GITER G2500-48 User manual

INSTALLATION MANUAL
BATTERY MODULE
G2500-48
G2500-24
Version:V5.0
Giter Co., Ltd.
T+86 512 6828 7609
W www.giter-ess.com
808-812, Building 10A, Zilang Science and Technology City, 60 Chongzhou Avenue,
Economic and Technological Development Zone, Nantong,Jiangsu Province, 226006

Copyright Statement CONTENT
This manual is under the copyright of GITER Co., Ltd, with all rights reserved. Please keep the
manual properly and operate in strict accordance with all safety and operating instructions in this
manual. Please do not operate the system before reading through the manual.
Version Information
Version Date Content
V1.0 20201110 New
V2.0 20210406 Update line sequence
V3.0 20210623 Modify Dial code
V4.0 20210706 Modify Parts List
V5.0 20220119 update connection diagram
1. Introduction
1.1 General Precaution
2. Installation
2.1 Parts List
2.2 GTE Battery
2.3 Limitation of Liability
2.4 Installation of the Battery
2.4.1 Installation Site and Environment
2.4.2 Unpacking the Box
2.4.3 Installation and Wiring
3. System Operation
3.1 Switch On/off
4. Maintenance and Fault Handling
4.1 Routine Maintenance
4.2 Other Faults and Abnormal Phenomena
4.2.1 Unable to Turn On
4.2.2 Shut Down Immediately After Turn On
4.2.3 Unable to Charge
4.2.4 Unable to Discharge
4.2.5 No Communication Between Battery and Upper Controller (if Any)
4.2.6 Unable to Turn off
4.2.7 Outer Light is Always on
5. Appendix
5.1 Specification
02
02
02
02
02
06
06
06
06
07
11
11
12
12
12
12
12
12
13
13
13
14
14
14

GTE Battery
1. It is strictly prohibited to put the battery into water or in fire, so as to avoid explosion or other
danger and to endanger personal safety;
2. Please connect the wires correctly during the installation. Do not connect the positive pole
to the negative ones. Do not connect lithium batteries in series;
3. Do not prick the battery with a needle, strike the battery with hammer or harm it in any other
means;
4. Before installing or removing the system, ensure that the power is off and that the battery
system is turned off.
5. When it encounters a fire, please inform the fire department immediately and use lithium
battery fire ex-tinguishers that meet the national requirements to put out the fire.
6.If the battery is improperly lifted or dropped while being removed during transportation, it can
cause injury.
7. Do not disassemble any part of the system without permission of the company or the
technical personnel authorized by the company, in order to prevent danger or injury to your
safety.The system the equipment failure caused thereby is not covered in the warranty.
With standard operation, no electrolyte shall leak from the battery pack and no toxic gases
shall form. Despite careful construction, it is possible that electrolyte may leak and toxic gases
may form if the battery pack is damaged or there is a fault occurs.
Do not install the system in any environment where temperature below -10°C or over 50°C
and in which humidity is over 85%.
Do not touch the system with wet hands.
Do not put any heavy objects on top of the system.
Do not damage the system with sharp objects.
Do not install or operate the system in potentially explosive atmospheres or
areas of high humidity.
Do not mount the inverter and the battery pack in areas containing highly
flammable materials or gases.
If moisture has penetrated the system (e.g. due to a damaged enclosure),
do not install or operate the system.
Do not move the system when it is already connected with battery modules.
Secure the system to prevent tipping with restraining straps in your vehicle.
The transportation of GTE battery must be made by the manufacturer or by instructed
personnel instructed per-sonal. The transportation process shall be recorded..
Certified novec 1230, FM-200, or carbon dioxide fire extinguisher with a min-imum capacity of
2kg must be carried during transportation.
Don't smoking Smoking is prohibited in the process of loading and unloading, as well as
approaching the vehicle.
If you want to replace the battery module, please pack it according to new packaging,
dan-gerous goods and packaging suppliers to receive it.
If you have made contact with the electrolyte, flush the affected area with clean water
immediately and consult your doctor immediately.
CAUTION
WARNING
01 02
1. Introduction
1.1 General Precaution
2.1 Parts List
2.2 GTE Battery
2.2.1 Dimensions and Specifications
2. Installation
Check the following parts list and make sure there is no part missing.
GITER delivers a complete system including:
Outer hexagonal and
internal torx triad
screw M5*10(X2)
Outer hexagonal and
internal torx triad
screw M5*10(X2)
Hexagon lobular
socket countersunk
head screws M4*8
(X10)
M6*12Cross
recessed pan head
triad screws(x4)
Communication
cable (x1)
M6 Buckle nut
(X4)
Hangers
(X2) User manual
Battery (X1)

