POWER SUPPLY
11...27Vdc, 18...27Vac ± 10%
50/60Hz, max. 4,5VA
TRANSMITTER POWER SUPPLY
2 wire, 18Vdc ±10%, max. 50mA
1,2Vdc for potentiometer >100Ω
(non isolated from sensor input)
AMBIENT CONDITIONS
Working temperature range: 0 to 50°C
Storage temperature range: -20 to 70°C
Humidity: 20 to 85%Ur non-condensing
WEIGHT
110g. in the complete version
A
B
C
D
E
CONNECTION DIAGRAM
DIMENSIONS and CUT-OUT
76
36
54
8
30
69,5
43
83
72
Dimensions: 72x36mm depth 54mm
PWR
SUPPLY
TC
Pt100
3-wires
NTC/PTC
Pt100
2-wires
LIN INP
LIN INP
TX 2-wires LIN INP
Vdc
4...20mA
LINE
OUT1
(TRIAC)
OUT2
OUT1
OUT3
DIGITAL
INPUT
ANALOG
OUTPUT
!For a correct installation see the warnings in the users’ manual
44
POWER SUPPLY
11...27Vdc, 18...27Vac not isolated9
NR. DIGITS
2 + sign 2
3 + sign 3
DIGITAL INPUT / RETRANSMISSION OUTPUT /
OUTPUT 3
None0 0 Digital input
Analogue output 4 to 20mA on max 60Ω
0 1
0 2 RelayR 0
None 0 0
OUTPUT 1, OUTPUT 2
Relay, RelayR R Relay, Logic
Triac, None
R D
T0
TRANSMITTER POWER SUPPLY
ORDER CODE
GEFRAN spa reserves the right to make any modification of the design or function, at any moment without prior notice
40T 72 9
The instrument conforms to the European Directives 2004/108/CE and 2006/95/CE with reference to the generic standards:
EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission in residential environment) EN 61010-1 (safety)
For T input (alternative to RTD, PTC, NTC)
18Vdc, 50mA
for 2-wire transmitter 2 4
1,2Vdc for potentiometer * 0 1
* R77 version for potentiometer input
(Rinput >10Mohm
DTS_40T 72_0509_ENG

Other gefran Measuring Instrument manuals

gefran KH-SIL2 Series User manual

gefran

gefran KH-SIL2 Series User manual

gefran SENSORMATE QE2008-W SET User manual

gefran

gefran SENSORMATE QE2008-W SET User manual

gefran 40A 48 User manual

gefran

gefran 40A 48 User manual

gefran 40F 96 User manual

gefran

gefran 40F 96 User manual

gefran 4A 48 User manual

gefran

gefran 4A 48 User manual

gefran 2308 User manual

gefran

gefran 2308 User manual

gefran QE1008-W SET User manual

gefran

gefran QE1008-W SET User manual

gefran KS Series User manual

gefran

gefran KS Series User manual

gefran 40B 48 User manual

gefran

gefran 40B 48 User manual

gefran 4T72 User manual

gefran

gefran 4T72 User manual

gefran 650 L Quick guide

gefran

gefran 650 L Quick guide

Popular Measuring Instrument manuals by other brands

Starrett 799A Series instruction manual

Starrett

Starrett 799A Series instruction manual

Agilent Technologies 86082A user guide

Agilent Technologies

Agilent Technologies 86082A user guide

SICK SIM1012 operating instructions

SICK

SICK SIM1012 operating instructions

Trotec B1DL Original instructions

Trotec

Trotec B1DL Original instructions

HoldPeak 870MR Operation manual

HoldPeak

HoldPeak 870MR Operation manual

HP 1652B Getting started

HP

HP 1652B Getting started

Gait up Physilog 4 User manual and specifications

Gait up

Gait up Physilog 4 User manual and specifications

AEMT TIME MARK 2732 manual

AEMT

AEMT TIME MARK 2732 manual

Riken Keiki SF6 Series operating manual

Riken Keiki

Riken Keiki SF6 Series operating manual

Midcontinent MD23-104 user guide

Midcontinent

Midcontinent MD23-104 user guide

Dickey-John GAC500XT manual

Dickey-John

Dickey-John GAC500XT manual

BioDrop 80-3006-20 quick start guide

BioDrop

BioDrop 80-3006-20 quick start guide

Avisoft UltraSoundGate 116Hnb user guide

Avisoft

Avisoft UltraSoundGate 116Hnb user guide

LaMotte 2020 instruction manual

LaMotte

LaMotte 2020 instruction manual

EXFO IQ-5320 instruction manual

EXFO

EXFO IQ-5320 instruction manual

TRANSMIC V1R1C0 quick start guide

TRANSMIC

TRANSMIC V1R1C0 quick start guide

Triplett EG480 user manual

Triplett

Triplett EG480 user manual

UE Systems ULTRAPROBE 10000 instruction manual

UE Systems

UE Systems ULTRAPROBE 10000 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.