GFS 790 000 User manual

Assembly Instruction
GfS Door Terminal
Safety on doors
Part No.: 790 000
Part No.:

GfS Door Teminal Part No.: 790 000
2790000_Ai_GfS-Door_Terminal_1112_GB
The GfS Door Terminal is a compact device to steer up to
2 holding magnets which are mounted on emergency exit
doors. It includes emergency exit switch, flash light, buzz-
er and key switch. The housing is made out of solid stain-
less steel.
In order to make full use of all GfS Door Terminal features
and to assure the safety of the operator it is important to
act according to the following instructions.
Before connecting and operating the device please
read the operating manual carefully.
• Theeletricinstallationmustbeexecutedbyan
authorized installer
• Beforeopeningthedevicetheexternalpowersupply
has to be switched-o
• Incaseofsystemfailurepleasedisconectthedevice
and ask an authorized installer to repair it
• Pleaseusethedevicejustaccordingtothefollowing
instruction
This assembly instruction should be handed on to
the operator
INDROTUCTION/SAFETY INSTRUCTION INSTALLATION
IMPORTANT:
Connect the GfS Door Terminal completely before
applying voltage.
• MounttheGfSDoorTerminalonthewallwiththe
enclosed screws (see hole pattern). You can find the
dierent measures on page 4)
• Connectallrequiredcables
• Tightenthescrewsoftheemergencyexitbutton
insertion (positioned horizontally)
• TightenthescrewsofthecoveroftheLED-eld
(positioned vertically)
• Now,applythevoltage
• Carryoutfunctiontest
ATTENTION
GfS recommends to checks the functions of the
GfS Door Terminal every 6 months.
Weitergabe oder Vervielfältigung dieser Bedienungsanleitung, Verwer-
tung und Mitteilung ihres Inhalts sind nicht gestattet, soweit nicht
ausdrücklich zugestanden. Zuwiderhandlungen verpflichten zu Schadener-
satz. Alle Rechte für den Fall der Patenterteilung oder Gebrauchsmuster-
Eintragungvorbehalten.
Die Angaben in dieser Bedienungsanleitung können ohne vorherige
Ankündigung geändert werden. Die Zusammenstellung der Informationen
in dieser Bedienungsanleitung erfolgt nach bestem Wissen und Gewis-
sen. GfS – Gesellschaft für Sicherheitstechnik mbH übernimmt keine
Gewährleistung für die Richtigkeit und Vollständigkeit der gemachten An-
gaben. Insbesondere kann GfS – Gesellschaft für Sicherheitstechnik mbH
nicht für Folgeschäden aufgrund fehlerhafter oder unvollständiger Anga-
ben haftbar gemacht werden. Da sich Fehler, bei aller Sorgfalt nie vermei-
denlassen,sindwirfürHinweisejederzeitdankbar.
1200
850
Escape direction

Part No.: 790 000 GfS Door Teminal
3
790000_Ai_GfS-Door_Terminal_1112_GB
TECHNICAL DATA
Power supply 12V-24VDC
Consumption State of activation 365 mA
(1 holding magnet)
State of alarm 150 mA
Degree of protection IP 20
Output 1 incident message relay
Max. contact load DC 30V/0,5A
Operating temperature -20Cbis+60C
Dimensions 90 x 240 x 80 mm
Weight ca. 1,6 kg
• 2x32LED(red/green)fordisplayingtheactualstatus
• integratedbuzzerwith100dB/1m
• integratedashlight
• emergencyexitswitchacc.toEN60947-5-1
• integratedkeyswitch
• 2mmthick,robuststainlesssteelhousing
• integratedcontrolunit
• reusablecoverforemergencyexitswitchmade
outofMacrolon
Input
• 12-24V/DCsupply
• 1xsingleremoteopening
• 1xpermanentremoteopening
• 2xholdingmagnetsignals
• 1xdoor-too-long-openalarm
• 1xintrusion-alarm(orbridge),clampsbriged=door
closed
• 2xsabotagealarm
• 2xpredenedbrightnessesofLED
• 1xrealarmcontrolsystem(withbridgenormal
operation)
• 1xemergencyexitswitchwithinternalfailsafe
contacts
• 1xreserveinput
Output
• 2xholdingmagnet(electricescaperoutestrikes)
• 1xRS-485interface(bi-directional,halfduplex)for
integration into building control systems
• 1xexternalsirène24V,0,5AOC
• 1xexternalashlight24V,0,5AOC
• 1xincidentmessagerelay(collectivemessage)
30 V, 0,5 A
Conformity
Thisproductcomplieswiththeessentialrequirementsof
theR&TTEguideline1999/5/EG.Thecerticateof
conformityyoumayrequestfromyoursupplier.
Disposal
Dispose an obselet GfS Door Terminal at a a colleting
point for electronic waste or at your supplier. Dispose
the packaging material at a paper collecting point for
paper resp. plastic. You may not dispose an obsolte
device the general garbage.
Warrenty
Within the legal warrenty time we intend to repair all
defect devices, whether the defect is caused by the
material or assembly, or replace them. The warenty
expires after a third-party repair.
Service
In case of a system failure or a defect GfS Door Terminal
please contact the following address:

