Global Fire Equipment J-NET-SP User manual

INSTALLATION
Juno-Net Sub-Panels allow expansion of the system in groups of either 1, 2 or 3 loops. When
supplied in an enclosed cabinet with independent primary and secondary power supplies up to
9 Loops may be installed in each cabinet which also contains a 5A PSU/Charger unit and space
for standby rechargeable batteries. One RS422/RS485, Fibre Optic orTCP/IP interface is required
per cabinet to enable networking with the rest of the system.
Each sub-panel board controls up to 3 Analogue Addressable Detection Loops via its own
independent processor. In the event of communications failure with the main control unit, the
sub panel is capable of operating independently, detecting Fire/Fault events and activating its
own sounders, relays and I/O devices.
J-NET-SP STAND ALONE
*J-NET-SP-003-SA
ORDER CODE
TECHNICAL SPECIFICATIONS
DESCRIPTION
LOOPS
SOUNDER OUTPUTS/ sub-panel
AUX. RELAYS FIRE/ sub-panel
AUX. RELAY FAULT/ sub-panel
AUX POWER OUTPUT
ADDITIONAL OUTPUTS
PRIMARY SUPPLY
SECONDARY SUPPLY
POWER SUPPLY RATING
QUIESCENT CURRENT (NO DEVICES)
BATTERIES (INTERNAL)
DIMENSIONS
WEIGHT (NO BATTERIES)
OPERATING TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY/ PROTECTION
J-NET-SP
J-NET-SP-001-SA
J-NET-SP-002-SA
J-NET-SP-003-SA
Sub-Panel Board w/o Loop Card
Sub-Panel Board w/ 1 Loop
Sub-Panel Board w/ 2 Loops
Sub-Panel Board w/ 3 Loops
1, 2 or 3 loops - max 275 mA/ Loop
2 at 28V DC / 500 mA each
2 rated 50 VAC / DC 1A resistive
1 rated 50 VAC / DC 1A resistive
28V DC 300 mA
N/A
N/A
28 V DC Nominal
N/A
90 mA
2 x 12V 12 AH
L: 113 W: 180 H: 26 mm
0,3 Kg
0ºC to +40ºC
-10 to +50ºC
N/A
ORDER CODE
TECHNICAL SPECIFICATIONS
DESCRIPTION
LOOPS
SOUNDER OUTPUTS/ sub-panel
AUX. RELAYS FIRE/ sub-panel
AUX. RELAY FAULT/ sub-panel
AUX POWER OUTPUT
ADDITIONAL OUTPUTS
PRIMARY SUPPLY
SECONDARY SUPPLY
POWER SUPPLY RATING
QUIESCENT CURRENT (NO DEVICES)
BATTERIES (INTERNAL)
DIMENSIONS
WEIGHT (NO BATTERIES)
OPERATING TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY/ PROTECTION
J-NET-SPX (BOXED) 1 TO 9 LOOPS
*J-NET-SPX-009
1 to 9 loops - max 275 mA per loop
4/6/8 24V DC / 500 mA each
2 rated 50 VAC / DC 1A resistive
1 rated 50 VAC / DC 1A resistive
28V DC 300mA
N/A
85 - 265 V AC, 50/60Hz
28 V DC Nominal
150W
90 mA/sub-panel
2 x 12V 12 AH
H: 375 W: 345 D: 139 mm
5,1 Kg (no batteries)
0ºC to +40ºC
-10 to +50ºC
Max. 85% no condensation / IP21
9 Loops - 5.4A PSU
8 Loops - 5.4A PSU
7 Loops - 5.4A PSU
6 Loops - 5.4A PSU
5 Loops - 5.4A PSU
4 Loops - 5.4A PSU
3 Loops - 5.4A PSU
2 Loop - 5.4A PSU
1 Loop - 5.4A PSU
J-NET-SPX-009
J-NET-SPX-008
J-NET-SPX-007
J-NET-SPX-006
J-NET-SPX-005
J-NET-SPX-004
J-NET-SPX-003
J-NET-SPX-002
J-NET-SPX-001
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

