GEZE SECULOGIC T 320 Series Installation and operation manual

1
GEZE
SECULOGIC
T 320
Emergency Exit System
Terminal
EN
Installation And Commissioning
Instructions With Connection Diagram

SECULOGIC T 320
2
Content
1 In this document ...................................................................................................................................................3
1.1 Product description ......................................................................................................................................................................................3
1.2 Other documents ..........................................................................................................................................................................................3
1.3 Symbols and signs .........................................................................................................................................................................................3
2 Safety and liability ................................................................................................................................................4
2.1 Basic safety instructions .............................................................................................................................................................................4
2.2 Product liability ..............................................................................................................................................................................................4
3 Installation and assembly ...................................................................................................................................5
3.1 Requirements ..................................................................................................................................................................................................5
3.2 Install the terminal ........................................................................................................................................................................................5
4 Commissioning ......................................................................................................................................................5
4.1 Requirement ...................................................................................................................................................................................................5
4.2 Service mode ..................................................................................................................................................................................................5
4.3 Settings ............................................................................................................................................................................................................6
4.4 Terminal T 320 settings ................................................................................................................................................................................6
4.5 Description of basic functions ..................................................................................................................................................................7
5 Operation .................................................................................................................................................................8
5.1 Control the terminal T 320 via key-operated push button ............................................................................................................8
5.2 Open the doors and trigger the alarm in an emergency ...............................................................................................................9
5.3 Cancel alarm ....................................................................................................................................................................................................9
5.4 Read out fault report (via TZ 320) ......................................................................................................................................................... 10
5.5 Read out alarm signal (via TZ 320)........................................................................................................................................................ 10
5.6 Correct fault .................................................................................................................................................................................................. 10
6 Connection diagram ..........................................................................................................................................11
6.1 Door control unit (terminals) ...................................................................................................................................................................11
6.2 Terminal T 320 ...............................................................................................................................................................................................12
6.3 Connection of external key-operated push button to T 320 ......................................................................................................13
7 Technical Data ......................................................................................................................................................14
7.1 Terminal T 320 UP ........................................................................................................................................................................................14
7.2 Terminal T 320 AP ........................................................................................................................................................................................15

SECULOGIC T 320
3
In this document
1 In this document
This instruction describes the installation, commissioning and connection of the GEZE Terminal T 320.
1.1 Product description
The GEZE terminal is part of the SecuLogic escape route system and secures and monitors electrically locked
doors in bidirectional emergency routes. Doors along emergency routes are reliably safeguarded against
unauthorised access in both emergency directions by the GEZE door control unit with Terminal T 320.
Simultaneously, entry in emergency situations is ensured at all times via the integrated emergency button.
1.2 Other documents
Data sheets with technical data are included in delivery of the corresponding components. You will nd these
data sheets and other documents as well as the detailed installation and commissioning instructions with
connection diagram for the door control unit TZ 320 No. 131537 on the internet at www.geze.de/SecuLogic.
1.3 Symbols and signs
Warning notices
In these instructions warning notices are used to warn you about damage to person and property.
XXPlease always read and observe these warning notices.
XXFollow all measures designated with the warning symbol and warning word.
Warning
symbol
Warning word Meaning
WARNING Danger for persons.
Non-observance may lead to serious injury or death.
Further symbols and signs
In order to clarify the correct meaning, important information and technical information is highlighted.
Symbol Meaning
"Important information"
"Additional information"
XX Symbol that indicates an action: You are required to do something here.
Note the correct order where there is more than one step.

