Geotech Geocontrol PRO User manual

Rev10/27/2017 Part# 11150263 `
Geocontrol
PRO
Installation and Operation
M
a
nu
a
l


Table of Contents
DOCUMENTATION CONVENTIONS ............................................................................................1
Section
1:
System Description ......................................................................................................3
Section
2:
System Installation.......................................................................................................4
Section
3:
System Op
e
r
a
t
i
o
n
.........................................................................................................5
Section
4:
System
M
a
i
n
t
e
n
a
n
ce
....................................................................................................7
Section
5:
System Troubleshooting.............................................................................................10
Section
6:
System Specifications ................................................................................................12
Section
7:
Replacement Parts List..............................................................................................15
EC Declaration of Conformity.......................................................................................................19
THE W
A
RR
A
NTY ........................................................................................................................20

1
DOCUMENTATION CONVENTIONS
This manual uses the following conventionsto present
i
n
form
a
t
i
o
n
:
WARNING
An exclamation point icon indicates a WARNING of a situation or condition
that
could lead to personal injury or death. You should not proceed until you read
and thoroughly understand the WARNING message.
C
A
UT
I
ON
A raised hand icon indicates CAUTION information that relates to a situation
o
r
condition that could lead to equipment malfunction or damage. You should n
o
t
proceed until you read and thoroughly understand the CAUTION message.
A note icon indicates NOTE information. Notes provide additional or su
pp
l
e
m
e
n
t
a
ry
information about an activity or
c
o
n
c
e
p
t
.
NOTE
NOTICES
Disconnect from power source when not in use.
Controller power input source must not exceed maximum r
a
t
in
g
s.
Controller must be wired to a negative ground sys
t
e
m.
Controller may not operate properly with excess wiring not supplied by m
a
nu
f
a
c
t
ur
e
r.
Avoid spraying fluid directly at
c
o
n
t
r
o
ll
e
r.
Never submerge
c
o
n
t
r
o
ll
e
r.
Avoid pulling on wires to unplug controller
w
irin
g
.
Avoid using controller with obvious physical damage.
To prevent controller damage, avoid dropping
c
o
n
t
r
o
ll
e
r.
In order to ensure that your Controller has a long service life and operates
properly, adhere
t
o
the cautions below and read this manual before use.

2
Notice for consumers in
Eu
rop
e
:
Thefollowing apply only to users in European
c
o
un
t
ri
e
s
•
This product is designated for separate collection at an appropriate collection
p
o
in
t
.
Do not dispose of as household
w
a
s
t
e
.
•
For more information, contact the seller or the local authorities in charge of
w
a
s
t
e
management.
TheGeotech Geocontrol PROcannot be made dangerous or unsafe as a result of
failure due
t
o EMC Interference.
Do not operate this equipment if it has visible signs of significant physical damage
other
t
h
a
n normal wear and tear.
This symbol indicates that this product is to be collected separately.

3
Section
1:
System Description
Function and Theory
The Geocontrol PROis a unique controller for operating down well bladder type s
a
m
p
lin
g
pumps. When an external 12 VDCpower source is connected to the controller, the internal
air compressor is capable of producing pressure up to 100 PSI
(7
b
a
r
)
. This pressure allows
the user to take samples from a depth to 180’
(
55 m
)
.
The controller offers a variable cycle timer for controlling the portable compressor’s
ON
t
im
e
and OFF time. While the compressor is ON, air is pushed down well to the bladder pump,
c
o
mpressing the internal bladder and evacuating the liquid in the pump. When the
c
o
m
p
r
e
ss
o
r
turns OFF, the air pressure in the pump exhausts out of the system, allowing liquids to enter
the
pump. See Figure 1-1.
Compressor OFF
Compressor ON
Figure 1-1: Bladder Pump when the Compressor is ON and OFF