GfS Door Teminal Part No.: 790 000
4790000_Ai_GfS-Door_Terminal_1112_GB
DIMENSION
240
198
10 72
90
42
20
60
80
80
15
50
41.98

Part No.: 790 000 GfS Door Teminal
5
790000_Ai_GfS-Door_Terminal_1112_GB
TERMINAL DIAGRAM
Pos Abb. Function Signal
1GND Operatingvoltageminus Ground
2 +24V Operatingvoltageplus +24V
3 FACS Fire alarm control system Floating contact or bridge to 4
4FACS Fire alarm control system Floating contact or bridge to 3
5 NO1 Response magnet 1 Groundisswitched,holdingmagnet1isenergized(HallRelayNO)
6 NO2 Response magnet 2 Groundisswitched,holdingmagnet2isenergized(HallRelayNO).
In case that there is just 1 magnet, 6 and 7 must be bridged!
7GND CommonGNDMagnets GND-Signal(HallRelaisCOM)
8Magnet- Magnet-Coil1and2 Negative connection for magnets
9Magnet+ Magnet+Coil1and2 Positive connection for magnets
10 GND Reference for remote opening Signal ground
11 REM Remote opening input Switch-on GNDresp.bridge10and11Openingcommand
12 GND Reference contact for door contact Signal GND
13 DC Contact Switch-on GND resp. bridge 12 and 13. Door closed
14 RS-485A Communication Data signals
15 RS-485B Communication Data signals
16 DST Communicationmultifunctionport Acc.totherequiredfunctionsasinputoroutput,alsousableforcommunication
purposes with 1 wire
17 COM IncidentmessagerelayCOM Floating contact 30 V/0,5 A max
18 NC IncidentmessagerelayNC Floating contact 30 V/0,5 A max
19 NO Incident message relay Floating contact 30 V/0,5 A max
20 ext. flash Externalashlight Opencollector-output,30V/0,5Amax
21 ext. sir. Externalsiren Opencollector-output,30V/0,5Amax
22 GND Reference for reserve and dim input Signal GND
23 Res1 Reserve input Free function
24 Dim Dim input Switch-on GND resp. bridge 24 with 22. Dim command
1
GND
2
+24V
3
FACS
4
FACS
5
NO1
6
NO2
7
GND
8
Mag–
9
Mag+
20
Dim
21
Res 1
22
GND
23
ext. sir.
24
ext. flash
10
GND
11
REM
12
GND
13
DC
14
RS485-A
15
RS485-B
16
DST
17
COM
18
NC
19
NO
12 V – 24 V
+

GfS Door Teminal Part No.: 790 000
6790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Alarm secured
LED ring with cross shines red
Incident message relay is activated, emergency exit switch
is illuminated, magnet is activated, door contact closed
(DCconnected)aswellasmagnet1and2.
red
Opening time delay
Attheendoftheopeningtimedelay(5sec.preset,adjustable)
the green LEDs blink slowly twice
and the GfS Door Terminal is activated again.
Precondition: Holding magnet and door contact are closed.
When the door is opened during the opening time delay and
no opening contact active, the status changes directly into
“Waiting for door too be closed”
green
Opening command 1
Turn key switch to the right.
LED ring with corners blink green.
Magnetisdeactivated,thedoormaybeopenedoncewithout
causing an alarm. green
Opening command 2
Input “Remote” activated.
OpeningcommandremainsactiveaslongastheGfSDoorTerminal
receives the signal plus opening time delay. green

Part No.: 790 000 GfS Door Teminal
7
790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Permanent opening
Permanent opening is active as long as Input “Remote” is activated.
Permanent opening with key switch: Turn key switch clockwise for
atleast5sec.,tillLEDsexpire.Removekey.
LEDs and emergency exit switch illumination are pulsing.
Door may be opened as long and as often as desired.
Magnetsarepermanentlydeactivated.
pulse
green
Waiting for door to be closed
The LEDs blink slowly green
at the end of the opening time.
In case that the holding magnet and door contact are not closed the
LEDs blink green for another 15 sec
(till conditions for activation are met).
blinks slowly
green
Door-too-long-open
If the door stays open for more than 15 sec. an alarm
“Door-too-long-open” is triggered.
Every 3 secs the green LEDs change for 200 ms into red,
while the internal and external buzzers are activated.
Deactivation of alarm
Closedoor(doorreedcontact,counterplate)orgiveagainan
opening command (opening command 1 and 2 possible)
Intermitting
red/greenLEDs
+buzzer
Emergency exit switch alarm
Push emergency exit switch
Flash-light, buzzer (internal and external) are activated, deactivation
of incident message relay, magnets are seperated and deactivated
by the processor.
LEDs blink quickly green (as after opening command).
Resetofalarmjustpossiblewithkeyswitch.Unlatchemergency
exit switch.
blinks green
+siren
+ashlight