SECULOGIC T 320
4
Safety and liability
2 Safety and liability
The GEZE terminal was designed according to state-of-the-art technology and recognised, safety-related regulations.
However, there might be danger during installation and use. Therefore, pay attention to the following instructions.
2.1 Basic safety instructions
XXInstallation, commissioning and repairs may only be carried out by experts authorised by GEZE.
XXUse only GEZE original parts for repair work.
XXGEZE assumes no liability for damages resulting from unauthorised changes to the system.
XXPrimary safety measures take place on site.
XXThe standards VDE 0100 and VDE 0815 must be observed during cable routing.
XXAn expert must check the doors with electric locking mechanism in the escape routes once a year.
The expert is to issue a certicate on the in-service inspection, which the operator has to show
on demand to the building supervisory board. Inspection can be carried out by a GEZE
service technician or a professional organisation authorised by GEZE.
XXFurthermore, GEZE recommends that the operator inspects the escape route system monthly for externally
identiable damages and defects. Such damages and defects, if existing, must be repaired immediately by a
GEZE service technician or a professional organisation authorised by GEZE.
Intended Use
The GEZE door control unit is designed to control and monitor electrically locked emergency routes.
External products may only be integrated after consulting GEZE.
Contrary to intended use
The connection of products which were not expressly approved for use by GEZE is contrary to the intended
purpose.
2.2 Product liability
àIn accordance with the manufacturer's dened liability for its products in the Product Liability Act,
attention should be paid to the information contained here and in corresponding installation instructions and
connection diagrams for the product (product information, intended use, incorrect use, product performance,
product maintenance, obligations to supply information and instructions). Non-observance releases the
manufacturer from its liability.
àOnly experts authorised by GEZE may carry out installation, functional inspection and maintenance.
GEZE assumes no liability for damages resulting from unauthorised changes to the system.
àGEZE assumes no liability for combining with devices from other manufacturers. Use only GEZE original parts
for repair work and maintenance.

SECULOGIC T 320
5
Installation and assembly
3 Installation and assembly
WARNING!
Danger of electric shock.
XXInstallation may only be carried out by an expert authorised by GEZE.
XXCheck that the cables are disconnected before installation.
3.1 Requirements
àCable routing is in accordance with GEZE cable diagram
àAutomatic circuit breakers as primary disconnection on the mains-side
àCompliance with the VDE 0100 and VDE 0815 standards for the cable routing
àSabotage secured cable routing according to VDE 0833 (on-wall cables in the steel tube)
àFor in-wall plug socket variant installed near the door (depth 62.5 mm) with an installation height top of oor
of 850 mm to a maximum of 1200 mm for the emergency button
3.2 Install the terminal
Installation of the T 320 terminal is identical to installation for the door control unit TZ 320. Consult the
installation instructions from the Installation and Commissioning Instructions No. 131537 or the Brief Instructions
No. 139926. When using a T 320 terminal a TZ 320 is always required. The TZ 320 assumes control of the system.
4 Commissioning
4.1 Requirement
Before the rst commissioning of doors with electric locking mechanisms in the escape routes, correlation with
verication of suitability is to be conrmed by means of a certicate issued by the manufacturer. An expert must
also ensure that the electric locking mechanism is installed properly and operational (see checklist for
commissioning in the TZ 320 instructions or in the inspection book).
The door control unit TZ 320 must be in operation, and the connection between the door control unit and
terminal must be set up according to the connection diagram (page 12). All settings for the terminal are
implemented via the door control unit TZ 320.
4.2 Service mode
The service mode must be activated at the door control unit TZ 320 in order to set parameters on the terminal.
4.2.1 Switch on the service mode
Requirement:
àThere is no alarm.
àThe burglar alarm system is disabled.
XXTurn the key left and hold for approximately ten seconds.
àThe right LED lights up green, the left and lower LEDs are o.
4.2.2 Switch o the service mode
XXDo not make adjustments or select 'end of service mode' in the service menu for three minutes.
àThe door control unit and terminal are in normal state again.