67
15
2348
Conventional
Sounder Circuits
1 & 2
Monitored - OC and SC
Auxiliary
Supply Output
Rated 28V DC @ 0.4A
Monitored
Power Supply Input
28.5V DC Nominal
Battery Supply
2 x 12V Lead-Acid Batteries
Auxiliary Relay Outputs
Aux 1 - FIRE - Changeover
Aux 2 - FIRE - Changeover
Fault - Normally Closed
Non-monitored
Loop
Connections
1
2
3
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
PANEL NO.|A B|U
PROCESSOR
Loop Card
Connectors
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
Loop Card
1-3 Loop(s)
Loop Card
Stand-offs (4)
FS2
Battery Fuse
3A-Slow Blow
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Use switches 1 through 5 to set sub-panel’s address this should always be set in the range 1 to 32.
Please note that when Juno Net Sub-Panel is connected to Juno Net Panel using J-NET-CON-SP1
the lowest address that can be used is 2 and not 1. The reason being that J-NET-CON-SP1 will
always occupy sub-panel address 1.
Address Setting
Switch 1 ON = 1
Switch 2 ON = 2
Switch 3 ON = 4
Switch 4 ON = 8
Switch 5 ON = 16
Address 0 should never be used.
Please note that there is an offset of 1 between sub-panel dil switch address and panel no. as
shown by the Juno Net Main Panel. e.g. if a Sub-Panel is programmed with address 1 it will
identified by the Main Panel as Panel No. 02.
DIL SWITCH FUNCTIONS
SUB-PANEL ADDRESS
PROTOCOL SELECTION
Switch8
Set to ON when firmware upgrade for
Sub-Panel is required. Revert to OFF
position when operation is complete.
PANEL UP/ DOWNLOAD
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
67
15
2348
PA N E L N O. | A B | U
67
15
2348
PA N E L N O. | A B | U
ON
OFF
8
ON
OFF
NORMAL
U
6 6
7 7
ON ON
OFF OFF
NORMAL NORMAL
A B A B
6 6
7 7
ON ON
OFF OFF
EXTENDED EXTENDED
A B A B
6 6
7 7
ON ON
OFF OFF
WIZMART ZEOS
A B A B
6 6
7 7
ON ON
OFF OFF
GFE GFE
A B A B
Panels with
versions 3.09
or lower
Panels with
versions 3.09 B2
or higher
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Data Loop Interface
Connector
SUB-PANELS
self-contained
67
15
2348
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
+ -
LOOP 1
RETURN
+ -
LOOP 2
RETURN
+ -
LOOP 3
RETURN
+ -
LOOP 2
OUT
+ -
LOOP 3
OUT
+ -
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
PANEL NO.|A B|U
J-NET-INT-485
J-NET-INT-FO
J-NET-INT-TCP-IP
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016

Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016
NEUTRO
FASE
1A
F
U
S
E
5A POWER SUPPLY UNIT
MEANWELL
MODEL: LPP-150-27
INPUT: 85-264VAC ; 120-370VDC
OUTPUT: +27V 5.6A
47/63Hz
DANGER
220 VOLTS
J-NET RS 485 INT.
RS 485 OUT RS 485 IN
A AA AB BB B
TX 1 RX 1RX 2 TX 2
MAIN PANEL
SUB PANEL or
REPEATERS
J1 & J2 OFF
J2
J1
J1 & J2 ON
1 2 3 4 5 6
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V24V 28V 28VMON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PA N E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
1
1 2 3 4 5 6
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V
24V 28V 28V
MON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PAN E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
3
123456
ON
SNDR 1 SNDR 2
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
AUX PS POWER SUPPLY IN
0V 0V 0V
24V 28V 28V
MON
ETH
BATT
24V EVAC
COMMSOK
COMMSFLT
PRE-ALARM
FAULT
5VOLT FAULT
FIRE
PAN E L NO
SILENCE A
CN4
MPX
CN5
CN3
H8/3003
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
311
100
50
272
4R7
35
SUB-PANEL
2
J-NET-SP with LOOP-CARD J-NET-SP with LOOP-CARD
J-NET-SP with LOOP-CARD
J-NET-RS485-INT-NEW
MAX 3A FAST ACTING
MAX 3A FAST ACTING
MAX 3A FAST ACTING
67
15
2348
PROCESSOR
24V 0V
POWER
28V 28V
SUPPLY IN
+ -
24V
BATT
+ -
24V
BATT
AUX 2 AUX 1
FAULT
NO NC C NO NC C
Data Loop Interface
Connectors
CN3 CN4
COMMS OK
COMMS FLT
PRE-ALARM
FAULT
5 VOLT FAULT
FIRE
LOOP 1
OUT
- +
LOOP 1
RETURN
- +
LOOP 2
RETURN
- +
LOOP 3
RETURN
- +
LOOP 2
OUT
- +
LOOP 3
OUT
- +
SNDR 2
- +
SNDR 1
- +
ETH
Sub-Panel rev 3.0
02/2008
SILENCE
FS2
Battery Fuse
3A-Slow Blow
PANEL NO.|A B|U
180 mm
113 mm
OVERALL DIMENSIONS (mm)

Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION MANUAL - V. 12/2016
JUNO-NET SUB PANEL
globalfire.pt
Manufacturers of Fire Detection Equipment
JUNO-NET SUB PANEL INSTALLATION MANUAL - V. 12/2016
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: [email protected] • Technical Support: techs@globalfire.pt • www.globalfire.pt
This manual suits for next models
12