2008.5.28
Long-Distance Connection
The supplied Terminal Resistor must be used when the connection distance is greater
than 200 meters.
GV-I/O USB Box
(the first) GV-I/O USB Box
(the last)
GV-NET/IO Card
When one GV-I/O USB Box is connected to one GV-NET/IO Card, only insert the
Terminal Resistor in the GV-I/O USB Box.
RS-485+
RS-485-
RS-485+
RS-485-
Terminal Resistor
GV-I/O USB Box
RS-485+
RS-485-
RS-485+
RS-485-
Terminal Resistor
~
When one GV-I/O USB Box is connected to another GV-I/O USB Box or more, only
insert the Terminal Resistors in the RS-485 connectors of the first and the last connected
GV-I/O USB Boxes.
Wet Contact Dry Contact (Default)
The GV-I/O USB Box allows the use of mixing dry and wet contact devices together.
The 16 inputs divided as four-in-one groups (A, B, C and D) are related to the 4
switches on the box for dry and wet contact.
To change the inputs to different kind of contact, push the switch upward (wet contact)
or downward (dry contact).
DIP Switch
1234
ECE
ON
A B C D
1234
ECE
ON
A B C D
USB Driver Installation
To use the USB function, it is required to install the driver on the PC. Follow these steps
to install the driver:
(3) Click Install to install the drivers. When the installation is complete, this message will
appear: Install done!
(4) Click Exit to close the dialog box.
(1) Insert the software CD. It will run automatically and pop up a window.
(2) Select Install or Remove GeoVision GV-Series Driver, and then click Install
GeoVision USB Devices Driver. This dialog box appears.
(5) To verify the drivers are installed correctly, go to Device Manager. Expanding the
Ports field, you should see one entry for Prolific USB-to-Serial Bridge.