Green Turtle PHIX User manual


Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Table of Contents
1. PHIX™ Cartridge System Overview________________________________________ 2
1.1. PHIX™ Cartridge System Design and Operation____________________________ 2
1.2. PHIX™ Cartridge Design Considerations ___________________________________ 3
2. Principles of Operation ___________________________________________________ 4
3. Step-by-Step Installation Procedures ______________________________________ 7
4. Maintenance of the PHIX™ Cartridge System _____________________________ 12
4.1. Maintenance Inspection (Chamber 2) ___________________________________ 12
4.2. Solids Removal__________________________________________________________ 12
4.3. Media Replacement ____________________________________________________ 14
5. Green Turtle Limited Warranty ___________________________________________ 13

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Congratulations!
You now have the most efficient and innovative wastewater neutralization system. The
PHIX™ Cartridge System, manufactured by Green Turtle, is a point-source acidic
wastewater treatment solution complying with local plumbing codes throughout North
America. Your engineered system protects your building’s plumbing system and the local
sanitary sewer system form harmful solids and corrosive acids. Now, you have a safe, easy
and worry-free neutralization solution treating low pH where it starts – at the sink.
1. PHIX™ Cartridge System Overview
The PHIX Cartridge System, installed directly under the sink, treats acidic wastewater
and removes solids. The PHIX Cartridge System is compatible with sink sizes, and easy
to install in most commercial, institutional and industrial applications.
The PHIX Cartridge System features an engineered flow-through design to maximize
efficiency and minimize maintenance. The System uses all natural and safe PHIX™
Media which permits better control over effluent pH. It is partly consumed throughout
the neutralization process and is a simply added to the process as required. PHIX M
edia
requires no special storage or handling and ensures optimal and neutralization
treatment within the space-saving unit.
1.1. PHIX™ Cartridge System Design and Operation
The PHIX Cartridge System is constructed from 100 percent durable Polypropylene
(poly) and has a high resistance to numerous chemicals. The PHIX Cartridge System
includes a bucket, siphon pump and hose, supporting bracket and one prescribed
package of PHIX Media.
The PHIX Cartridge System design has four main components (see Figure 1.1.) and is
sized for standard sink drain times in North America. Its engineered design allows for
efficient neutralization of acidic wastewater using PHIX Media, removal of harmful
solids, and easy installation and maintenance.
The PHIX Cartridge System attaches easily to the underside of a sink using the specially
designed Manifold. Wastewater from the sink flows down through the Internal Skeleton
into Chamber 2 (Solids Collection Chamber). Solids settle to the bottom of Chamber 2
and the wastewater then flows up through the perforated plate and into Chamber 1
(Treatment Chamber) containing PHIX Media. Neutralization of the acidic wastewater
occurs upon contact with PHIX Media in Chamber 1. The treated wastewater then exits
the unit through the Manifold and into the drain pipe.
Continued PHIX Cartridge System Design and Operation
Figure 1.1. PHIX Cartridge System
The PHIX Cartridge System uses four main components to adjust pH. Any modifications to
the unit will alter the ability of the System to effectively treat wastewater.
1.1. PHIX™ Cartridge Design Considerations
1. The PHIX Cartridge System removes solids and treats acidic wastewater only.
2.
The PHIX Cartridge System is primarily designed for under the sink installation.
1. The PHIX Cartridge System cannot intercept fats, oils or grease from the
wastewater. A grease interceptor by Green Turtle is recommended if oil and
grease are present. For more information on grease interceptors, please visit
www.greenturtletech.com or contact a Green Turtle Representative at 1-877-428-
8187 (USA) | 1-877-966-9444 (Canada).
1.
The PHIX Cartridge System cannot intercept fats, oils or grease from the
wastewater. A grease interceptor by Green Turtle is recommended if oil and
grease are present. For more information on grease interceptors, please visit
www.greenturtletech.com or contact a Green Turtle Representative at 1-877-428-
8187 (USA) | 1-877-966-9444 (Canada).
3.
2.

