manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Gems Sensors & Controls
  6. •
  7. Control Unit
  8. •
  9. Gems Sensors & Controls Warrick 26M Series Owner's manual

Gems Sensors & Controls Warrick 26M Series Owner's manual

Form 261
Bulletin P/N 100204-1
Rev. K
This bulletin should be used by e perienced personnel as a guide to the installation of the Series 26M Control. Selection
or installation of equipment should always be accompanied by competent technical assistance. We encourage you to
contact Gems Sensors or a representative if further information is required.
Installation
1. Install octal socket in appropriate enclosure
using two #6 or #8 screws.
2. Install rail mount socket on appropriate rail
(DIN mount) in appropriate enclosure if appli-
cable.
3. Wire control per wiring diagram following
N.E.C and local codes.
4. Install control module in socket.
Warrick
®
Series 26M Control
Installation and Operation Bulletin
Specifications
Control Design: Solid-state components enclosed in a clear Le an
plug-in style housing. Not NEMA rated.
Contact Design: 1 SPDT (1 form C), powered contacts
(input Power L1 connected to common of relay contacts)
Contact Ratings: 10A@120/240-VAC resistive (120°F), 1A
@120/240VAC resistive (150°F), 1/3 HP @ 120/240-VAC (120°F).
Contact Life: Mechanical -5 million operations
Electrical -100,000 operations minimum at rated load
Supply Voltage: Factory Configured: 24V, 120V, 220V, or 240V AC
+10%/-15% of nominal, 50/60 Hz. Factory Configured: 208V/240V
Model: 187V Min to 242V Ma , VAC 50/60 Hz
Power Consumption: 24/120/220/240-VAC with both relays ener-
gized
~
4.4 VA.
Secondary Circuit: 2.3 VAC RMS voltage on probes, < 1 milliam-
pere source capability.
Sensitivity: Factory programmed to 4.7K, 10K, 26K, 50K, or 100K
Ohms
Operating Ambient Temperature Range: -40°F to +150°F (-40°C to
+65°C)
Terminals: All connections made with screw-clamp terminals.
Time Delays: Standard LLCO, 0.5 sec. on rising level, 3 sec. on fall-
ing level. Optional 0-90 sec. time delays in 1-sec. increments for
rising and falling.
Listings: Control carries U.L. Limit Control Listing (UL-353) for
24VAC and 120VAC Line Powered units only (220VAC, 240VAC,
208/240VAC units not rated).
SENSITIVITY
CHARACTER
SENSITIVITY
(K-OHMS)
Distance
(FT)
A 4.7 900
B 10 600
C 26 250
D 50 100
E 100 50
∗ Based on type MTW or THHN wire,
#14 or #16 AWG
Sensitivity vs. Ma imum
Probe Wire Distance*
Dimensional Drawing
Torque all terminals and socket mounting screws to 7 in-lb ma .
Mount the octal socket
(base) on rigid vertical
or horizontal surface
using #6 or #8 screws.
The control should be
mounted within an
enclosure of proper
NEMA integrity.
Gems Sensors & Controls | One Cowles Road | Plainville, CT 06062-1198
Telephone: 1-800-378-1600 | Email: [email protected] | www.GemsSensors.com
Operation
26MXXXXX-XX-XX
AUTOMATIC RESET (Reset Switch terminals not wired)
When the liquid rises to the electrode on terminal LLCO, the
control energizes, changing state of the load contacts. (LED
will be lit) The control remains energized until the liquid
level recedes below electrode on terminal LLCO. The con-
trol then de-energizes, (LED will not be lit) returning load
contacts to original state. Unless otherwise specified, there
is a three second time delay on decreasing level. Liquid
must be below probe on terminal LLCO for a full three sec-
onds before control de-energizes.
MANUAL RESET (Normally closed pushbutton installed
across reset terminals) When the liquid rises to the elec-
trode on terminal LLCO, the control will remain de-
energized until the pushbutton is depressed. Upon Reset
Switch activation, the control will energize, (LED will be lit)
changing the state of the contacts. The control remains
energized until the liquid level recedes below electrode on
terminal LLCO. The control then de-energizes, (LED will not
be lit) returning load contacts to their original state. Unless
otherwise specified, there is a three second time delay on
decreasing level. Liquid must be below probe on terminal
LLCO for full three seconds before control de-energizes.
Operator to wait 5 full seconds after power is applied before
pressing reset switch (if manual reset is used).
MANUAL RESET OPTIONAL POWER OUTAGE FEA-
TURE (Normally closed pushbutton across reset terminals)
Control will auto-recover from a power loss. With liquid pre-
sent on LLCO electrode at a power outage event, the con-
trol will de-energize and will automatically re-energize upon
return of power with liquid present on the probe at power-
up. However, if loss of liquid is sensed on power-up, the
control will remain de-energized until liquid again rises to
electrode and pushbutton is depressed. The control will not
attempt to auto-recover from a power outage if no liquid
was present on the probe at power loss.
TEST FEATURE
Allows LLCO circuit to be tested without the need to drop
the water level in the boiler to create a dry probe condition.
Holding down the reset button for 3 seconds will allow the
LLCO circuit to trip, simulating a dry probe. The controller
will return to normal operation once the reset button is
pressed a second time.
LED STATUS INDICATOR In normal operation, the LED
on the control will either be on or off depending on the
controller state. On-board microprocessors continuously
monitor for fault conditions. In the event a fault is detected,
the LED will blink a pattern indicating the fault type. If you
e perience an inoperable control and the LED is blinking,
attempt to leave the control in the blinking state and con-
tact the factory for assistance.
Time Delay Increasing Level: 0-90
seconds, Blank = 0 seconds.
Time Delay Decreasing Level: 0-90
seconds, Blank = 3 seconds.
Optional Character: see Chart
Enclosure: 0-None, 1-NEMA 1, 2-
NEMA 4
Socket Style: A-11 Pin Octal, B-Din
Mount, M-NONE, Module Only
Supply Voltage: 1-120VAC (+10%/
-15%), 2-240VAC (+10%/-15%), 3-
24VAC (+10%/-15%), 5-220VAC
(+10%/-15%), 8-208/240VAC (187
to 242 VAC absolute Range)
Mode/Sensitivity: A-4.7K, B-10K,
C-26K, D-50K, E-100K
N.C.
Pushbutton
Power
Outage
Test
Feature
A X X X
B X
C X
E X
F X X
Y X X
Z X X
0 No Option
Wiring Diagram