SECULOGIC T 320
6
Commissioning
4.2.3 Connect the service terminal ST 220 with the door control unit
The service terminal is connected with the door control unit via an infrared interface.
3
1 Service terminal ST 220
2 Infrared interface to TZ 320
3 ESC button
XXBefore covering the control unit, hold the service terminal and press the ON button for approximately one
second.
àThe service terminal is switched on.
XXPress the ESC button.
àThe rst level of the service menu is displayed.
4.3 Settings
All settings can only be implemented with the service terminal ST 220 via the TZ 320.
4.4 Terminal T 320 settings
A terminal connected to TZ 320 is automatically recognised and switched on. The terminal can be switched o
via the service menu.
4.4.1 Switch on terminal
XXIn the service menu, select system environment > terminal > terminal available.
àThe upper display line of the service terminal shows the selected value.
4.4.2 Switch o terminal
XXIn the service menu, select system environment > terminal > terminal unavailable.
àThe upper display line of the service terminal shows the selected value.
4.4.3 Set sabotage contact
XXIn the service menu, select system environment > sabotage contacts.
XXTo evaluate sabotage contacts, select TT > sabotage contact TT active : yes.
XXTo not evaluate sabotage contacts, select TT > sabotage contact TT active : no.
4.4.4 Short-term unlock and alarm setup
The settings for short-term unlock and alarm setup for the terminal are implemented by the door control unit.

SECULOGIC T 320
7
Commissioning
4.5 Description of basic functions
4.5.1 Short-term unlock
Short -term unlock is the authorised, time-limited release of the emergency route locking device. During the
short -term unlock time the door can be passed through without triggering an alarm. It is triggered via the inter-
nal key-operated push button or an external control device connected to the 'short-term unlock' input.
4.5.2 Abort with short-term unlock
With continuous short-term the door locks ahead of time when the door is closed before expiry of the short -term
unlock time. This prevents accessibility for unauthorised persons after somebody has passed through the door.
4.5.3 After-trigger with short-term unlock
The unlock time restarts if a short-term unlock is triggered again during the release time.
4.5.4 Pre-alarm
If the release time is exceeded during passing through, an acoustic signal is output which informs the user that
the short -term unlock time has been exceeded. If the door is closed during a pending pre-alarm it is automati-
cally locked and the pre-alarm is reset.
4.5.5 Door alarm
The door alarm is triggered if the pre-alarm time is exceeded. The door alarm must be reset via the internal key
switch or via a short-term release. If the door is closed during a pending door alarm, it is locked and can only
be unlocked again when the alarm has been reset (except with actuation of the emergency button or with
emergency unlock). The door alarm is also triggered with a 'door break-in'.
4.5.6 Unlocked
The current supply to the interlocking element is permanently interrupted. The door can be passed through
without triggering an alarm.
4.5.7 Locked
The interlocking element is fed with current via the door control unit. The emergency route locking device is
'active' and passing through for unauthorised persons is only possible via the emergency button (alarm is triggered).
4.5.8 Emergency unlock
The TZ 320 can be emergency unlocked via the re alarm system or hazard alarm system (burglar alarm system/
hazard alarm system/smoke and heat venting system). This is a non security-relevant interruption of current
supply to the interlocking element.
4.5.9 Direct release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism via an opening contact
by actuating the emergency button.
4.5.10 Indirect release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism if a further switching op-
eration is triggered upon activating the emergency button via the opening contact which then interrupts power
supply to the electric locking mechanism.