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Internal Skeleton and Chamber 1 (Treatment Chamber)
The Internal Skeleton directs the flow of the wastewater through the system. PHIX
Media is contained in Chamber 1. The two components operate as follows:
1. The Internal Skeleton inserts into Chamber 1 and channels wastewater from
the sink strainer through the center pipe (A) directly into Chamber 2 for solids
removal (see Figure 2.2.).
2. Wastewater flows up from Chamber 2 through the perforated plate (B) where
it comes into contact with PHIX Media housed in Chamber 1 (see Figure 2.2.).
The perforated plate ensures the PHIX Media remains in Chamber 1 and solids
are retained in Chamber 2.
3. The neutralized wastewater flows through the woven filter (C). The woven
filter retains the PHIX Media inside the PHIX Cartridge System. The internal
structure brackets (D) support the woven filter (C) (see Figure 2.2.).
4. The treated wastewater exits the unit through the Manifold and into the drain
pipe.
Figure 2.2. Internal Skeleton and Chamber 1
Internal Skeleton Cross Section of Internal Skeleton Chamber 1
inserted in Chamber 1
1. Principles of Operation
Introduction
The operation of the PHIX Cartridge System is simple, safe and effective. The System
has four main components: Manifold, Internal Skeleton, Chamber 1 and Chamber 2. All
components work together to ensure acidic wastewater is neutralized.
Manifold
The Manifold houses the unit’s three main connections:
1. Threads to the sink drain (see Figure 2.1.);
2. Connection to the drain pipe with a 1 ½” adapter, not included with the System
(see Figure 2.1.);
3. Threads into Chamber 1 of the PHIX Cartridge (see Figure 2.1.).
Figure 2.1. Manifold
A.
B.
C.
2.

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Chamber 2 (Solids Collection Chamber)
Chamber 2 is threaded onto the bottom of Chamber 1 and can be removed as
required, provided the water is first removed from the System (see Section 4.2. for
instructions). Chamber 2 captures solids larger than 1/8” (paper, food etc.)
preventing items from disrupting the neutralization treatment process, or becoming
lodged in the downstream piping.
Figure Error! No text of specified style in document..3.
Chamber 2
1. Step-by-Step Installation Procedures
Introduction
The PHIX Cartridge System includes a bucket, siphon pump and hose, supporting
bracket, and one prescribed package of PHIX Media. To install the unit, please follow
these simple step-by-step installation instructions.
Installation Instructions:
1. Remove Drain
Remove the existing waste (drain) pipe between the sink strainer and the stub out at
the wall or floor. If the piping is plastic with compression (threaded-type) fittings,
unthread the pipe and save it for possible reuse. If the pipe is welded or metal, cut
using a hacksaw and discard. Unscrew fittings by hand or with groove-joint pliers.
Figure 3.1. Standard Sink Connection
Installation Tip: Before removing the drain plug or disconnecting the trap, place a
plastic bucket under the drain trap to catch any standing water.
3.
Figure 2.3. Chamber 2

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
3. Connect Plastic Waste Pipe
Install a 1 ½” adapter to the threaded connection on the outlet of the Manifold
(1 ½” adapter not included with the System). Connect a two-piece tubular P-
trap between the adapter, and to the stub out (drain fitting). If required, cut the
P-trap and rotate both the trap section of the P-trap and the PHIX Cartridge
System to ensure that they are aligned. Complete the connection by tightening
the waste pipe fittings and the PHIX Cartridge System. All piping from the PHIX
Cartridge System must meet the local plumbing codes.
Figure 3.3. Configuration of the PHIX Cartridge and Piping Connections
Please Note: If a dishwasher is present, connect the dishwasher hose between the
PHIX Cartridge System drain fittings and the P-trap.
1. Connect the PHIX™ Cartridge System
To connect the PHIX Cartridge System to the sink, thread the slip nut at the top of
the PHIX Cartridge System onto the threads of the sink strainer (underneath the
sink). Ensure the washer, provided with the System, is installed between the top of
the PHIX Cartridge System and the sink strainer before threading the two together.
Figure 3.2. Connection between the PHIX Cartridge and Sink
2.