Popular Control Unit manuals by other brands

Wetelux 707331 instruction manual

Wetelux

Wetelux 707331 instruction manual

Sonifex CM-TB8 User handbook

Sonifex

Sonifex CM-TB8 User handbook

Quectel MC90-TE-A user guide

Quectel

Quectel MC90-TE-A user guide

Flowserve Valtek Mark Six Installation, operation & maintenance instructions

Flowserve

Flowserve Valtek Mark Six Installation, operation & maintenance instructions

GEA DHV operating instructions

GEA

GEA DHV operating instructions

Mitsubishi Electric MELSEC Q Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC Q Series user manual

Ross Controls CrossCheck CC4 Series Integration guide

Ross Controls

Ross Controls CrossCheck CC4 Series Integration guide

Curtis 1353 user manual

Curtis

Curtis 1353 user manual

ABB FENA-01 Quick installation and start-up guide

ABB

ABB FENA-01 Quick installation and start-up guide

Thitronik Pro-finder Operating and installation instructions

Thitronik

Thitronik Pro-finder Operating and installation instructions

GEM DN 15-50 Installation, operating and maintenance instructions

GEM

GEM DN 15-50 Installation, operating and maintenance instructions

Comelit UT2010 Technical manual

Comelit

Comelit UT2010 Technical manual

SSS Siedle BSG 650-02 manual

SSS Siedle

SSS Siedle BSG 650-02 manual

Gardena smartsystem 19035 Operator's manual

Gardena

Gardena smartsystem 19035 Operator's manual

Federal Signal Corporation TM33 installation instructions

Federal Signal Corporation

Federal Signal Corporation TM33 installation instructions

Frequency Central Waverider VCDO MKii Build documentation

Frequency Central

Frequency Central Waverider VCDO MKii Build documentation

Fibocom L810-MiniPCIe Hardware user manual

Fibocom

Fibocom L810-MiniPCIe Hardware user manual

Norac UC4 Total Control installation manual

Norac

Norac UC4 Total Control installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.