SECULOGIC T 320
8
Operation
5 Operation
1 'Locking' LED
2 'Door state' LED
3 'Alarm' LED
4 Emergency button
No. Display Colour Meaning
1Red Locked
Red ashing (every second) Sluice allocated
Red ashing (every 2 seconds) Locked via burglar alarm system
Red ashing (3 seconds on, 1 second o) Locked level
Green Unlocked
Green ashing (every second) Short-term unlock
Green ashing (every 2 seconds) Unlocked via time-switch
Green ashing (3 seconds on, 1 second o) Passive sluice
2Red Door closed
Green Door open
3Yellow Alarm
Yellow ashing (every second) Pre-alarm
Yellow ashing (every second) Fault
5.1 Control the terminal T 320 via key-operated push button
Unlock door
When unlocking, the interlocking elements are disconnected by an authorised person. The door can be opened.
XXTurn the key left and hold for approximately one second.
àLED 1 ashes green. The door is unlocked.
Note
The 'Unlock' function can be disabled via the service menu:
system environment > SCT conguration > unlock by SCT activate : yes/no.
Lock door
When locking, the interlocking elements are engaged by an authorised person. The door cannot be opened.
XXTurn the key to the right.
àLEDs 1 and 2 light up red. The door is locked.
Unlock door temporarily (short-term unlock)
During the short-term unlock the door is unlocked for a settable time by an authorised person.
The door is unlocked again after expiry of the unlock time.
àIf the door is not closed after expiry of the unlock time, the pre-alarm is triggered
àIf the door is closed before expiry of the unlock time, the door is locked again (abort)
àIf a new short-term release is triggered during the unlock time, the unlock time starts over again (post trigger)
XXTurn the key to the right.
àLED 1 ashes green.

SECULOGIC T 320
9
Operation
5.2 Open the doors and trigger the alarm in an emergency
By actuating the emergency button, the interlocking elements on the corresponding door are switched o
(indirect release via TZ 320).
XXPress emergency button.
àLED 1 lights up green and LED 3 lights up yellow. The door is unlocked.
àThe alarm is triggered.
5.3 Cancel alarm
The alarm remains active at the door control unit until the cause of the alarm is eliminated and the alarm on the
door control unit or terminal is acknowledged.
5.3.1 Reset emergency button
After the emergency situation has been eliminated the emergency button must be reset.
XXRemove the cover of the emergency button.
XXTurn the emergency button to the right.
àThe emergency button returns to normal state.
XXReplace cover.
XXAcknowledge alarm.
5.3.2 Acknowledge alarm
Precondition:
àThe cause of the alarm is eliminated.
àReset alarm is displayed in the service terminal.
Acknowledge alarm and lock door
XXTurn the key to the right.
Acknowledge alarm and unlock door
XXTurn the key left and hold for approximately one second.
The non security-relevant alarms emergency unlock, door alarm and sabotage alarm can also be
acknowledged via the Lock and Unlock functions on the TE 220 and VAT 220.
The door alarm can also be acknowledged via the short-term unlock input of the TZ 320 or KL 220.
A sabotage alarm can only be acknowledged 30 seconds after the cause of the alarm has been eliminated.
For the duration of the sabotage time the TZ 320 and T 320 are primarily locked. Release via the emergency
button is possible.
If the alarm cannot be acknowledged by pressing the key-operated push button the a new alarm is possibly
pending.
XXCheck which alarm/fault is pending with the service terminal and correct with the following tables.

SECULOGIC T 320
10
Operation
5.4 Read out fault report (via TZ 320)
Faults in the system are indicated via ashing of LED 3.
XXConnect the service terminal with the door control unit.
àThe fault report is shown on the display of the service terminal.
XXFind out the cause of malfunction and correct the fault with the aid of the following table.
The table only contains faults that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further fault reports.
Fault report Cause Remedy
TT communication Connection with door control unit is faulty
XXSwitch o the terminal via the service menu
XXEstablish connection to the terminal
XXChange the terminal
5.5 Read out alarm signal (via TZ 320)
Misuse of the system or emergency situations is indicated via alarm tones and lighting up of LED 3.
XXConnect the service terminal to the door control unit and press the ESC button.
àThe alarm signal is shown on the display of the service terminal.
XXEstablish the cause of the alarm and cancel the alarm with the aid of the following table.
The table only contains alarm signals that can be caused by the Terminal T 320.
Please refer to the TZ 320 user manual for further alarm signals.
Alarm signal Cause Remedy
Sabotage alarm
sabotage contact TT Sabotage contact of the terminal is not
closed
XXClose contact
XXAcknowledge alarm after expiry of the
sabotage time
sabotage time runs Sabotage time unexpired XXAcknowledge alarm after expiry of the
sabotage time
Indirect release
EB TT pushed Indirect release via terminal XXReset the emergency button on the
terminal
fuse failure Fuse F1 is defective XXChange the fuse
J1, J2 jumper for indirect release to TZ 320
falsely set
XXConrm the emergency button of the
T 320
XXReset the emergency button of the T 320
Acknowledge alarm Cause of the alarm eliminated
XXAcknowledge alarm via the key-operated
push button
5.6 Correct fault
Fault Cause Remedy
Emergency button T 320
without
function, no
alarm signal
available
J1J2 jumper for indirect release to
TZ 320 falsely set
XXDisconnect power supply to system
XXSet jumpers J1 and J2 to external
power supply
XXConnect power supply
àAlarm signal for indirect release is
displayed
XXConrm the emergency button of the
T 320 and reset
XXAcknowledge alarm
By actuating the key-
operated push button of
the T 320 / TZ 320, all LEDs
and the emergency button
lighting go out
Ribbon cable incorrectly connected between
SCT 320 and TZ 320 / T 320
XXConnect ribbon cable correctly
All LEDs are o despite
power supply
F1 locking device of the TZ 320 is defective XXChange the F1 fuse
(GEZE Id-No. 138362, VE 10)