03 04
2.2.2 Interface 2.2.2 Error and Protection Code
2.2.1 LED SOC Display
In normal condition, LED light indicates the SOC (State of Charge) as the figure below:
Figure 1 G2500-48 Interface
Item Description Item Description
1
2
3
4
5
6
7
8
Earthing point(with screws) (x2)
Communication Port
DIP Switch
LED SOC Display
Power Switch
Battery Circuit Breaker
Positive port
Negative port
LED Light Protection Code LED Display Description
1
2
3
4
5
6
7
8
Temperature difference
High temperature
Over-current charge
Over-current discharge
Cell over voltage
Cell under voltage
1
1
2 3 456
7 8
LED Light
State
Standby:
Green light flashes every
1s
Work:
Green light flashes every
10s
Green light
flashes every 3
seconds.
LED Light SOC Description
SOC<5%
5%≤SOC<25%
25%≤SOC<50%
50%≤SOC<75%
75%≤SOC<95%
SOC≥95%
Charging in low-temperature
environment
Discharging in low-temperature
environment
When the alarm code appears, the battery is still in normal working mode. When the elements
triggering the alarm are removed, the battery will automatically resume working.
In the working mode, if the alarm code 09 appears, the power button can be pressed 5 times within
10 seconds, and the BMS will force the MOS to close. At this time, the inverter can detect the battery
and charge the battery.

05 06
Error Code: 2.3 Limitation of Liability
2.4 Installation of the Battery
2.4.1 Installation Site and Environment
2.4.2 Unpacking the Box
LED Light Error Code Description Troubleshooting
Red light
flashes every
3 seconds.
Error 01
Error 05
Error 07
Error 08
Error 09
Error 10
Error 11
Error 12
Error 13
Any product damage or property loss caused by the following conditions Giter does not assume any
direct or indirect liability.
Product modified, design changed or parts replaced without Giter authorization;
Changes, or attempted repairs and erasing of series number by non Giter technician;
System design and installation are not in compliance with local standards and regulations;
The product has been improperly stored in dealer’s or end user’s premises;
Transport damage (including painting scratch caused by movement inside packaging during the
shipping). A claim should be made directly to shipping or insurance company as soon as the
container/packaging is unloaded and such damage is identified;
Failure to follow any/all of the user manual, the installation guide and the maintenance
regulations;
Improper use or misuse of the device;
Insufficient ventilation of the device;
The maintenance procedures relating to the product have not been followed to an acceptable
standard;
Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.).
Damages caused by any external factors.
LED Display
Temperature
sen-sor failure
DIP switch
mode difference
SN missing
BMS disconnect
(master)
Software version
inconsistent
MOSFET over
temperature
Multi master
Multi master
MOSFET error
Please restart the
battery.
If the problem is not
resolved, please
contact GITER after
sales team.
Please keep
consistence of DIP
switches then restart
the system.
Please reconnect the
communi-cation
cable.
Please contact
GITER after sales
team.
Please Reconnect
the commu-nication
cable.
Please contact Giter
after sales team.
After shutting down
the battery system,
please restart all
batter-ies within 30s.
Please turn off the
battery and turn on
the battery after
about 2 hours.
This manual describes the basic steps of how to install and set up.
Take out the battery from the packing box and check whether the accessories are complete, as
shown in Figure 2.
The following location are not allowed for installation:
• sites with high humidity, or where there is condensation;
• sites which are salty and where humid air can penetrate;
• flooded areas.
• earthquake areas –additional security measures are required here;
• sites with explosive atmosphere;
• sites with direct sunlight;
• sites with extreme change of ambient temperature;
• sites with highly flammable materials or gases;
• sites with a potentially explosive atmosphere.

