3 Settings
There are three parameters to set in the
heating system:
-the heating curve,
-the maximum flow heating temperature,
-the correction of the outdoor
temperature.
It is important that all the settings are made
on all the component parts of the heating
system:
-the Systempro control unit,
-the Climapro2RF programmable room
thermostat,
-the boiler.
iThe outdoor sensor sends data
on the outside temperature to
the room thermostat (via the
radio receiver) or the control
unit every 10 minutes.
iShould the connection to the
outdoor sensor be interrupted,
the regulation of the system will
be modified after a period of 7
days.
The Systempro control unit will
make modifications according
to an outside temperature
reading of 0 ºC (default).
The room thermostat will make
modifications without taking
into account the outdoor
temperature reading.
3.1 Adjustment of the heating curve
Choose the curve(value adjustable between
0.2 and 4), which allows you to obtain the
maximum heating flow temperature for the
usual minimum outdoor temperature for the
region in which the sensor is installed.
iComment: The lower the heat
loss of the house, the lower the
value of the heat curve required:
[0.2 - 0.6] highly insulated
modern house with low
temperature radiators or
underfloor heating,
[≈1.5] standard/modern house
with radiators,
[2.5 - 4] older properties with
radiators.
3.2 Setting the maximum flow heating
temperature.
This function, available on the control unit
and on the boiler, enables the maximum
heating output temperature to be set (value
adjustable between 30 °C
and 80 °C).
• Consult the instruction manuals of the
control unit and the boiler.
3.3 Outdoor temperature correction
This function, available on the control unit
and on the room thermostat, enables the
temperature measured by the outdoor
sensor to be corrected (+/- 5 °C at 1 °C
intervals).
• Consult the Climapro2RF instruction
manual.