NETIChome®
Double On/Off
Ordering code: NEWHAB1 Type: Double On/Off
Double On/Off module is part of NETIChome®system.
This module is used for switching On or Off two electrical devices (e.g.
lights, fans, etc ...). The module can be controlled either through wireless
network or through the wall switches.
The module is designed to be mounted inside a “flush mounting box”
and is hidden behind a traditional wall switch.
Module measures power consumption of two electrical devices and
supports connection of digital temperature sensor.
Supported switches
Module supports mono-stable switches (push button) and bi-stable
switches. The module is factory set to operate with bi-stable
switches.
Installation
Before the installation disconnect power supply.
Connect the module according to electrical diagram.
Locate the antenna far from metal elements (as far as possible).
Do not shorten the antenna.
Danger of electrocution!
Module installation requires a great degree of skill and may be
performed only by a qualified and licensed electrician.
Even when the module is turned off, voltage may be present on its
terminals. Any works on configuration changes related to
connectcon mode or load must be always performed by
disconnected power supply (disable the fuse).
Note
Do not connect the module to loads exceeding recommended values.
Connect the module only in accordance to the below diagrams. Improper
connections may be dangerous.
Package contens
Double On/Off
Electrical diagram 230VAC
Notes for the diagram:
Electrical diagram 24VDC
Notes for the diagram:
Durability of the device depends on applied load. For resistive load
(light bulbs, etc.) and 4A current consumption of each individual
electrical device, the durability exceeds 70 000 switches of each
individual electrical device.
Module Inclusion (Adding to wireless network)
Connect module to power supply,
bring module within maximum 1 meter (3 feet) of the NETIC,
enable add/remove mode on NETIC,
auto-inclusion (30 minutes after connected to power supply) or
press service button Sfor more than 1 second or
press push button I1 three times within 3s (3 times change
switch state within 3 seconds)
Module Exclusion/Reset (Removing from wireless
network)
Connect module to power supply
bring module within maximum 1 meter (3 feet) of the NETIC,
enable add/remove mode on NETIC,
press service button Sfor more than 5 second or
press push button I1 five times within 3s (5 times change
switch state within 3 seconds).
By this function all parameters of the module are set to default values
and own ID is deleted
Association
Association enables Double On/Off module to transfer commands inside
wireless network directly (without NETIC) to other NETIChome modules.
Associated Groups:
Group 1: basic on/off (triggered at change of the output Q1 state and
reflecting its state)
Group 2: basic on/off (triggered at change of the output Q1 state and
reflecting its state)
Group 3: default reporting group (reserved for the NETIC)
Configuration parameters
Parameter no. 1 –Input 1 switch type
Available configuration parameters:
default value 1
0 mono-stable switch type (push button)
1 bi-stable switch type
Parameter no. 2 –Input 2 contact type
Available configuration parameters:
default value 1
0 mono-stable switch type (push button)
1 bi-stable switch type
Parameter no. 10 - Activate / deactivate functions ALL ON/ALL OFF
Available configuration parameters:
default value 255
255 - ALL ON active, ALL OFF active.
0 - ALL ON is not active ALL OFF is not active
1 - ALL ON is not active ALL OFF active
2 - ALL ON active ALL OFF is not active
On/Off module responds to commands ALL ON / ALL OFF that may be
sent by the NETIC or by other controller belonging to the system.
Parameter no. 11 - Automatic turning Off relay Q1 after set time
Available configuration parameters:
Default value 0
0 - Auto OFF disabled
1- 65535 = 10mseconds –655,35 seconds Auto OFF enabled, with
define time, step is 10mseconds
Parameter no. 12 - Automatic turning Off relay Q2 after set time
Available configuration parameters:
Default value 0
0 - Auto OFF disabled
1- 65535 = 10mseconds –655,35 seconds Auto OFF enabled, with
define time, step is 10mseconds
Parameter no. 30 - Saving the state of the relays Q1 and Q2 after a
power failure
Available configuration parameters:
default value 0
0 –Double On/Off module saves its state before power failure
(it returns to the last position saved before a power failure)
1 - Double On/Off module does not save the state after a
power failure, it returns to "off" position.
Parameter no. 40 –Power reporting in Watts on power change for
Q1
Set value means percentage, set value from 0 –100 = 0% - 100%
Available configuration parameters:
default value 5
0 –Reporting Disabled
1 –100 = 1% - 100% Reporting enabled. Power report is send
(push) only when actual power in Watts in real time change for
more than set percentage comparing to previous actual power in
Watts, step is 1%.
NOTE: if power changed is less than 1W, the report is not send (pushed),
independent of percentage set.
Parameter no. 41 –Power reporting in Watts on power change for
Q2
Set value means percentage, set value from 0 –100 = 0% - 100%
Available configuration parameters:
default value 5
0 –Reporting Disabled
1 –100 = 1% - 100% Reporting enabled. Power report is send
N
+ 24VDC
L
- 24VDC
Q1
Output for electrical device no. 1
Q2
Output for electrical device no. 2
I2
Input for switch to control electrical device no. 2
I1
Input for switch to control electrical device no. 1
TS
Terminal for digital temperature sensor (only for
NETIChome compatible digital temperature sensor,
which must be ordered separately).
N
Neutral lead
L
Live lead
Q1
Output for electrical device no. 1
Q2
Output for electrical device no. 2
I2
Input for switch to control electrical device no. 2
I1
Input for switch to control electrical device no. 1
TS
Terminal for digital temperature sensor (only for
NETIChome compatible digital temperature
sensor, which must be ordered separately).
S
Service button (used to add or remove
module from the NETIChome system).
N
L
TS
I1 I2 Q2 Q1 LN
+
-
TS
I1 I2 Q2 Q1 LN
(push) only when actual power in Watts in real time change for
more than set percentage comparing to previous actual power
in Watts, step is 1%.
NOTE: if power changed is less than 1W, the report is not send (pushed),
independent of percentage set.
Parameter no. 42 –Power reporting in Watts by time interval for Q1
Set value means time interval (0 –65535) in seconds, when power
report is send.
Available configuration parameters:
default value 300 (power report in Watts is send each 300s)
0 –Reporting Disabled
1 –65535 = 1 second –65535 seconds. Reporting enabled, Power
report is send with time interval set by entered value.
Parameter no. 43 –Power reporting in Watts by time interval for Q2
Set value means time interval (0 –65535) in seconds, when power
report is send.
Available configuration parameters:
default value 300 (power report in Watts is send each 300s)
0 –Reporting Disabled
1 –65535 = 1 second –65535 seconds. Reporting enabled, Power
report is send with time interval set by entered value.
Technical Specifications
Power supply
110 - 230 VAC ±10% 50/60Hz,
24-30VDC
Rated load current of AC output
(resistive load)*
2 X 4A/ 230VAC
Rated load current of DC output
(resistive load)
2 X 4A/ 30VDC
Output circuit power of AC output
(resistive load)
2 X 920W (230VAC)
Output circuit power of DC output
(resistive load)
2 X 96W (24VDC)
Power measurement accuracy
P=0-200W, +/-2W
P˃200W, +/-3%
Frequency Range
868.42MHz
Digital temperature sensor range
(sensor must be ordered separately)
-50 ~ 125°C
Operation temperature
-10 ~ 40°C
Distance
up to 30 m indoors (depending on
building materials)
Dimensions (W x H x D)
41,8 x 36,8 x 16,9mm
Weight
25g
Electricity consumption
0,4W
For installation in boxes
Ø ≥ 60mm or 2M
Switching
Relay (2x)
*In case of load other than resistive, pay attention to the value of cos φ
and if necessary apply load lower than the rated load. Max current for
cos φ=0,4 is 2A at 250VAC.
Important disclaimer
Wireless communication is inherently not always 100% reliable, and as
such, this product should not be used in situations in which life and/or
valuables are solely dependent on its function.
Warning
Do not dispose of electrical appliances as unsorted municipal waste,
use separate collection facilities.
Contact your local government for information regarding the collection
systems available. If electrical appliances are disposed of in landfills or
dumps, hazardous substances can leak into the groundwater and get
into the food chain, damaging your health and well-being. When
replacing old appliances with new once, the retailer is legally obligated
to take back your old appliance for disposal at least for free of charge.
This user manual is subject to change and improvement without notice.
Goap d.o.o. Nova Gorica
Ulica Klementa Juga 007
5250 Solkan
Slovenia
E-mail: info@netichome.com
Tel: +386 5 335 95 00
Fax: +386 5 300 61 43
Web: www.netichome.com
Web: www.goap.eu
Partner
D
Date: 01.04.2014
Document: NETIChome_Double On/Off user
maual_V2.0_eng

