GMI D5014S User manual

D5014 - SIL 3 Repeater Power Supply G.M. International ISM0103-8
SIL 3 Repeater Power Supply
Hart, DIN-Rail and Termination Board,
Models D5014S, D5014D
D5014S - D5014D
INSTRUCTION MANUAL

2 D5014 - SIL 3 Repeater Power Supply G.M. International ISM0103-8
General Description: The single and dual channel Repeater Power Supply, D5014S and D5014D module is a high integrity analog input interface suitable for applications
requiring SIL 3 level (according to IEC 61508:2010 Ed.2) in safety related systems for high risk industries. Provides a fully floating dc supply for energizing conventional
2 wires 4-20 mA, active or passive, transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load.
The circuit allows bi-directional communication signals, for Hart transmitters.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I,
Division 2 or Class I, Zone 2.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
Technical Data
Characteristics
Supply: 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits 5 Vpp, 2 A time lag fuse internally protected.
Current consumption @ 24 V: 90 mA for 2 channels D5014D, 45 mA for 1 channel D5014S with 20 mA output typical.
Power dissipation: 1.35 W for 2 channels D5014D, 0.675 W for 1 channel D5014S with 24 V supply voltage and 20 mA output typical.
Isolation (Test Voltage): I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
Input: 4 to 20 mA (separately powered input, voltage drop 0.5 V) or 4 to 20 mA (2 wires Tx current limited at 25 mA), reading range 0 to 24 mA.
Transmitter line voltage: 15.0 V typical at 20 mA with max. 20 mVrms ripple on 0.5 to 2.5 KHz frequency band, 14.5 V minimum.
Output: 4 to 20 mA, on max. 550 load in source mode (typical 12 V compliance);
V min. 8 V at 0 load V max. 30 V in sink mode, current limited at 25 mA or
1 to 5 V on internal 250 shunt (or 2 to 10 V on internal 500 shunt on request).
Response time: 5 ms (0 to 100 % step change).
Output ripple: 20 mVrms on 250 communication load on 0.5 to 2.5 KHz band.
Frequency response: 0.5 to 2.5 KHz bidirectional within 3 dB (Hart protocol).
Performance: Ref. Conditions 24 V supply, 250 load, 23 ± 1 °C ambient temperature.
Calibration accuracy: ± 0.1 % of full scale.
Linearity error: ± 0.05 % of full scale.
Supply voltage influence: ± 0.02 % of full scale for a min to max supply change.
Load influence: ± 0.02 % of full scale for a 0 to 100 % load resistance change.
Temperature influence: ± 0.01 % of full scale on zero and span for a 1 °C change.
Compatibility:
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
ATEX: II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
IECEx / INMETRO / NEPSI: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I
UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nA [ia Ga] IIC T4 Gc
C-UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nA [ia Ga] IIC T4 Gc
FM: NI-AIS / I / 2 / ABCD / T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / AEx nA [ia] / IIC / T4
FMC: NI-AIS / I / 2 / ABCD / T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / Ex nA [ia] / IIC / T4
EAC-EX: 2ExnA[ia]IICT4 X
UKR TR n. 898: 2ExnAiaIICT4 X, ExiaI X
associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10.
Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 8-11, 10-12.
Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 0 nF, Li = 0 nH at terminals 8-11, 10-12.
Um = 250 Vrms, -40 °C Ta 70 °C.
Approvals:
BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26.
UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15, ANSI/ISA 12.12.01 for UL
and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL.
FM 3046304 and FMC 3046304C conforms to Class 3600, 3610, 3810, 3611,
ANSI/ISA-60079-0, ANSI/ISA-60079-11, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.157, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-11, C22.2 No. 60079-15.
C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.10, 30852.14.
C16.0036 X conforms to 7113, 22782.5-78, I 60079-15.
GYJ14.1406X conforms to GB3836.1, GB3836.4; GB3836.8, GB3836.20.
TC21005 for TIIS approval.
TÜV Certificate No. C-IS-236198-04, SIL 2 / SIL 3 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV No.A-13625 and KR No. MIL20769-EL002 Certificates for maritime applications.
Mounting:
T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board.
Weight: about 155 g D5014D, 130 g D5014S.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location: installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4.
Protection class: IP 20.
Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
FSM
SIL 3