4
Section
2:
System Installation
To assemble the Geocontrol PRO,make sure the power switch is in the
OFF position
(
r
o
c
k
e
r in
down
p
o
si
t
i
o
n
)
. Plug the power input cord into a fuse protected 12V lighter receptacle on a
negatively grounded system. If the controller is to be wired directly to a 12V battery, connect the
positive
(
r
e
d
)
alligator clip to the positive
(
r
e
d
)
battery terminal and connect the negative
(
b
l
a
c
k
)
alligator clip to the negative
(
b
l
a
c
k
)
battery terminal. Next, securely plug in the circular plug
connector on the opposite end of the cable to the corresponding receptacle
o
nthe face of the
controller. Continue by plugging the pump’s air hose into the port labeled AIR
o
n the controller’s
face. Then plumb the discharge line into a suitable container. Check all wiring and plumbing for
c
o
rr
e
c
t
n
e
ss.
Before proceeding, confirm the 12VDC system polarity is not reversed at any connection
p
o
in
t
.
DC Power Cord
w
i
t
h
Cigarette
L
i
g
h
t
e
r
A
d
a
p
t
or
AC Power Cord
and Adaptor
Adaptor
12
V
o
l
t
B
a
tt
e
r
y
Figure 2-1: Installation Diagram
Verify the 12VDC system to be used is rated and fuse protected for operation at 15 amps
continuous operation. Failure to verify system rating could result in damage to
equipment. Overheated wiring and other materials or components in contact or near by
the power delivery system could pose a potential fire or burn hazard.

5
Section
3:
System Opera
t
i
o
n
Disconnect power source when not in use.
Double check 12V systems positive and negative are not reversed at any connection
p
o
in
t
.
Before turning the power switch
ON,
turn the Geocontrol PRO’s
FILL TIME
and
DISCHARGE
TIME
knobs to adjust the cycle times. Theseknobs are located on the front
face of the
Ge
o
c
o
n
t
r
o
l PRObelow the airline pressure gauge. To the left is DISCHARGE TIME
and to the right is FILL
TIME
. Use the radial number scales around each timer knob to adjust
timer values in s
e
c
o
n
d
s.
Discharge
Time
The discharge time is the time it takes to squeeze the bladder and push the water out of the
pump. Increase
t
his time with increased depth to water and larger bladder pumps. Decrease
this time with l
ow
e
r depth to water and smaller bladder pumps. Timer can be set from
approximately 2-75 s
e
c
onds
Fill
Time
The fill time is thetime allowed for the bladder to refill. Increase the fill time with more depth to
water
a
n
d
larger bladder pumps. Decreasethe fill time with less depth to water and smaller
b
l
a
dd
e
r pumps. The timer can be set from approximately 2-75 seconds. Fill rate depends on
hy
d
r
o
s
t
a
t
i
c
pressure
(
p
r
e
ssur
e
from the water above the
p
um
p
)
and varies depending on pump
p
l
a
c
e
ment within the water column; the more water above the pump the faster it will
f
ill.
Turn the controller power switch ON. When using longer fluid discharge lines, it could take
mul
t
i
p
l
e
cycles for water to reach the outlet. If the fluid discharge from the pump falls off before
the discharge cycle is complete, the discharge time is set too high. This could result in a
c
r
ea
s
e
d
bladder that will reduce per cycle pump volumes. Therefore, if the compressor is still runnin
g
and water has stopped coming out of the discharge tube, the discharge time should
b
e
decreased. Pumping efficiency can be maximized by measuring the amount of fluid
d
is
c
h
a
r
g
e
d
. If
the volume of fluid after one pump cycle is less than the rated volume of the pump
b
e
in
g
used,
then the fill rate can be in
c
r
ea
s
e
d
.
Do not operate this equipment if it has visible signs of significant physical
damage other
t
h
a
n normal wear and tear.
Operating the equipment in any way other than that described within this
document
c
o
ul
d
potentially damage the
e
q
ui
p
m
e
n
t
.