Popular Control Unit manuals by other brands

Cognex In-Sight 1400 Installation and reference manual

Cognex

Cognex In-Sight 1400 Installation and reference manual

National Instruments NI PXIe-4138 Getting started guide

National Instruments

National Instruments NI PXIe-4138 Getting started guide

Vicoustic Super Bass 90 installation manual

Vicoustic

Vicoustic Super Bass 90 installation manual

Bosch RC 4001 Montage und Bedienungsanleitung

Bosch

Bosch RC 4001 Montage und Bedienungsanleitung

KraftPowercon PRX Series manual

KraftPowercon

KraftPowercon PRX Series manual

ICRealtime CONSOLE-5X user manual

ICRealtime

ICRealtime CONSOLE-5X user manual

SimCom SIM340 user manual

SimCom

SimCom SIM340 user manual

Oriental motor OPX-2A operating manual

Oriental motor

Oriental motor OPX-2A operating manual

Keyautomation CT-PAE Instructions and warnings for installation and use

Keyautomation

Keyautomation CT-PAE Instructions and warnings for installation and use

SimCom SIM7060 Series Application note

SimCom

SimCom SIM7060 Series Application note

Kieback&Peter RBW322-FTL-902 operating instructions

Kieback&Peter

Kieback&Peter RBW322-FTL-902 operating instructions

SimCom SIM7200 Hardware guide

SimCom

SimCom SIM7200 Hardware guide

Krom Schroder BCM 400 B2 Series operating instructions

Krom Schroder

Krom Schroder BCM 400 B2 Series operating instructions

1010music Fxbox 2.0 quick start guide

1010music

1010music Fxbox 2.0 quick start guide

Uni-Com UAC-01EC2 installation guide

Uni-Com

Uni-Com UAC-01EC2 installation guide

Paradox Digiplex EVO PRT3 Programming instructions

Paradox

Paradox Digiplex EVO PRT3 Programming instructions

Abus FUBE50000 Installation and operating instructions

Abus

Abus FUBE50000 Installation and operating instructions

Mark 06 29 192 Technical manual

Mark

Mark 06 29 192 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.