3
D5014 - SIL 3 Repeater Power SupplyG.M. International ISM0103-8
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed.2 for Tproof = 1 / 10 yrs (10% / >10 % of total SIF).
SIL 2 according to IEC 61508:2010 Ed.2 for Tproof = 14 / 20 yrs (10% / >10 % of total SIF).
PFDavg (1 year) 6.69 E-05, SFF 90.47 %.
Systematic capability SIL 3
2 fully independent channels.
Input from Zone 0 (Zone 20), installation in Zone 2.
4-20 mA Input / Output Signal Active-Passive / Source-Sink
Hart compatible.
Input and Output short circuit proof.
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM, FMC, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TIIS, TÜV Certifications.
Type Approval Certificate DNV and KR for maritime applications.
TUV Functional Safety Certification.
High Density, two channels per unit.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Input Ch 1 for 2 wires Transmitters
Terminal block connections
HAZARDOUS AREA SAFE AREA
- Input Ch 1 for 2 wires Transmitters or
+ Input Ch 1 for External Powered Transmitters
+ Input Ch 2 for 2 wires Transmitters
- Input Ch 2 for 2 wires Transmitters or
+ Input Ch 2 for External Powered Transmitters
- Input Ch 1 for External Powered Transmitters
- Input Ch 2 for External Powered Transmitters
7
8
9
10
11
12
+ Output Ch 1
1
- Output Ch 1
2
+ Output Ch 2
3
- Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
7 8
9 10
11 12
2 1
4 3
6 5
Model: D5014
1 channel S
2 channels D
Power Bus and DIN-Rail accessories:
Connector JDFT049 Cover and fix MCHP196
Terminal block male MOR017 Terminal block female MOR022
11
D5014
12
9 10
7 8
1 2
3 4
5 6
SIL 3
2
1
PWR
PWR

4 D5014 - SIL 3 Repeater Power Supply G.M. International ISM0103-8
Parameters Table
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D5014 Associated
Apparatus Parameters
Must
be
Hazardous Area/
Hazardous Locations
Device + Cable Parameters
Uo / Voc = 25.9 V
Ui / Vmax
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5014 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device,
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the
effective group. See parameters indicated in the table below:
D5014 Terminals
Ch1
Ch2
7 - 8
9 - 10
Uo / Voc = 1.1 V
Ch1
Ch2
8 - 11
10 - 12
Io / Isc = 92 mA
Ch1
Ch2
7 - 8
9 - 10
Io / Isc = 56 mA
Ch1
Ch2
8 - 11
10 - 12
Po / Po = 594 mW
Ch1
Ch2
7 - 8
9 - 10
Po / Po = 16 mW
Ch1
Ch2
8 - 11
10 - 12
Ii/ Imax
Pi / Pi
D5014 Terminals
Ch1
Ch2
8 - 11
10 - 12
D5014 Associated Apparatus
Parameters Cenelec (US)
Ci / Ci device + C cable
IIC (A, B)
Co / Ca = 100 nF
Co / Ca = 770 nF
Co / Ca = 2.63 µF
IIB (C)
IIA (D)
IIC (A, B)
Co / Ca = 100 µF
Co / Ca = 1000 µF
Co / Ca = 1000 µF
IIB (C)
IIA (D)
Co / Ca = 4.02 µF
Co / Ca = 770 nF
I
IIIC (E, F, G)
I
Co / Ca = 1000 µF
Co / Ca = 1000 µF
Ch1
Ch2
7 - 8
9 - 10
Ch1
Ch2
8 - 11
10 - 12
Li / Li device + L cable
IIC (A, B)
Lo / La = 3 mH
Lo / La = 16.8 mH
Lo / La = 33.7 mH
IIB (C)
IIA (D)
IIC (A, B)
Lo / La = 11.3 mH
Lo / La = 45.3 mH
Lo / La = 90.7 mH
IIB (C)
IIA (D)
Lo / La = 55.2 mH
Lo / La = 16.8 mH
I
IIIC (E, F, G)
I
Lo / La = 151.1 mH
Lo / La = 45.3 mH
Ch1
Ch2
7 - 8
9 - 10
Ch1
Ch2
8 - 11
10 - 12
Li / Ri device and
L cable / R cable
IIC (A, B)
Lo / Ro = 59.9 µH/
Lo / Ro = 239.7 µH/
Lo / Ro = 479.4 µH/
IIB (C)
IIA (D)
IIC (A, B)
Lo / Ro = 2327.2 µH/
Lo / Ro = 9309 µH/IIB (C)
IIA (D)
Lo / Ro = 786.6 µH/
Lo / Ro = 239.7 µH/
I
IIIC (E, F, G)
I
IIIC (E, F, G)
Lo / Ro = 30545.4 µH/
Lo / Ro = 9309 µH/
Ch1
Ch2
7 - 8
9 - 10
Lo / Ro = 18618.1 µH/
IIIC (E, F, G)
IIIC (E, F, G)

