Metering systeMs
Thermal energy meTering kiT wiTh remoTe energy
consumpTion display
ge552y192 - ge552y193 - ge500y308 - ge500y309 - ge500y310
ISO
14001
0032A/3
OHSAS
18001
0064L/1
ISO
9001
0006/7
GE500Y308 CALCULATOR UNIT
Description
Electronic unit for calculating the thermal energy in heating and cooling
systems and volumes of hot and cold sanitary water measured.
The calculator unit is equipped with separate sections, so simultaneous
calculations of the following can take place:
• thermal energy in a heating circuit;
• thermal energy in a cooling circuit;
• volume of sanitary cold water measured;
• volume of sanitary hot water measured;
The GE500Y308 unit is equipped with an “M-Bus” row interface and a “Bus-
locale” row interact which allow the user to check consumption whilst
remaining inside the apartment, using the GE500Y309.
Technical data
• Power supply: battery
• Nominal battery voltage: 3,6V
• Type of battery: Lithium-thionyl chloride
• Battery format: pre-packaged pack (2xAA – 4,8Ah capacity)
• Battery life: 10 + 1 years
• Ambient operating temperature: 5÷55 °C
• Transport/storage temperature: -20÷55 °C
• Protection degree: IP52
• Approval: 2004/22/CE MID (B+D-type exam), certification no. CH-
MI004-13017
• Environmental class: A (E1, M1)
• Maximum power: 33000 kW with impulse weight <100
330000 kW with impulse weight <100
• Temperature measuring range: 2÷150 °C (Θmin=2 °C Θ max=150 °C)
• Temperature difference: 3÷148 °C (ΔΘmin=3 °C ΔΘmax=148 °C)
• Heating/cooling switchover: according to the temperature difference
recorded between the probes (ΔΘ); however, no energy metering takes place
for -3 °C <ΔΘ <+3 °C
• Display characteristics: liquid crystal with 8 digits, 19 ideograms and 2
additional digits
• Energy measuring unit on LCD: MWh (standard), configurable in kWh, MJ and GJ
• Dynamic behavior: temperature measurements are taken at each pulse of the
volume gauge with a resolution of 30 seconds, provided that the time between
pulses is greater than or equal to 30 seconds. If the time between pulses is
less than 30 seconds, measurements are carried out every 30 seconds. In the
absence of pulses, the temperature measurement is updated every 60 minutes.
In temperature display menu, the measurement is updated every 10 seconds.
• Type of probe: thermo-resistive Pt500
• Max length of probe cables: 2,5 m (standard), configurable to 5 m and 10 m
• Probe cable type: unshielded
• Effective current value of probe: < 72 μA (measured every 30 seconds)
• Impulse inputs: 2 for heating/cooling circuit volumes
2 for sanitary water volumes
• Impulse inputs class: IB (in accordance with EN 1434-2)
• Impulse inputs circuit type: pull-up of 1 MΩ with mass reference (GND
terminal), voltage +3,6 V
• Impulse input compatibility: gauges with output impulse class OA (reed
output) and OC (open-collector)
• Max frequency/Min. impulse duration: 5 Hz - 100 ms
• Gauge installation side: return (standard), configurable on the supply
• Impulse weight: 1 / - 2,5 / – 10 / – 25 / – 100 / – 250 / – 1000 - 2500 liters/impulse
• Heating fluid: water (standard), configurable for water and glycol solutions
• M-BUS communication interface: complies with EN 1434-3 with galvanic isolation
• M-BUS communication speed: 2400 Baud (standard), also configurable to
300 or 9600 Baud
•
Type of cable for connection to M-Bus: telephonic cable J-Y(ST) Y2 x 2 x 0,8 mm
2
• Bus locale interface: complies with EN 13757-6, 2400 Baud, single-direction
proprietary protocol compatible with GE500Y309 display unit
• Type of cable for connection to Bus locale: 2 bight x 0,6 mm2- max length 50 m
• Billing registration period: 12 months fixed, 2 periods with programmable
dates (DD/MM)
• Recording faults/alarms: circular log of 4 events (event type and date-time)
• Other recording: max. flow rate of heating fluid and max. power
• Type of connections: 18-pole extractable terminal board, 5 mm width
• MID approval certicate: CH-MI004-13017
Installation
Open the calculator unit by using the two side hooks to remove the upper
part with the electronic section.
Replace the electronic unit carefully in its packaging.
Remove the bracket from the terminal board base and secure it to the wall;
fix the terminal board base onto the bracket and secure it with the "anti-
tamper" kit (screw and O-Ring) provided. The seals provided must be affixed
to the calculator unit after installation and initial start-up.
NB:
For electrical connections please refer to product instructions.
Dimensions
A C
B
Product code A [mm] B [mm] C [mm]
GE500Y308 141 78 47