16 - Fine tuning (T2)
It is possible to ne tune the room sensor of the control
panel so the correct current room temperature is displayed.
Setting option: between -5 and 0 °C.
Factory setting: -3 °C.
17 - Timer levels 3 and 4
If automatic reconnection is used for speeds 3 or 4, you
can enter how many hours the system should run on level
3 or 4 before it automatically returns to level 2. The set
point can be congured between 1 and 9 hours.
Setting option: between 1 and 9 hours.
Factory setting: 3 hours.
18 - Filter/stop
To ensure that the lters are changed when the alarm
“Change Filter” ashes on the screen of the control panel,
the set point can be congured to ON. The system will
then stop automatically after 14 days if the lters have not
been changed.
If this precaution is not required, the set point can be con-
gured to OFF and the system will continue to operate.
Setting option: ON/OFF.
Factory setting: OFF.
19 - Method of regulation
There are 3 options:
0. Room regulation (T2 sensor)
1. Supply air regulation (T1 sensor)
2. Extract air regulation (T7 sensor)
If the system is used in a dwelling, supply air regulation is
the normal choice. The set point is congured to 1.
For room regulation, congure the set point to 0.
For extract air regulation, congure the set point to 2.
Setting option: between 0 and 2.
Factory setting: 2.
20 - Preheating
If preheating is set to ON in item 2 of the User menu, the
set point must be congured to the fresh air temperature,
at which the preheating should connect.
Setting option: between -15 and 0 °C.
Factory setting: -3 °C.
21 - Bypass open
Here you set the temperature at which the bypass should
be 100 % open. You set a temperature dierential which
means that if you want the bypass to be 100 % open at
e.g. 23 °C and if the set temperature in User Menu item 1
is 20 °C, this menu item should be set to 3 °C.
The bypass will open, provided that:
1. The exhaust temperature is higher than the outdoor
air temperature.
2. The outdoor air temperature is above the set tempera-
ture in the Service Menu Item 29.
GE Energy 1/2/3 with modulating bypass: If the tempera-
ture rises 0.5 °C above the temperature set in User Menu
item 1, the bypass damper will begin to open. The bypass
is 100 % open when the temperature reaches the set point
in the User Menu Item 1 + the temperature dierential set
in this menu item.
To get a smooth opening of the bypass, the temperature
at which the bypass is fully open should be set appr. 3 ºC
above the set temperature in Use Menu item 1.
GES Energy S/M with ON/OFF bypass: The bypass opens
when the temperature reaches the set point in the User
Menu Item 1 + the temperature dierential set in this menu
item.
Setting option: between 1 and 10 °C.
Factory setting: 3 °C.
22 - Regulation water
If a water after heater with a motor-operated valve is
installed in the system it may be necessary to adjust the
regulation time.
The less regulation time, the faster the motor-operated
valve will regulate.
Setting option: between 1 and 250 seconds.
Factory setting: 20 seconds.
23 - Regulation electricity
If an electrical preheater or an electrical after heater is
installed, it may be necessary to adjust the regulation time.
Setting option: between 1 and 300 minutes.
Factory setting: 3 minutes.
24 - Frost reduction
To avoid icing of the counter current heat exchanger,
the supply air ow can be reduced gradually, when the
exhaust air temperature after the counter current heat
exchanger has fallen below the set temperature. This
function gradually reduces the supply air ow, until the set
value has been reached.
Caution: May cause negative pressure in the house!
Setting option: between 0 and 10 °C. The function is dis-
abled if set to 0 °C.
Factory setting: 0 °C.
25 - Frost protection
If a water after heater with motor-operated valve is instal-led
in the system, a frost protection sensor must be tted to the
water after heater and the set point congured to ON.
If no frost protection sensor is installed, the set point must
be congured to OFF.
Setting option: ON/OFF.
Factory setting: OFF.
26 - Frost protection temperature
If frost protection in item 25 is set to ON, the frost protec-
tion temperature must be congured to the temperature
where the system should stop and the motor-operated
valve open completely for the ow of hot water.
Setting option: between 0 and 10 °C.
Factory setting: 5 °C.