Global Fire Equipment J-NET-SP User manual

INSTALLATION
Juno-Net Sub-Panels allow expansion of the system in groups of either 1, 2 or 3 loops. When
supplied in an enclosed cabinet with independent primary and secondary power supplies up to
9 Loops may be installed in each cabinet which also contains a 5A PSU/Charger unit and space
for standby rechargeable batteries. One RS422/RS485, Fibre Optic orTCP/IP interface is required
per cabinet to enable networking with the rest of the system.
Each sub-panel board controls up to 3 Analogue Addressable Detection Loops via its own
independent processor. In the event of communications failure with the main control unit, the
sub panel is capable of operating independently, detecting Fire/Fault events and activating its
own sounders, relays and I/O devices.
J-NET-SP STAND ALONE
*J-NET-SP-003-SA
ORDER CODE
TECHNICAL SPECIFICATIONS
DESCRIPTION
LOOPS
SOUNDER OUTPUTS/ sub-panel
AUX. RELAYS FIRE/ sub-panel
AUX. RELAY FAULT/ sub-panel
AUX POWER OUTPUT
ADDITIONAL OUTPUTS
PRIMARY SUPPLY
SECONDARY SUPPLY
POWER SUPPLY RATING
QUIESCENT CURRENT (NO DEVICES)
BATTERIES (INTERNAL)
DIMENSIONS
WEIGHT (NO BATTERIES)
OPERATING TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY/ PROTECTION
J-NET-SP
J-NET-SP-001-SA
J-NET-SP-002-SA
J-NET-SP-003-SA
Sub-Panel Board w/o Loop Card
Sub-Panel Board w/ 1 Loop
Sub-Panel Board w/ 2 Loops
Sub-Panel Board w/ 3 Loops
1, 2 or 3 loops - max 275 mA/ Loop
2 at 28V DC / 500 mA each
2 rated 50 VAC / DC 1A resistive
1 rated 50 VAC / DC 1A resistive
28V DC 300 mA
N/A
N/A
28 V DC Nominal
N/A
90 mA
2 x 12V 12 AH
L: 113 W: 180 H: 26 mm
0,3 Kg
0ºC to +40ºC
-10 to +50ºC
N/A
ORDER CODE
TECHNICAL SPECIFICATIONS
DESCRIPTION
LOOPS
SOUNDER OUTPUTS/ sub-panel
AUX. RELAYS FIRE/ sub-panel
AUX. RELAY FAULT/ sub-panel
AUX POWER OUTPUT
ADDITIONAL OUTPUTS
PRIMARY SUPPLY
SECONDARY SUPPLY
POWER SUPPLY RATING
QUIESCENT CURRENT (NO DEVICES)
BATTERIES (INTERNAL)
DIMENSIONS
WEIGHT (NO BATTERIES)
OPERATING TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY/ PROTECTION
J-NET-SPX (BOXED) 1 TO 9 LOOPS
*J-NET-SPX-009
1 to 9 loops - max 275 mA per loop
4/6/8 24V DC / 500 mA each
2 rated 50 VAC / DC 1A resistive
1 rated 50 VAC / DC 1A resistive
28V DC 300mA
N/A
85 - 265 V AC, 50/60Hz
28 V DC Nominal
150W
90 mA/sub-panel
2 x 12V 12 AH
H: 375 W: 345 D: 139 mm
5,1 Kg (no batteries)
0ºC to +40ºC
-10 to +50ºC
Max. 85% no condensation / IP21
9 Loops - 5.4A PSU
8 Loops - 5.4A PSU
7 Loops - 5.4A PSU
6 Loops - 5.4A PSU
5 Loops - 5.4A PSU
4 Loops - 5.4A PSU
3 Loops - 5.4A PSU
2 Loop - 5.4A PSU
1 Loop - 5.4A PSU
J-NET-SPX-009
J-NET-SPX-008
J-NET-SPX-007
J-NET-SPX-006
J-NET-SPX-005
J-NET-SPX-004
J-NET-SPX-003
J-NET-SPX-002
J-NET-SPX-001
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