6
Theair line pressure gauge can be utilized to maximize efficiency. The pressure indicated on the
gauge should not exceed an equivalent depth to water pressure. 1 PSI = 2.31’
(1
bar = 1.02 m
)
of
water. Once the bladder in the pump is empty of liquids the pressure will increase sharply. If a quick
pressure increase is noticed, reduce the discharge time until the
q
ui
c
k
pressure increase is no
longer
n
o
ti
c
eable.
For example, if the well you are sampling has a depth to water of 23’
(7
m
)
the pressure gauge
may not exceed 10 PSI (.7 bar)
.
When the
d
is
c
h
a
r
g
e
cycle begins the reading on the pressure
gauge will begin to rise. When pressure based on depth to water has been reached the reading
will stabilize at that pressure until the bladder is empty or
d
is
c
h
a
r
g
e
d
. Once the bladder is
compressed completely the pressure will again start to increase. For m
a
x
imum volume per cycle,
this is the optimum point at which the discharge timer
wo
ul
d
expire and the fill rate timer would
begin. To reduce the volume pumped per cycle, decrease the discharge time.
For use with negative
(
-
)
ground systems
o
nly.
Exceeding the recommended duty cycle will cause
o
v
e
rh
ea
t
in
g
. Damage will
result if the supply voltage exceeds 14 VDC.

7
Section
4:
System
M
a
i
n
t
e
n
a
n
ce
Maintenance Pro
ce
d
u
r
e
s
Disconnect power source when not in use.
Unit must be returned to Geotech Environmental Equipment for any service. In order to ensure a
long service life, keep the Geocontrol
PRO
clean. A soft, damp cloth can be used to remove dust
and dirt from the exterior surfaces of the Geocontrol PRO.In extreme cases, or to remove aged
caked on dirt and dust, a mild soap and water solution can be applied to a soft cloth
a
n
d
used to
clean the exterior surfaces of the Geocontrol PRO.Do not soak or directly spray li
q
ui
d
s on the
Geocontrol PRO.
Solenoid Maintenance
The following procedure outlines how to remove, disassemble, and clean a stuck or clogged
breather vents on the solenoid.
If you have brass breather vents and would like to replace them with the newer version of
stainless steel breather vents, contact Geotech Environmental Equipment and reference part #
11150333.
Tools
•
Phillips head screwdriver
•
1/4” wrench
•
7/16” wrench
•
Needle nose pliers
Steps
1. Unplug unit.
2. Remove clear tubing that connects to the compressor and the air pressure gauge.
•
Do not remove the tubing at the connections on the solenoid. See Figure 4-1.
The space that you will be working in will be tight. Use needle nose pliers to disassemble and
reassemble the solenoid.
Equipment should be repaired by Geotech Environmental Equipment factory
trained repair technicians only. Improper repair of equipment may result in
degradation of
p
e
r
f
o
rm
a
n
c
e
and/or service life. Disassembly exposes
potentially dangerous moving components that
c
o
ul
d
injure someone who is
not properly trained to repair this
e
q
ui
p
m
e
n
t
.

8
Figure 4-1: Compressor
3. Remove the two screws that connect the solenoid to the casing.
•
Do not disconnect the three black wires from the solenoid; they should be long
enough to allow you to set the solenoid down on a flat surface for cleaning. See
Figure 4-2.
Figure 4-2: Removing solenoid from casing
4. Unscrew the breather vents from the solenoid using a 7/16” wrench. See Figure 4-3.

9
Figure 4-3: Removing breather vents
5. Clean breather vents with water.
•
Do NOT use rubbing alcohol.
6. After cleaning is complete, put the breather vents back on the solenoid.
Make sure they are tightened.
7. Attach the solenoid to the casing using a 1/4” nut driver.
•
The clear tubing should point toward the compressor (right side).
8. Attach the tubing back to the compressor and the air pressure gauge.
•
Note that the longest piece of tubing attaches to the compressor.
If you need further assistance or want to replace the breather screens call Geotech Service at 1-
800-833-7958.

