7221793A
Lighting the Boiler (45/2 and 56/2 ONLY)
Thisapplianceisfittedwith aflue blockagesafety devicewhich
will shut down the appliance in the event of abnormal flue
conditions.ThisdeviceisNOTasubstituteforanindependently
mounted Carbon Monoxide detector. If the boiler shuts down
frequentlyfor no apparent reason the firstthings to be checked
are the chimney and air inlets into the room.
An additional cause of the flue blockage safety device shutting
thefiredowncouldbethatthefilterinthepilotportofthegastap
has become blocked.
Any problems found must be put right, by a competent person,
before the boiler is used again.
The boiler controls are placed behind the fire front plinth.
To remove the plinth, pull it gently forwards until it is free, see
diagram 3.
Refer to diagram 4b to identify the controls.
Turn off the electrical supply at the mains supply outside the
unit.
Check that all controls are calling for heat.
The clock, room thermostat and programmer, if fitted, will be
remotefromthe appliance, refer to manufacturer’s instructions
supplied with them.
Turn the thermostat control knob “B” to Off position "O", that is,
fully anticlockwise, “O” to be against the pointer.
Pushinandslightlyturngascontrolknob“A”clockwiseuntil' 'is
against its setting point, that is, set to “Off”.
Pushinslightlyandturngascontrolknob“A”anticlockwiseuntil
''isagainstitssettingpoint,thenpushfully inandholdin. At
the same time press and release piezo button “D” until pilot
burner “E” lights. Look at flame through viewing window “F”.
At initial lighting of the boiler air may be present and several
attempts may be needed to light the pilot. Keep the control
knob “A” pushed in whilst operating the ignition button.
When the pilot is alight and stable, keep knob “A” fully pushed
inforabout15secondsthenrelease. Checkthatthepilot isstill
alight, look through window “F”.
If the pilot burner fails to stay alight turn gas control knob “A”
“Off”, that is, fully clockwise. Wait three minutes. Repeat the
lighting operation, only now keep the control knob “A” pushed
in for a little longer than before after the pilot has lit.
NOTE: If the burner does go out, wait three minutes before
relighting. For any other reason, wait two minutes before
relighting the burner.
Push control knob “A” in slightly and turn anticlockwise until
'' is against the setting point.
Note. If gas control knob “A” is turned until ' ' is against the
settingpoint,asafetylockpreventsitbeingturnedonagain. No
attemptshould bemade to turnthe valve onagain untilatleast
three minutes have elapsed.
Turn on the electrical supply to the unit.
Turn the boiler thermostat knob “B” clockwise until “MAX” is
against the setting point, the main burner will light.
Adjust the thermostat to the required setting between “MIN”
and “MAX”. “MAX” is about 82oC (180oF).
Check that all external controls are set to your requirements.
Refit the plinth by carefully locating the top edge of the plinth
into the sliders, then push gently back as far as it will go.
To Turn the Boiler Off
Forshortperiods,turnthermostatcontrolknob“B”anticlockwise
until “O” is against setting point. The pilot will stay alight, to
relight the main burner, turn thermostat control knob “B”
clockwise to the desired setting between “MIN” and “MAX”.
For longer periods, push in slightly gas control knob “A” fully
clockwiseuntil' 'isagainstthesettingpoint. Turnthermostat
control knob “B” anticlockwise to “O”. Switch off the electrical
supply the appliance. To relight follow full lighting operation.
SETTING
POINT
'F' VIEWING
WINDOW
'E' PILOT BURNER
SETTING
POINT
OFF
PILOT/IGNITION
MAIN BURNER
'A'
GAS VALVE
CONTROL KNOB
'D' PIEZO
UNIT BUTTON
'B'
THERMOSTAT
CONTROL KNOB
BBUs 45/2 and 56/2 ONLY Diagram 4b
7997
Instructions for Use