SECULOGIC T 320
11
6 Connection diagram
Door
state
LED
Buzzer
Emergency
button LED
Alarm LEDs
Locking LED
Sabotage
contact
Programming
interface
6.1 Door control unit (terminals)
Terminal connections
Plug and screw terminals, max. cable cross section: 1 mm²
Clamping eld Terminal Function (default setting)
X100 1 GND supply
3 24 V DC supply unit
7 Indirect release + 24 V DC
8 Indirect release - GND
41 R5485-B, communication with door control unit TZ 320
42 R5485-A, communication with door control unit TZ 320
X103 Ribbon cable plug connector for GEZE key-operated push button

SECULOGIC T 320
12
Connection diagram
6.2 Terminal T 320
Here connected to a TZ 320 SN.
Important! Set jumper 1-2 of TZ 320
to external voltage supply.
3)
1)
2) 4)
5)
GEZE Key-operated push button GEZE ribbon cable
Connection to
TST 320 X 102
Plug connector for
GEZE key-operated
push button or
illumination
X104 (red terminal strip)
GND supply
24 V DC supply
Power supply unit
Luster terminal
Door terminal
GND supply
24 V DC supply
Indirect release +
Indirect release -
Connection to
GEZE SCT 320
Plug connector for
GEZE key-operated
push button or
illumination
X107 (green terminal strip)
indirect release
indirect release
GEZE Key-operated push button SCT 320
GEZE ribbon cable
Short-term unlock via push button,
key-operated push button,
access control...
Caution! Disconnect red bridge
(1-7) in FTÖ 331U.
or
Door contact
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
24 V DC
Input 1 (short-term unlock)
Input 2 (short-term unlock)
Input 3 (Fire alarm system)
24 V DC
GND
Door control unit
Instructions for the connection diagram
1) The mains fuse is implemented on-site.
2) GEZE power supply unit with TZ 320N UP = NET220. 500 mA max. 350 mA for periphery
GEZE power supply unit with TZ 320N AP = NT19.2-24. 750 mA max. 650 mA for periphery
Spatially separate the primary and secondary sides.
3) TZ 320N UP: Protection class II (do not connect protective conductor)
TZ 320N AP: Protection class I with protective conductor test in accordance with VDE0100
4) In the on-wall variant, the luster terminal is located on the mounting plate.
5) The contact is closed in a closed door.