10
Section
5:
System Troubleshooting
The Geocontrol PROhas been designed and manufactured to provide a long service life
a
n
d
trouble free operation in the field. If the compressor, during charge cycles, slows, check supply
voltage. If the supply voltage falls below 12V, the compressor’s
p
e
r
f
o
rm
a
n
c
e
will be directly
affected. A fully charged battery will produce the best r
e
sul
t
s.
Other sources of low pump output may be 12V lighter receptacles or plugs. Ensure these
connections are securely plugged in and clear of any debris. Once securely plugged in, r
o
t
a
t
in
g
the connection can often help if there is a dead spot in the connector. Also, check for
c
o
nn
e
c
tion
and cable fatigue, cracks, surface oxidation, rust, or other visible damage.
Problem: The compressor does not turn o
n.
Solution
•
Check battery polarity. In other words, the positive and negative cables are connected
positive to positive and negative to negative on the 12V battery. TheGeocontrol PRO
is
p
r
o
t
e
c
t
e
d
from damage due to reverse polarity
c
o
nn
e
c
t
i
o
n.
•
Turn the power switch to the OFFposition and let the unit sit in the OFFstate
for
t
wo
minutes. This will hard reset the electronic timer m
o
d
ul
e
.
•
If ambient temperatures are over 104°F
(
40°C
),
disconnect the compressor from power
and l
e
t
sit in a cool location. Do not open the case for any reason. Opening the case
will expose the internal components to debris that could result in reduced life
o
r
immediate equipment failure.
•
If the compressor still does not turn on the electronic timer module may have
f
a
il
e
d
.
Call Geotech Service at 1-800-833-7958 to arrange for the equipment to be sent back
t
o
a factory authorized repair l
o
c
a
t
i
o
n.
•
If 15 Amp circuit breaker is tripped, push to reset. If it trips again, call Geotech
Service at 1-800-833-7958 to arrange the equipment to be sent back to a
factory
a
u
t
h
o
ri
ze
d
repair l
o
c
a
t
i
o
n.
Problem: Compressor turns on and fluid is being pumped but no pressure is indicated on the
g
a
u
g
e
.
Solution
•
The pressure gauge has failed; however, operation of the device may continue even
t
h
o
u
g
h the gauge feature is not operational. Call Geotech Service at 1-800-833-7958 to
arrange
f
o
r the equipment to be sent back to a factory authorized repair l
o
c
a
t
i
o
n.
Problem: Fluidis not being pumped and the compressor turns on, no pressure is indicated on the
g
a
u
g
e
.

11
Solution
•
Remove the air line from the front of the Geocontrol PRO. Block the air outlet on the
f
r
o
n
t
of
the Geocontrol PROwhile the compressor is running to verify the pressure gauge needle
indicates an increase in pressure. Remove the blockage from the air outlet and
o
b
s
e
rv
e
whether a small burst of compressed air is released. If pressure cannot be built at the outlet
on the front of the Geocontrol PRO,call Geotech Service at 1-800-833-7958 to arrange for
the equipment to be sent back to a factory authorized repair l
o
c
a
t
i
o
n.
•
If pressure can be built at the air outlet on the front of the Geocontrol PROwhile the
c
o
m
p
r
e
ssor is runnin
g
o
Attach the air line only and block the end. Verify the pressure gauge needle
indicates an increase in pressure. Remove the blockage from the end of the air
line and
o
b
s
e
rv
e
whether a small burst of compressed air is released. If pressure
cannot be built
a
t
the end of the air line, check the air line for cuts, kinks and
holes, especially at/nearthe bladder pump hose barb or compression fitting
c
o
nn
e
c
t
i
o
ns.
•
If pressure can be built at the end of the air line while the compressor is runnin
g
:
oAttach the air line to the bladder pump. Remove the fluid discharge tube from the
b
l
a
d
der pump.
oWhile the compressor is running, very little air discharge should be felt at the pump
discharge fitting. Thepressure gauge on the front of the Geocontrol PROshould
indicate a rise in pressure.
oIf this does not occur and a continuous air flow can still be
f
e
l
t
at the pump fluid
discharge fitting, then the bladder, or bladder seal, has been
c
o
m
p
r
o
mised and
should be repaired or replaced. Information on this procedure can be found in the
product manual specific to the bladder pump being used. Or call Geotech Service
a
t
1-800-833-7958 for further
a
ssis
t
a
n
c
e
.
Do not over pressurize and crease the bladder inside the pump, as this will
reduce the fluid flow during normal
o
p
e
r
a
t
i
on.