Note
Figure 2 Unpacking the Battery
Figure 4 Install battery module & connect copper bar
(Take G2500-48 as an example)
Figure 5 Communication cable connection & DIP Switch
(Take G2500-48 as an example)
07 08
2.4.3 Installation and Wiring
The following actions should be carried out before wiring:
1. Ensure that the power button of all batteries is OFF;
2. Cut off all relevant power supply. Step 2: As shown in Figure 4, put the battery into the cabinet, tighten the four-angle screws
(M6*12 cross head triad screw, torque: 5 N.m); and fix the copper strip between the battery
modules with 3#cross screwdriver (M8; torque: 12 N.m).
Step 1: As shown in Figure 3, fix the hanging ear on both sides of the battery with 4 internal
Torx flat cup screws respectively.(Torque: 1.6 N.m; Tools: T20 internal torx screwdriver ).
1、Serial connection between batteries is not allowed;
2、The power line of the cross-sectional areaconnected to the inverter should be at least 35
mm2(About AWG 2), and temperature resistance ≥105°, pressure resistance (DC) ≥500V.
Fix the screws for
the copper bar
Fix the screws for
the hanging ear
INV-
INV COM
DIP Switch
INV+
WEON
1 2 3 4
WEON
1 2 3 4
WEON
1 2 3 4
WEON
1 2 3 4
WEON
1 2 3 4

09 10
2.4.3.2 Installation with Base
(Accessories need to be purchased separately)
The sequence is specific to the Voltronic inverters only.
Step 1: As shown in Figure 7, place the battery on the base and tighten limit brackets located at
the four corners (screw: M4*10 outer hexagonal and internal torx combination screw; torque: 1.6
N.m; 10pcs in total )
Step 2: As shown in Figure 7, stack the second battery neatly on the first one and tighten the
limit brackets with a T20 screwdriver(screw: M4*10 external hexagonal box Combination screw ;
torque requirement: 1.6 N.m; 10pcs ).
Step3: Refer to Step 2 and stack the battery in turn, as shown in Figure 9。
As shown in figure 5, connect the communication cable, and dial code after connection. Switch '2'
and '4' for the top battery. Switch '1','2' and ‘4’ for the bottom battery,and '4' for all other batteries.
Note
DIP Switch of battery should be set as below
Only one Bat: More than two Bats:
PS: The top battery communicates with the inverter
The communication wiring between the battery and the inverter has a special sequence.The
requirements of communication wiring connection are shown in Figure 6.
Note
A bracket (including a left bracket and a right bracket) is used for each 2 batteries
Figure 7 Install the first battery
Figure 8 Install the second battery
Figure 9 Stack and install 6 batteries
(Take G2500-48 as an example)
Left bracket
Right bracket
Voltronic Inverter
RJ45 connector
CN1
GITER BAT
RJ45 connector
CN2
1
2
BI
BI/W BI/W
BI
Or/W
Br/W
Br
Or
G/W
G
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Figure 6 Communication wiring
DIP 1 DIP 2 DIP 3 DIP 4
OFFON ONONOne BAT
WEON
1 2 3 4
Battery
position
DIP
Switch
DIP 1 DIP 2 DIP 3 DIP 4
OFFOFF
OFF OFF OFF
OFFON ON
ON ON
ON
ON
The TOP
The MID
The
BOTTOM
WEON
1 2 3 4
WEON
1 2 3 4
WEON
1 2 3 4
Battery
position
DIP
Switch