5
D5014 - SIL 3 Repeater Power SupplyG.M. International ISM0103-8
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5014 Associated Apparatus are not exceeded by
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded (50 % of the Co and Lo become the limits which must include the cable such that
Ci device + C cable 50 % of Co and Li device + L cable 50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot).
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D5014 Associated
Apparatus Parameters
Ui / Vmax = 30 V Uo / Voc
D5014 Terminals
Ch1
Ch2
8 - 11
10 - 12
li / Imax = 128 mA
Ch1
Ch2
8 - 11
10 - 12
Io / Isc
Ci = 0 nF, Li= 0 nH
Ch1
Ch2
8 - 11
10 - 12
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4
==
=
5 +
6 -
1
2RLmA
+
-
HHT Source I
Out 1 (SIL 3)
3
4RLmA
+
-
Source I
Out 2 (SIL 3)
HHT
7
11
+
-
HHT
2 Wire Tx
I
?
+
-
External
Powered Tx
In 1
10
12
+
-
2 Wire Tx
+
-
External
Powered Tx
In 2
HHT
I
?
8
9
MODEL D5014D
+
-Termination
board
connector
Power Bus
==
=
=
=
=
=
Supply 24 Vdc
mA +
V
Source V Sink I
+
-
+
-
RL
mA +
V
Source V Sink I
+
-
+
-
RL
==
=
5 +
6 -
1
2RLmA
+
-
HHT Source I
Out (SIL 3)
Supply 24 Vdc
7
11
+
-
HHT
2 Wire Tx
I
?
+
-
External
Powered Tx
In
8
MODEL D5014S
=
=
+
-Termination
board
connector
Power Bus
mA +
V
Source V Sink I
+
-
+
-
RL

6 D5014 - SIL 3 Repeater Power Supply G.M. International ISM0103-8
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4
Connections for Duplication of 2 wires Transmitter Input
Restriction on specifications for 2 wires Transmitter Input:
Bidirectional communication for Smart Transmitter is provided only on channel 1
The minimum supply voltage available for Transmitter (Vtx) is 14 V at 20 mA input
The safety parameters must be changed in: Uo/Voc = 27 V, Io/Isc = 93 mA, Po/Po = 623 mW
Terminals 7-10
Uo/Voc = 27 V
Io/Isc = 93 mA
Po/Po = 623 mW
IIC
IIB
IIA
0.090
0.705
2.330
3
16.6
33.2
57.0
228.3
456.6
Group
Cenelec
Lo/Ro
(µH/)
Lo/La
(mH)
Co/Ca
(µF)
I
iaD
3.750
0.705
54.5
16.6
749.1
228.3
==
=
5 +
6 -
1
2RLmA
+
-
HHT Source I
Out 1 (SIL 3)
3
4RLmA
+
-
Source I
Out 2 (SIL 3)
7
11
10
12
8
9
MODEL D5014D Duplicator
+
-Termination
board
connector
Power Bus
==
=
=
=
=
=
Supply 24 Vdc
+
-
HHT
2 Wire Tx
I
?
In 1
mA +
V
Source V Sink I
+
-
+
-
RL
mA +
V
Source V Sink I
+
-
+
-
RL
Safety Description

