Indicator
display
S ta te In d ica to r d is p la y R e m ark:
H i g h -p re s s u re p r ote c ti o n Outdoor malfunction indicator 1 turns on indoor run
indicator blinks
Indoor Run indicator turn off 3s
and blinks once
Low-pressure protection
Outdoor malfunction indicator 3 turns
on, indicator run indicator blinks
Indoor Run indicator turn off 3s
and blink 3 times
Over current protection Outdoor malfunction indicator 2 turns on,
indoor run indicator blinks
Indoor indicator turn off 3s and
blinks five times
Communication malfunction Outdoor malfunction indicators 1,2,3 turn on,
indoor run indicator blinks
Indoor indicator turn off 3s and blink six times
Normal communication Outdoor indicator 4, 5 blink in turn
Air exhaust protection
(compressor over heat protection)
Outdoor malfunction indicator 1, 3 turn on,
indoor running indicator blinks
Indoor running indicator turn off 3s
and blink four times
low pressure protection.
sequence as: communication malfunction air exhaust protection over current protection high pressure protection
When there are several malfunctions existed at the same time, it will display the high level malfunction in priority by a
When unit is on, detect outdoor unit ambient sensor malfunction, when there is short circuit, open circuit, the indoor cooling indicator
turns off 3s and blink 3 times.
Communication malfunction
the unit will be stopped as the indoor ambient temperature has arrived the setting temperature .
When it is detected that the indoor and outdoor units have communication malfunction , the running indicator will blink,
Overcurrent protection
When the compressor is turned on, if it has detected that the current exceed the stated value, the unit will stop as the indoor ambient
temp. has arrived at the setting temp., after the compressor has stopped for 3mins, it will resume to run in the original running state,
if the protections is more than 6 times (If compressor has continuously work more than 6mins, the protection times will reset),
the running indicator will blink, it can not resume to run automatically, it is need to press ON/OFF button to turn off the unit,
then repress ON/OF button to resume to work.
Power off memory function
Memory contents: Mode, Swing, Preset temp., Preset fan speed.
After powered off, when repower on, the unit will memorize the contents and automatically turn on and run.
Anti-high temperature protection
Under the Heat mode, when detected the evaporator tube temp. is very high, the outdoor unit will stop to run; When evaporator tube temp.
resume to normal,the outdoor unit will resume to work.
System high-pressure protection
System low-pressure protection
When detecting high-pressure protection, will turn off all overloads, all buttons and remote control signal will be shielded
the running indicator will blink;If detected the compressor high-pressure protection released, the buttons and remote
control shield will be released, the running indicator is still blink, it is need to press the ON/OFF button to turn off the unit,
after the running indicator turns off, repress the ON/OFF button to resume to run.
Air exhaust tube high temperature protection
After compressor started up, continuously 30s detected air exhaust temperature is very high or air exhaust sensor malfunction, running indicator
blink. The unit will stop according to indoor ambient temperature meet the setting temperature. After compressor stopped 3mins later, if the air
exhaust temperature resuem to normal, that the whole unit will resume to run.
If the above protection phenomenon continuously happened twice, the whole unit can not resume to run, the running indicator will
blink. Press ON/OFF button to turn off the unit, then repress ON/OFF button, if air exhaust temperature resume to normal that will
run at setting mode.
The first time heating start-up of compressor or other modes switch to the Heat mode, the air exhaust temp. protection
will be shielded for 1mins.
1.After compressor started up 2mins later to start detect low-pressure switch signal, if continuously 1min.
detected the low-pressure switch break, the whole unit will stop to run, indicator will blink,3mins later, if
low-pressure switch resumed that the unit will automatically resume to run; If continuously low-pressure
switch protection act for twice, the indicator blink but it cannot resume automatically, in order to inform
user air exhust; Press ON/OFF button to turn off the unit, then repress ON/OFF button and low-pressure
switch has resumed to run.
2. During defrosting, do not detect low-pressure switch signal, after defrosting finished, 10mins start to detect.
3. In heating mode, outdoor ambient temperature is lower 0 , will shield low-pressure switch for testing.
4. When heating, compressor is running but outdoor fan is stopping (anti-high temp. protection), low-pressure switch test shield,
outdoor fan will resume to run and start to test the low-pressure switch signal.
5. When compressor is stopping, continuously 30s detected low-pressure switch break off, the whole unit will stop, the indicator will blink,
it cannot resume automatically, it is need to press ON/OFF button to turn off the unit, then repress ON/OFF button, the low-pressure
switch can resume to work.
6. Once power on, before the compressor start up, if continuously 1s detect the low-pressure switch break,all loads will not open, to
turn off the unit and turn on the unit, untile detected the low-pressure switch resume, the loads will run normally.
When anti-freezing protection release and compressor has stopped 3mins, the running indicator will not turn off, the controller will run at
presetting mode.