SECULOGIC T 320
13
Connection diagram
Simplied diagram of connection between the TZ 320 and T 320
Sequence of terminals modied
Important! Set jumper 1-2 of TZ 320
to external voltage supply.
T 320 Door terminal
TZ 320 Door control unit
X104 (red terminal strip)
X107 (green terminal strip)
Indirect release
Indirect release
Indirect release +
Indirect release -
24 V DC supply
GND supply
24 V DC
GND
6.3 Connection of external key-operated push button to T 320
Connection of the key switch to the T 320 is only possible via ribbon cable. If other
key switches are to be connected the ribbon cable must be divided. 3 wires are required for the connection.
The red wire and both adjacent wires. The other 3 wires have no function and must be insulated.
unlock
lock
COM
red wire of ribbon cable
Key-operated push button

SECULOGIC T 320
14
Technical Data
7 Technical Data
7.1 Terminal T 320 UP
Terminal T 320 UP
Function Monitoring and control of a door in bidirectional emergency routes
(with a door control unit TZ 320)
Dimensions 55 x 55 x 37 mm (W x H x D)
W x H: Helmet
T: Distance of top edge of bearing ring to rear edge of terminal
Installation in ush-mounted socket, ø 60 mm, depth 62.5 mm
Operating voltage 24 V DC (± 10 %)
Current consumption 100 mA at 24 V DC
Protection class II according to EN 60950 (in installed state)
Application In interior spaces with up to 85% air humidity (non-condensing)
Operating temperature -10 to +50 °C
Guidelines Guideline for electric locking systems of doors in escape routes (EltVTR) - version
December 1997
Package content Control unit
Indicators Locking LED, door state LED, alarm LED, buzzer
Buzzer 75 DB (at approx. distance of 50 cm)

SECULOGIC T 320
15
Technical Data
7.2 Terminal T 320 AP
Terminal T 320 AP
Variants T 320 green
T 320 white-aluminium
Function Monitoring and control of a door in bidirectional emergency routes
(with a door control unit TZ 320)
Dimensions 77 x 197 x 88 mm (W x H x D)
Installation Wall mounting
Operating voltage 24 V DC (± 10 %)
Current consumption 100 mA at 24 V DC
Protection class II according to EN 60950
Application In interior spaces with up to 85% air humidity (non-condensing)
Operating temperature -10 to +50 °C
Guidelines Guideline for electric locking systems of doors in escape routes (EltVTR) - version
December 1997
Package content Mounting plate
Pre-assembled housing
Mounting accessories
Indicators Locking LED, door state LED, alarm LED, buzzer
Buzzer 75 DB (at approx. distance of 50 cm)