7
D5014 - SIL 3 Repeater Power SupplyG.M. International ISM0103-8
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4
Terminals 8-12
Uo/Voc = 2.2 V
Io/Isc = 56 mA
Po/Po = 31 mW
Safety Description
IIC
IIB
IIA
100
1000
1000
11.3
45.3
90.7
1163.6
4654.5
9309
Group
Cenelec
Lo/Ro
(µH/)
Lo/La
(mH)
Co/Ca
(µF)
I
iaD
1000
1000
151.1
45.3
15272.7
4654.5
Connections for Duplication of Active Input Signal
Restriction on specifications for external powered Transmitter:
The safety parameters must be changed in: Uo/Voc = 2.2 V, Io/Isc = 56 mA, Po/Po = 31 mW
==
=
5 +
6 -
1
2RLmA
+
-
Source I
3
4RLmA
+
-
Source I
7
11
10
12
8
9
MODEL D5014D Duplicator
+
-Termination
board
connector
Power Bus
==
=
=
=
=
=
Supply 24 Vdc
+
-
External
Powered Tx
In 1
Out 2 (SIL 3)
mA +
V
Source V Sink I
+
-
+
-
RL
mA +
V
Source V Sink I
+
-
+
-
RL
Out 1 (SIL 3)
Voltage drop 1.0 V

8 D5014 - SIL 3 Repeater Power Supply G.M. International ISM0103-8
D5014 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4,
Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb –40 to +70 °C, and connected to equipment with a maximum limit for
AC power supply Um of 250 Vrms.
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5014 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care
shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative.
Any unauthorized modification must be avoided.
Warning
Operation
D5014 provides fully floating DC supply for energizing 2 wires 4-20 mA transmitters, or separately powered 4 wires, 4-20 mA transmitters located in Hazardous Area,
and repeats and converts the current to a 4-20 mA or 1-5 V floating output signal to drive a Safe Area load.
The circuit allows bi-directional communication signal for smart transmitters, a “POWER ON” green led for each channel lits when input power is present.
Installation
D5014 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or
on customized Termination Board.
D5014 unit can be mounted with any orientation over the entire ambient temperature range.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without
suffering or causing any damage (for Zone 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
Identify the number of channels of the specific card (e.g. D5014S is a single channel model and D5014D is a dual channel model), the function and location of each connection terminal
using the wiring diagram on the corresponding section, as an example:
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”.
For Model D5014S connect positive output of channel 1 at terminal “1” and negative output at “2”.
For Model D5014D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”.
For Model D5014S, in case of a 2 wires Transmitter, connect the wires at terminal “7” for positive and “8” for negative.
For separately powered Transmitters connect input signal at terminal “8” for positive and “11” for negative.
For Model D5014D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2.
Connect input signal from separately powered Transmitters at terminals “10” for positive and “12” for negative on channel 2.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other
and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5014 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
According to EN61010, D5014 series must be connected to SELV or SELV-E supplies.
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking.
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green leds must be lit, for 2 wires transmitter
connection the supply voltage on each channel must be 14.5 V, output signal should be corresponding to the input from the transmitter. If possible change the transmitter output and
check the corresponding Safe Area output.

9
D5014 - SIL 3 Repeater Power SupplyG.M. International ISM0103-8
ON
D5014D
ON
D5014S
Configuration
Dip switch configuration
1234
ON
Ch1 4-20 mA
Source Mode
678
5
1234 678
5
1234 678
5
1234 678
5
Ch1 4-20 mA
Sink Mode
Ch2 4-20 mA
Source Mode
Ch2 4-20 mA
Sink Mode
Ch2 1-5 V
(on 250 ---
internal shunt)
Ch1 1-5 V
(on 250 ---
internal shunt)
ON ON OFF OFF
ON
ON ONON
OFF OFF OFF
OFF
ON ON OFF OFF
ON
ON ON
ON
OFF OFF OFF
OFF
Dip switch configuration
An output configuration DIP Switch is located on component side of pcb. This switch allows the mA (sink or source mode) or Volt operating mode configuration.
1234
ON
4-20 mA
Source Mode
1234
1234
1234
4-20 mA
Sink Mode
1-5 V (on 250 ---
internal shunt)
ON ON
ON
ONONON
OFF OFF
OFFOFFOFF
OFF
Source mode is factory settings
Only Source/Sink mode can be
used for SIL applications.
Source mode is factory settings
Only Source/Sink mode can be
used for SIL applications.
This manual suits for next models
1
Table of contents
Popular Touch Terminal manuals by other brands

Allen-Bradley
Allen-Bradley FLEX 5000 installation instructions

National Instruments
National Instruments NI TB-2633 installation instructions

Festo
Festo CPV GE ASI-4 Series Brief description

Mitsubishi Electric
Mitsubishi Electric GOT2000 Series Connection manual

Omron
Omron NXR-ILM08C-EIT manual

TrackSol
TrackSol Restaurant operating manual