12
Section
6:
System Specifications
Power R
e
q
u
i
r
e
m
e
n
t
s
:
72-84 W
12-14 VDCinput at 7.5
A
m
p
s
Nominal Operating C
u
rr
e
n
t
:
6 Amps DC
Over Current Pro
t
ec
t
i
o
n
:
15
A
m
p
s
T
i
m
e
r
:
Discharge Time
Fill Time
1.8 sec. min. –75 sec. m
a
x
.
1.8 sec. min. –75 sec. m
a
x
.
(+/- .25% repeatability)
Maximum Operating D
e
p
t
h
:
180’
(
55 m
)
Maximum Operating Pr
e
ssu
r
e
:
100 PSI
(7
b
a
r
)
(
s
e
l
f
-limited for s
a
f
e
t
y
)
@ 0.83 CFM (1.41 m3/h)
Ambient Operational T
e
mp
e
r
a
t
u
r
e
:
50°F-104°F
(
10°C
-
40°C
)
D
i
m
e
ns
i
o
ns
:
6.70" H x 4.80" x 11.40" W
(
17.02
c
m H x 12.92 cm D x 28.96 cm
W
)
W
e
i
g
h
t
:
9 lbs.
(4
kg
)
t
o
t
a
l
F
ea
t
u
r
e
s
•
Variablepump Discharge time
c
o
n
t
r
o
l.
•
Variablepump Fill time
c
o
n
t
r
o
l.
•
Interchangeable pump connection
c
o
n
f
i
g
ur
a
t
i
o
ns.
•
Operation with dedicated pump systems and special purpose well
c
a
p
s.
•
Approx. 45 to 60 minute operation with 8.0Ah lead acid battery
(
B
a
tt
e
ry Module
w
/
o
Charger, Geotech PN: 77250001
)
.
•
Reversepolarity
p
r
o
t
e
c
t
i
o
n.
•
AC adapter optional for use with world mains
c
o
nn
e
c
t
i
o
n.

13
Figure 6-1: Wiring Diagram

14
27
Parts Assembly
10
13
19
1
b
32
23
25
1a 21
11 33
20 30
12b 29
14 13
24 22
14 20 20
28 25
17
12a 16 18
431
8 20
5
26 34
635
2 3
7
15
9

15
Section
7:
Replacement Parts List
MODEL GEOCONTROL PRO –51150122
I
te
m
Qty
Description
Part No.
1
a
1
ENCLOSURE, GEOCONTROL
PRO,BACK, CE
51150121
1b
1
ENCLOSURE, GEOCONTROL
PRO,BACK, CE
51150121
2
2
POT,10K, 20%
W
/
KN
O
B
11150244
3
1
SWITCH,
GEOCONTROL
PRO
11150248
4
1
HOSEBARB,
SS4, BLKHD, .170 X 1
/
8
"
21150021
5
1
CONN, AMP, MALE, PANEL MOUNT
17200014
6
1
CIRCUIT BREAKER,
15AMP
GEOCONTROL
PRO
11150247
7
4
FOOT, RUBBER,
7/8",
W
/
WASHER
11150262
8
2
SCREW,
SS8, 4-40 X 7/16" FH PHIL
16700007
9
4
SCREW
SS8, 8-32 X.5", PNH
PPF036001
10
1
HANDLE,PE,NI
11350009
11
1
TEE,
BRS, 1/8" NPT, FXFXF
PPP047034
12a
1
GAUGE,
PANELMOUNT, 1-100PSI W/MOUNTING CLAMP
11150254
12b
1
GAUGE,
PANELMOUNT, 1-100PSI W/MOUNTING CLAMP
11150254
13
14
SCREW,
SS8, 6-32 X .25", PNH,
M
/
S
17200078
14
4
NUT,
HEX,
4-40, NYLOC
17200046
15
4
WASHER,
SS8, #8, LOCK
17200081
16
1
SOLENOID, GEOCONTROL
PRO
11150249
17
1
STANDOFF,
NYL, .187 X .437 X .375
17500355
18
2
SCREW,
SS8, 4-40 X 1.25", FLHD
PPF051015
19
4
SCREW,
SS8, 6-32 X 3/8", FLH
PPF013034
20
4
HOSEBARB,
BRS, 90D.170 X 1
/
8
M
P
T
17200393
21
1
VENT, BREATHER,
1/4" NPT
11150252
22
2
VENT, BREATHER,
1/8" NPT
11150333
23
4
PLUG, BRS, 1/4"NPT, SOCKET
11150251
24
1
NUT, SS8, 5/16-32,
HEX,
THIN
11150261
25
5
CLAMP, NYL, 1/4" SNAPPER
11150259
26
1
QCK CNCT, NCKL, 1/4" X 1/8MPT, PUSH/PULL
PPP103001
27
1
ASSY,PCB,
GEOCONTROL
PROPOTTED
51150054
28
1
TUBING
,FEP,
.170 X1/4, FT FEP
87050509
29
1
TUBING
,FEP,
.170 X1/4, FT FEP
87050509
30
1
TUBING
,FEP,
.170 X1/4, FT FEP
87050509
31
1
DIODE, SCHOTTKY,
100V, 40A, TO-247AC
16550223
32
1
COMPRESSOR,
PRO,SIPPER
11150325
33
1
HOSEBARB,
BRS, .170 X 1
/
4
M
P
T
16550032
34
3
WASHER,
SS8, #10, LOCK
PPF022003
35
3
SCREW,
SS8, 10-32 X 5/8", PNH
PPF037008
N
/
S
1
WASHER,
SS410, 5/16", INTRNLTOOTH
17500339
N/S = Not
S
h
ow
n