Germany
GEZE Sonderkonstruktionen GmbH
Planken 1
97944 Boxberg-Schweigern
Tel. +49 (0) 7930-9294-0
Fax +49 (0) 7930-9294-10
E-Mail: sk.de@geze.com
Germany
GEZE GmbH
Niederlassung Nord/Ost
Bühringstraße 8
13086 Berlin (Weissensee)
Tel. +49 (0) 30-47 89 90-0
Fax +49 (0) 30-47 89 90-17
E-Mail: berlin.de@geze.com
Germany
GEZE GmbH
Niederlassung West
Nordsternstraße 65
45329 Essen
Tel. +49 (0) 201-83082-0
Fax +49 (0) 201-83082-20
E-Mail: essen.de@geze.com
Germany
GEZE GmbH
Niederlassung Mitte
Adenauerallee 2
61440 Oberursel (b. Frankfurt)
Tel. +49 (0) 6171-63610-0
Fax +49 (0) 6171-63610-1
E-Mail: frankfurt.de@geze.com
Germany
GEZE GmbH
Niederlassung Süd
Breitwiesenstraße 8
71229 Leonberg
Tel. +49 (0) 7152-203-594
Fax +49 (0) 7152-203-438
E-Mail: leonberg.de@geze.com
Germany
GEZE Service GmbH
Reinhold-Vöster-Straße 25
71229 Leonberg
Tel. +49 (0) 7152-9233-0
Fax +49 (0) 7152-9233-60
E-Mail: service-info.de@geze.com
Germany
GEZE Service GmbH
Niederlassung Berlin
Bühringstraße 8
13086 Berlin (Weissensee)
Tel. +49 (0) 30-470217-30
Fax +49 (0) 30-470217-33
E-Mail: service-info.de@geze.com
Austria
GEZE Austria GmbH
Wiener Bundesstrasse 85
5300 Hallwang b. Salzburg
Tel. +43-(0)662-663142
Fax +43-(0)662-663142-15
E-Mail: austria.at@geze.com
Baltic States
GEZE GmbH Baltic States oce
Dzelzavas iela 120 S
1021 Riga
Tel. +371 (0) 67 89 60 35
Fax +371 (0) 67 89 60 36
E-Mail: oce-latvia@geze.com
Benelux
GEZE Benelux B.V.
Leemkuil 1
Industrieterrein Kapelbeemd
5626 EA Eindhoven
Tel. +31-(0)40-26290-80
Fax +31-(0)40-26 290-85
E-Mail: benelux.nl@geze.com
Bulgaria
GEZE Bulgaria - Trade
Representative Oce
61 Pirinski Prohod, entrance „B“,
4th oor, oce 5,
1680 Soa
Tel. +359 (0) 24 70 43 73
Fax +359 (0) 24 70 62 62
E-Mail: oce-bulgaria@geze.com
China
GEZE Industries (Tianjin) Co., Ltd.
Shuangchenzhong Road
Beichen Economic Development
Area (BEDA)
Tianjin 300400, P.R. China
Tel. +86(0)22-26973995-0
Fax +86(0)22-26972702
E-Mail: Sales-info@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd.
Branch Oce Shanghai
Unit 25N, Cross Region Plaza
No. 899, Ling Ling Road,
XuHui District
200030 Shanghai, P.R. China
Tel. +86 (0)21-523 40 960
Fax +86 (0)21-644 72 007
E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd.
Branch Oce Guangzhou
Room 17C3
Everbright Bank Building, No.689
Tian He Bei Road
510630 Guangzhou, P.R. China
Tel. +86(0)20-38731842
Fax +86(0)20-38731834
E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd.
Branch Oce Beijing
Room 1001, Tower D
Sanlitun SOHO
No. 8, Gongti North Road,
Chaoyang District,
100027 Beijing, P.R.China
Tel. +86-(0)10-5935 9300
Fax +86-(0)10-5935 9322
E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd.
Branch Oce Singapore
21, Bukit Batok Crescent,
No. 23-75, Wcega Tower,
Singapore 658065
Tel. +65-6846 1338
Fax +65-6846 9353
E-Mail: gezesea@geze.com.sg
France
GEZE France S.A.R.L.
ZAC de l’Orme Rond
RN 19
77170 Servon
Tel. +33-(0)1-606260-70
Fax +33-(0)1-606260-71
E-Mail: france.fr@geze.com
Hungary
GEZE Hungary Kft.
Bartók Béla út 105-113.
Budapest
H-1115
Tel. +36 (1) 481 4670
Fax +36 (1) 481 4671