67
15
2348
Conventional
Sounder Circuits
1 & 2
Monitored - OC and SC
Auxiliary
Supply Output
Rated 28V DC @ 0.4A
Monitored
Power Supply Input
28.5V DC Nominal
Battery Supply
2 x 12V Lead-Acid Batteries
Auxiliary Relay Outputs
Aux 1 - FIRE - Changeover
Aux 2 - FIRE - Changeover
Fault - Normally Closed
Non-monitored
Loop
Connections
1
2
3
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
PANEL NO.|A B|U
PROCESSOR
Loop Card
Connectors
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
Loop Card
1-3 Loop(s)
Loop Card
Stand-offs (4)
FS2
Battery Fuse
3A-Slow Blow
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Use switches 1 through 5 to set sub-panel’s address this should always be set in the range 1 to 32.
Please note that when Juno Net Sub-Panel is connected to Juno Net Panel using J-NET-CON-SP1
the lowest address that can be used is 2 and not 1. The reason being that J-NET-CON-SP1 will
always occupy sub-panel address 1.
Address Setting
Switch 1 ON = 1
Switch 2 ON = 2
Switch 3 ON = 4
Switch 4 ON = 8
Switch 5 ON = 16
Address 0 should never be used.
Please note that there is an offset of 1 between sub-panel dil switch address and panel no. as
shown by the Juno Net Main Panel. e.g. if a Sub-Panel is programmed with address 1 it will
identified by the Main Panel as Panel No. 02.
DIL SWITCH FUNCTIONS
SUB-PANEL ADDRESS
PROTOCOL SELECTION
Switch8
Set to ON when firmware upgrade for
Sub-Panel is required. Revert to OFF
position when operation is complete.
PANEL UP/ DOWNLOAD
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
67
15
2348
PA N E L N O. | A B | U
67
15
2348
PA N E L N O. | A B | U
ON
OFF
8
ON
OFF
NORMAL
U
6 6
7 7
ON ON
OFF OFF
NORMAL NORMAL
A B A B
6 6
7 7
ON ON
OFF OFF
EXTENDED EXTENDED
A B A B
6 6
7 7
ON ON
OFF OFF
WIZMART ZEOS
A B A B
6 6
7 7
ON ON
OFF OFF
GFE GFE
A B A B
Panels with
versions 3.09
or lower
Panels with
versions 3.09 B2
or higher
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Data Loop Interface
Connector
SUB-PANELS
self-contained
67
15
2348
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
PANEL NO.|A B|U
J-NET-INT-485
J-NET-INT-FO
J-NET-INT-TCP-IP
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016
NEUTRO
FASE
1A
F
U
S
E
5A POWER SUPPLY UNIT
MEANWELL
MODEL: LPP-150-27
INPUT: 85-264VAC ; 120-370VDC
OUTPUT: +27V 5.6A
47/63Hz
DANGER
220 VOLTS
J-NET RS 485 INT.
RS 485 OUT RS 485 IN
A AA AB BB B
TX 1 RX 1RX 2 TX 2
MAIN PANEL
SUB PANEL or
REPEATERS
J1 & J2 OFF
J2
J1
J1 & J2 ON
1 2 3 4 5 6
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V24V 28V 28VMON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PA N E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
1
1 2 3 4 5 6
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V
24V 28V 28V
MON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PAN E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
3
123456
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V
24V 28V 28V
MON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PAN E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
2
J-NET-SP with LOOP-CARD J-NET-SP with LOOP-CARD
J-NET-SP with LOOP-CARD
J-NET-RS485-INT-NEW
MAX 3A FAST ACTING
MAX 3A FAST ACTING
MAX 3A FAST ACTING
67
15
2348
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
- +
LOOP 1
RETURN
- +
LOOP 2
RETURN
- +
LOOP 3
RETURN
- +
LOOP 2
OUT
- +
LOOP 3
OUT
- +
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
PANEL NO.|A B|U
180 mm
113 mm
OVERALL DIMENSIONS (mm)

Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: [email protected] • Technical Support: techs@globalfire.pt • www.globalfire.pt
This manual suits for next models
12
Table of contents
Popular Computer Hardware manuals by other brands

Samsung
Samsung S3F80JB user manual

Universal Scientific Industrial Co., Ltd.
Universal Scientific Industrial Co., Ltd. MP-B-IP-00 user guide

Renesas
Renesas e1 user manual

Trinnov Audio
Trinnov Audio magnitude 32 user guide

2E
2E 2E-AC120D6-ARGB Operation guide

Lava
Lava ISA Bus Bi-Directional Parallel Port Board datasheet