11 12
3. System Operation
4. Maintenance and Fault Handling
3.1 Switch On/Off
4.1 Routine Maintenance
4.2 Other Faults and Abnormal Phenomena
4.2.1 Unable to Turn on
Check all power cables and communication cables carefully.
Common faults and corresponding troubleshooting are listed below.
START: Switch off the Battery Breaker, press the Power Switch (Rebound button) to "ON" for 1-2
seconds. Then the battery module will activate and the LED display will light up.
CLOSE: Press the Power Switch (Rebound button) to "ON" for 5 seconds, and the bat-tery will be
turned off.
Batteries should be turned on in the correct order to avoid damage
• Check if the environment situation the requirements of the battery.
• Check whether the charging and discharging function of the battery is normal. When one of the
following situations happen, it is necessary to charge the battery in time: the battery alarm code
09 appears, the battery is often under charged, and the battery is stored for more than 3 months.
• Check the battery and its appearance, terminals, cables, LED lights, etc.
Fault Troubleshooting Description
Press the Power switch
to "ON" for 2 seconds
and then let go. The
LED is not light up
within 3 seconds.
Check if there is
resistance when you
press the switch button.
If the button has no
resistance, please
con-tact customer service.
4.2.3 Unable to Charge
Fault Troubleshooting Description
The battery is not fully
charged, and no alarm
code or error code appears
in LED display, but the
battery cannot be charged
normally.
1.Confirm the battery has
been turned on.
2.Check if the power cables
are connected correctly;
3.Check if the battery Breaker
is off;
4.Check if the ambient
temperature is within the
operating range.
If the battery still cannot
be charged normally after
these steps, please
contact customer service.
4.2.2 Shut Down Immediately After Turning on
Fault Troubleshooting Description
Press the Power switch to
"ON" state for 2 seconds and
then let go. The LED lights up
for 8 seconds and goes off.
Confirm whether the
switch can bounce back.
If the button cannot
bounce back, please
contact customer service.
2.4.3.3 Communication Connection Diagrams

5.1 Specification
13
4.2.4 Unable to Discharge
Fault Troubleshooting Description
The battery has energy
stored and LED has no
alarm code or error code,
but the batterycannot be
discharged normally.
1. Confirm if the battery has been
turned on;
2. Check if power cables are
connected correctly;
3. Check if the battery Breaker is
off;
4. Check if the ambient
temperature is within the
operating range;
5. Disconnect the power ca-bles
and test the battery output
voltage. If the voltage is too low,
please charge immediately. If
there is no voltage, please
contact customer service. If the
voltage is normal, you can restart
the battery.
If the battery still cannot
be discharged normally
after these steps, please
contact customer service.
4.2.5 No Communication Between Battery and Upper Controller (if Any)
Fault Troubleshooting Description
Upper controller failed to
detect the batteries
1. Confirm if the battery has been
turned on;
2. Check if the power cables are
connected correctly;
3. Check if the communication
cables are connected correctly
and whether they are damaged;
4. Check whether the DIP switch
2 of the battery which is from the
upper controller is set to "ON";
5. Restart the batteries.
If the battery still cannot
be used normally after
following the steps, please
contact customer service.
14
4.2.6 Unable to Turn off
Fault Troubleshooting Description
Press the Power switch to
"ON" state for 5 seconds
and let go. The LED
display does not go off.
1. Confirm whether there is
resistance when the button is
pressed;
2. Confirm whether the outer
light is always on.
If the button has no
resistance or outer ring is
always on, please contact
customer service.
4.2.7 Outer Light is Always on
5. Appendix
Fault
Items G2500-48 G2500-24
Troubleshooting Description
The LED outer light is
always on and the status
light is off.
1. Press the “Power” switch
for more than 5 seconds to
observe the status of the LED
outer light.
If the LED still keeps on
after the steps, please
contact customer service
Nominal Voltage
Nominal charge/discharge current
Charging limit voltage
Discharge limit voltage
Nominal Capacity
Usable Capacity
DoD
Max. Number in parallel per cabinet
Communication Interface
IP Protection
Weight
Operating temperature range
Certification
51.2V
25A(0.5C)
57.6V
48V
25.6V
50A(0.5C)
28.8V
24V
2.56KWh
2.43KWh
95%
6pcs
RS485/CAN
IP21
27kg
0℃~50℃* (Charge) -10℃~50℃* (Discharge)
UN38.3
*When the temperature is below 0℃or above 40℃, the performance will be limited.
Other manuals for G2500-48
1
This manual suits for next models
1
Table of contents
Other GITER Control Unit manuals
Popular Control Unit manuals by other brands

Beta LaserMike
Beta LaserMike LASERSPEED 8000 Instruction handbook

Fleck
Fleck 7700 Service manual

ICP DAS USA
ICP DAS USA XP-8000-Atom-CE6 quick start guide

Axion
Axion 40 Series user manual

Betts
Betts ES22PP-AABN Installation and maintenance manual

Allen-Bradley
Allen-Bradley 1792-IB16 Series B installation instructions