GfS Door Teminal Part No.: 790 000
8790000_Ai_GfS-Door_Terminal_1112_GB
FUNCTIONS
Fire alarm
In case of a central fire alarm clamp 3 and 4 are seperated, the
failure relay is deactivated. Holding magnets are seperated and
deactivated by the processor.
LEDs blink quickly green (like open). The emergency exit
switch illumination blinks in push-pull.
The deactivation of the alarm only with key switch (turn right)
possible.
blinks green
Intrusion, sabotage
In case that one of the two feedback loops of the holding magnets
or door contacts are interrupted, an intrusion alarm is triggered.
LEDs change from red to orange.
The incident message relay is deactivated, the external siren is
activated.
The magnet stays active!
Resetjustpossiblewithkeyswitch(turnright).
IncasethatthePCBisremoved(sabotageontheGfSDoor
Terminal) he same alarm is triggered.
orange
+siren

Part No.: 790 000 GfS Door Teminal
9
790000_Ai_GfS-Door_Terminal_1112_GB
PROGRAMMING
Programming
1Turn key switch to the right (create status open)
2Hold key switch left at least for 5 sec. till orange ring shines
3Turn key switch to the left, release
4Turn briefly key switch to the left. Repeat this in order to enter other programming modes
5Turn key switch to the right in order to confirm the correct programming mode
6Turn key switch to the right in order to change the status/ value
7Turn key switch to the left in order to store the value and finish programming mode
Programming mode
1Open time delay 2Silent alarm 3Accoustic alarm switch-o
orange orange orange
1x 1x 1x
Change opening time
Executeprogrammingsteps1-3
Orange LED ring shines. Programming mode: opening time.
Start programming – execute step 5 (turn to the right)
(Conrmprogrammingmodebyturningkeytotheleft)
Orange LED ring changes to red
1greenLEDmeans5sec.openingtime.Byturningthekeyswitch
to the right the opening time increases each time by additional 3
sec.
1 turns to the right: 8 sec
2 turns to the right: 11 sec
8 turns to the right: 29 sec
Each turn leads to 1 more LED to shine green (max. 8).
9 turns to the right: 5 sec
Whentherequiredopeningtimedelayisset,turnkeyswitchbriey
to the left (step 7 – end programming mode)
The LEDs blink quickly 4 times.
The new values are set. In case of a power break down, the
opening time remains stored.
1LEDgreen=5sec
rot
rot
2LEDsgreen=11sec
1x
1x
store/ leave programm

GfS Door Teminal Part No.: 790 000
10 790000_Ai_GfS-Door_Terminal_1112_GB
PROGRAMMING
Silent alarm
Executeprogrammingsteps1-3
Executestep4once.(turntotheleft)
The LED cross shines orange.
Executeprogrammingstep5(turntotheright).
Orange cross changes into green
(sirènewillbetriggeredincaseofanalarm)
Executeprogrammingstep6onceinordertochangetosilent
alarm (turn to the right).
The LED cross shines red.
With any further execution of programming step 6 the setting
changes from green/accustic alarm to red/silent alarm.
Executeprogrammingstep7inordertoendtheprogramming.
orange green
on
red
o
1x 1x
1x
store/leave programm
Automatic accoustic alarm switch-o
Executeprogrammingstep1-3.
Executestep4twice(turntotheright).
Two orange half circles shine.
Executestep5(turntotheright).
Two half circles shine green.
Executestep6once(turntotheright).
LED half circles shine red.
Siren is automatically switched-o after 3 min.
With any further execution of programming step 6 the setting
changes from green/no automatic alarm switch-o to red/automatic
alarm switch-o.
Executeprogrammingstep7inordertoendtheprogramming.
orange red
3 min
green
permanent
alarm
1x 1x
1x
store/leave programm

Part No.: 790 000 GfS Door Teminal
11
790000_Ai_GfS-Door_Terminal_1112_GB
SPARE PARTS
European Cylinder Part No.
for insertion into GfS Door Terminal,
incl. 2 keys
901 375
2 replacement keys 901 376
Replacement cover for flash-light Part No.
for the flash-light of the GfS Door
Terminal, red
799 000
Replacement cover for emergency exit switch Part No.
for emergency exit switch of the GfS
Door Terminal made out of unbrakeable
Macrolon,transparent
799 001
Pictos Part No.
for marking the use of the emergency exit switch
Regularprintquality,
adhesive
921 390
Pictos Part No.
for marking the use of the emergency exit switch
fluorescent,
adhesive
921 490

GfS – Gesellschaft für Sicherheitstechnik mbH
Tempowerkring 15 · 21079 Hamburg · Fon 0 40-79 01 95 0 · Fax 0 40-79 01 95 11 · [email protected] · www.gfs-online.com
Stamp
790000_Ai_GfS-Door_Terminal_1112_GB
Table of contents
Popular Touch Terminal manuals by other brands

POSIFLEX
POSIFLEX XT-5515: XT-5515Pro user manual

Wodaplug
Wodaplug WDS600-104GH-R220 EPON ONU user manual

Beijer Electronics
Beijer Electronics X2 base 10 v2 Hardware and installation manual

EBN Technology
EBN Technology EZPPC70-2B-C1G Service manual

Bilanciai
Bilanciai DD1010 Use, maintenance and installation manual

Unitech
Unitech Tashi MT380 Proximity Quick reference guide