16
Accessories
Description
Part No.
GEOCONTROL
PROW/CASE, 1.66, CE, PUMP, 12VDCCORD,
BATTERY
W/CHRG
91150011
GEOCONTROL
PROW/CASE, .85, CE, PUMP, 12VDC CORD,
BATTERY
W/CHRG
91150015
GEOCONTROL
PROW/CASE, .675, CE, PUMP, 12VDCCORD,
BATTERY
W/CHRG
91150016
GEOCONTROL
PRO,W/CASE, CE, 12VDC CORD,NO PUMP, NO BATT
91150017
GEOCONTROL
PRO,CE, SOLO,
CONTROLLER
ONLY, NO ACCESSORIES
51150122
POWER
SUPPLY,
EXTERNAL,
AC
ADAPT
12V, 100W
51150063
ADAPTOR, CONTROLPRO-WELL
CAP
INCLUDES
10FTTUBING
81150019
CASE,
GEOCONTROL
PRO,CE
51150127
ASSY,
POWER
CORD,DC
W
/
A
M
P
57500008
ADAPTER, CIGARETTE
TOCLIPS
17500035
BATTERY/CHARGER,
MODULAR, 12VDC,7.5Ah, MALE CIG PLUG
77250000
KIT,WLM-BP
CONTROLLER
LINK LOW DRAWDOWN OPTION
91150001
ASSY, CABLE,WLM, LOGIC UNIT CONT
52050174
Maintenance Accessories
Description
Part No.
REBUILD KIT, COMPRESSOR, SIPPER PRO
11150334
REBUILD KIT, SOLENOID, GEOCONTROL PRO
11150433

17
DOCUMENT REVISIONS
EDCF#
DESCRIPTION
REV/DATE
-
Previous Release
10/29/12
1583
Added Compressor Repair Kit to Replacement Parts List.
Added Revision History Table - SP
05/24/13
-
Updated back page information, updated EC Declaration of Conformity,
added “Maintenance Accessories” under Section 8: Replacement Parts
List, SP
1/13/15
Project #1526
General formatting and editing, StellaR
1/16/17
Project #1495
Timer changed from 60 seconds to 75 seconds, StellaR
10/27/2017
Other manuals for Geocontrol PRO
3
Table of contents
Other Geotech Controllers manuals
Popular Controllers manuals by other brands

Johnson Controls
Johnson Controls FMS-1655L installation manual

Delta Electronics
Delta Electronics DTC1000 Series instruction sheet

L-Acoustics
L-Acoustics LA2Xi owner's manual

Newport
Newport SMC100CC user manual

Dahua
Dahua DHI-ARC3008C user manual

Ascon tecnologic
Ascon tecnologic X33H operating instructions