E-Mail: oce-hungary@geze.com
Iberia
GEZE Iberia S.R.L.
Pol. Ind. El Pla
C/Comerc, 2-22, Nave 12
08980 Sant Feliu de Llobregat
(Barcelona)
Tel. +34 9-02 19 40 36
Fax +34 9-02 19 40 35
E-Mail: info@geze.es
India
GEZE India Private Ltd.
MF2 & 3, Guindy Industrial Estate
Ekkattuthangal
Chennai - 600 097
Tamilnadu
Tel. +91 (0) 44 30 61 69 00
Fax +91 (0) 44 30 61 69 01
E-Mail: oce-india@geze.com
Italy
GEZE Italia Srl
Via Giotto, 4
20040 Cambiago (MI)
Tel. +3902950695-11
Fax +3902950695-33
E-Mail: italia.it@geze.com
Italy
GEZE Engineering Roma Srl
Via Lucrezia Romana, 91
00178 Roma
Tel. +3906-7265311
Fax +3906-72653136
E-Mail: roma@geze.biz
Kazakhstan
GEZE Central Asia
050061, Almaty, Kasakhstan
Rayimbek ave. 348, A, oce 310
Tel. +7 (0) 72 72 44 78 03
Fax +7 (0) 72 72 44 78 03
E-Mail: oce-kazakhstan@geze.com
Poland
GEZE Polska Sp.z o.o.
ul. Annopol 21
03-236 Warszawa
Tel. +48 (0)22 440 4 440
Fax +48 (0)22 440 4 400
E-Mail: geze.pl@geze.com
Romania
GEZE Romania S.R.L.
IRIDE Business Park
Building nr. 10, level 2
Str. Dimitrie Pompei nr. 9–9a
RO-020335 Bucharest, sector 2
Tel. +40 (0) 316 201 257
Fax +40 (0) 316 201 258
E-Mail: oce-romania@geze.com
Russian Federation
GEZE GmbH Representative
Oce Russia
Kolodesnij pereulok3, str. 25
Oce Nr. 5201-5203
107076 Moskau
Tel. +7 (0) 49 55 89 90 52
Fax +7 (0) 49 55 89 90 51
E-Mail: oce-russia@geze.com
Scandinavia
GEZE Scandinavia AB
Mallslingan 10
Box 7060
18711 Täby, Sweden
Tel. +46(0)8-7323-400
Fax +46(0)8-7323-499
E-Mail: sverige.se@geze.com
Scandinavia
GEZE Norway
Industriveien 34 B
2072 Dal
Tel. +47(0)639-57200
Fax +47(0)639-57173
E-Mail: norge.se@geze.com
Scandinavia
GEZE Finland
Postbox 20
15871 Hollola
Tel. +358(0)10-4005100
Fax +358(0)10-4005120
E-Mail: nland.se@geze.com
Scandinavia
GEZE Denmark
Mårkærvej 13 J-K
2630 Taastrup
Tel. +45(0)46-323324
Fax +45(0)46-323326
E-Mail: danmark.se@geze.com
South Africa
DCLSA Distributors (Pty.) Ltd.
118 Richards Drive, Midrand,
Halfway House Ext. 111
P.O. Box 7934
Midrand 1685
Tel. +27(0)113158286
Fax +27(0)113158261
E-Mail: info@dclsa.co.za
Switzerland
GEZE Schweiz AG
Bodenackerstrasse 79
4657 Dulliken
Tel. +41-(0)62-2855400
Fax +41-(0)62-2855401
E-Mail: schweiz.ch@geze.com
Turkey
GEZE GmbH Türkiye - İstanbul
İrtibat Bürosu
Ataşehir Bulvarı, Ata 2/3
Plaza Kat: 9 D: 84 Ataşehir
Kadıköy / İstanbul
Tel. + 90 (0) 21 64 55 43 15
Fax + 90 (0) 21 64 55 82 15
E-Mail: oce-turkey@geze.com
Ukraine
Repräsentanz GEZE Ukraine TOV
ul. Viskoznaya, 17, building 93-B,
oce 12
02094 Kiev
Tel. +38 (0) 44 501 22 25
Fax +38 (0) 44 499 77 25
E-Mail: oce-ukraine@geze.com
United Arab Emirates/GCC
GEZE Middle East
P.O. Box 17903
Jebel Ali Free Zone
Dubai
Tel. +971(0)4-8833112
Fax +971(0)4-8833240
E-Mail: geze@emirates.net.ae
United Kingdom
GEZE UK Ltd.
Blenheim Way
Fradley Park
Licheld
Staordshire WS13 8SY
Tel. +44(0)1543443000
Fax +44(0)1543443001
E-Mail: info.uk@geze.com
GEZE GmbH
P.O.Box 1363
Reinhold-Vöster-Straße 21–29
71229 Leonberg
Germany
Tel.: 0049 7152 203-0
Fax: 0049 7152 203-310
www.geze.com 143250-00
This manual suits for next models
2
Table of contents