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
4. Install Support Bracket
The installation of the support bracket ensures that the suspended PHIX Cartridge
System is properly supported. The bracket also prevents the unit from accidentally
being moved or nudged.
1. Place the bracket on the ground or cabinet floor directly below the block
located on the bottom of Chamber 2.
2. Thread the nut from the bracket up into the notch on the block (located on the
bottom of Chamber 2). The nut should rest snuggly inside the notch. If the
bracket does not reach the block, a spacer is required.
3. Screw the flange of the bracket down into the ground or cabinet floor.
Figure 3.4. Expanded view of the Support Bracket
1. Initial Startup Procedure
Once the installation is complete, you must perform a flow test to verify
there are
no leaks.
Flow test:
Run water from tap into sink, and visually inspect threaded connections.
1.1. If a leak is detected tighten threaded connections until the leak has stopped.
1.2. Once the test is complete, please see Section 5.3. for instructions on adding PHIX
Media to the PHIX Cartridge System.
1. After the PHIX Media is added, the System is ready for operation.
1.
Maintenance of the PHIX™ Cartridge System
The maintenance of the PHIX Cartridge System is critical to ensure no disruption in the
neutralization treatment process. The PHIX Cartridge System must be maintained
according to the following procedures to ensure continual effective treatment of acidic
wastewater.
1.1. Maintenance Inspection (Chamber 2)
When the drain down time of the sink increases, the PHIX Cartridge System requires
cleaning. To check the amount of waste in Chamber 2 use a flashlight and shine behind
the Chamber to perform a visual inspection. If half of Chamber 2 is filled with waste, the
unit requires cleaning (see Section 4.2 for Solid Removal instructions).
1.2. Solids Removal
Chamber 2 captures any solids that may go down the sink; if the Chamber becomes full
of waste and requires cleaning, please do the following:
1. Remove water from the unit by inserting the siphon tube (included with the System) down the
center drain of the sink. When the tube touches the bottom of Chamber 2, pull up slightly so the
tube is no longer touches the bottom (see Figure 4.1.).
2. Begin to siphon the water from the PHIX Cartridge System into a bucket by priming the tube with
the siphon pump (included with the System).
3. Once all of the water is removed, thread the nut down from the support bracket to create
adequate space to remove Chamber 2 from under the system.
4. Unthread Chamber 2 from Chamber 1 using an adjustable wrench on the block at the bottom
of Chamber 2. Use a strap wrench on Chamber 1 (see Figure 4.1.)
5. Empty the waste collected in Chamber 2 into a trash bin. No special handling required. Rinse
Chamber 2 with water and wipe clean with a cloth.
6. Rethread Chamber 2 tightly onto Chamber 1.
Figure 4.1. Solids Removal
Siphoning of the water out of the PHIX Cartridge System Unthread Chamber 2 to discard the waste
4.
5.
1.
2.
3.
1.1.
If a leak is detected tighten threaded connections until the leak has
stopped.
1.2.
Once the test is complete, please see Section 5.3. for instructions on
adding PHIX Media to the PHIX Cartridge System.
1. After the PHIX Media is added, the System is ready for operation.
1. After the PHIX Media is added, the System is ready for operation.
4
4

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
1.
To clean the Internal Skeleton, rinse the perforated plate and the center pipe
with water and wipe clean with a cloth, then insert the Internal Skeleton
back into Chamber 1.
2.
Pour one package of PHIX Media into Chamber 1, between the center pipe
and the sidewall (see Figure 4.2.). Place the woven filter on the top of
Internal Skeleton and reattach the Chamber 1 and Chamber 2 to the
Manifold, using the appropriate tools to ensure a tight seal.
1.
The system is replenished with PHIX Media and is now ready to resume
operation.
10.
11.
12.
1.1. Media Replacement
PHIX Media in the PHIX Cartridge System must be replaced at regular intervals according
to the following guidelines.
USAGE
REPLACEMENT FREQUENCY
Constant use, highly acidic wastewater
Quarterly (every 3 months)
Moderate use, mixed acidic and basic wastewater
Biannually (twice a year)
Low use, mildly acidic wastewater
Annually (once a year)
To confirm the media maintenance schedule for your application, or to place an order
for replacement media please contact a Green Turtle Representative at 1-877-428-8187
(USA) | 1-877-966-9444 (Canada).
To add or replace PHIX Media:
1. Remove water from the unit by inserting the siphon tube (included with the
System) down the center drain of the sink. When the tube touches the
bottom of Chamber 2, pull back up slightly so the tube is no longer touches
the bottom.
2. Begin to siphon the water from the PHIX Cartridge System into a bucket by
priming the tube with the siphon pump (included with the package).
3. Once all of the water is removed, thread the nut down from the support
bracket, so there is adequate space to remove the main body from the
Manifold.
4. To remove Chamber 1 and Chamber 2 from the Manifold, use a strap
wrench on Chamber 1 while holding the Manifold tightly. Then unthreading
the joint between Chamber 1 and the Manifold.
5. Remove the woven filter located on the top of Chamber 1.
6. Rinse the filter with water - the filter can be re-used, or replaced when
required.
7. Dispose any remaining Media found in Chamber 1 into a trash bin. (Note: No
special handling of used PHIX Media is required)
8. If there is any waste in Chamber 2, do not remove Chamber 2 from
Chamber 1, simply remove the Internal Skeleton from Chamber 1.
1. Dispose the collected waste into a trash bin. Rinse Chamber 1 and 2 with
water and wipe clean with a cloth.
9.
4.3

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Figure 4.2.PHIX Media Replacement
Siphoning of the water out of the PHIX Cartridge System Replace PHIX Media
1. Green Turtle Limited Warranty
(a) This warranty is provided by Green Turtle Technologies Ltd. for products sold in
Canada, and by Green Turtle Americas Ltd. for products sold in the continental U.S.
Although the companies are collectively referred to herein as “Green Turtle,” each
company only warrants products sold in its respective market. PHIX Cartridge Systems
are not intended for industrial, residential or other consumer use, and may not be
purchased or sold for those applications. Green Turtle warrants to Customer that the
PHIX Cartridge System shall be free of defects in materials and workmanship for one
year from the date of shipment (the “Warranty Period”), subject to the terms and
conditions below. Green Turtle’s warranties will not apply to any PHIX Cartridge System
with respect to which there has been (i) improper installation or testing, (ii) failure to
provide a suitable operating environment, (iii) use of the PHIX Cartridge System for
purposes other than that for which it was designed, (iv) installation or use of the Phix
Cartridge System in any application other than commercial or institutional use; (v)
failure to monitor or operate or maintain the PHIX Cartridge System in accordance with
applicable Green Turtle specifications and good industry practice (including, without
limitation, periodic replacement of any operational media in accordance with Green
Turtle’s recommendations and technical requirements), (vi) unauthorized attachment
or removal or alteration of any part of the PHIX Cartridge System, (vii) unusual
mechanical, physical or electrical stress, (viii) modifications or repairs done by
unqualified personnel, or (ix) any other abuse, misuse, neglect or accident. PHIX
Cartridge System supplied hereunder may contain used parts and/or be reconditioned.
(b) After initial installation of the PHIX Cartridge System, the installation checklist
supplied by Green Turtle must be properly completed, and the completed checklist
must be submitted to Green Turtle within 30 days after installation (failure to deliver the
document may result in denial of the claim).
(c) Customer shall notify Green Turtle in writing promptly (and in no case later than 30
days after discovery) of the failure of any PHIX Cartridge System to conform to the
warranty set forth above, shall describe in commercially reasonable detail the
symptoms associated with such failure, and shall provide to Green Turtle the
opportunity to inspect such PHIX Cartridge Systems as installed, if possible. Green Turtle
must receive the notice during the Warranty Period for such PHIX Cartridge System.
5.

Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
Green Turtle (USA) Green Turtle (Canada)
Five LakePointe Plaza, Suite 410 2596 Dunwin Drive
2709 Water Ridge Parkway, Charlotte NC 28217 Mississauga, Ontario L5L 1J5
Tel: 704.295.1733 | 1.877.428.8187 Tel: 416.966.9400 | 1.877.966.9444
Fax: 704.295.1734 Fax: 416.966.3439
NO EMPLOYEE OF GREEN TURTLE OR ANY OTHER PARTY IS AUTHORIZED TO MAKE ANY
OTHER REPRESENTATIONS, WARRANTIES, OR CONDITIONS FOR THE PHIX CARTRIDGE
SYSTEM OTHER THAN THE WARRANTY SET FORTH HEREIN. GREEN TURTLE’S MAXIMUM
LIABILITY UNDER THE WARRANTY SHALL BE LIMITED TO A REFUND OF THE PURCHASE PRICE
OF THE PHIX CARTRIDGE SYSTEM. IN NO EVENT SHALL GREEN TURTLE BE LIABLE FOR THE
COST OF PROCUREMENT OR INSTALLATION OF SUBSTITUTE GOODS BY BUYER OR FOR ANY
SPECIAL, CONSEQUENTIAL, INDIRECT, PUNITIVE, CONSEQUENTIAL OR OTHER DAMAGES,
INCLUDING, WITHOUT LIMITATION, COSTS, EXPENSES, OR LIABILITIES ASSOCIATED WITH
ENVIRONMENTAL CONTAMINATION, FINES OR PENALTIES, FIRES, EXPLOSIONS, OR ANY
OTHER CONSEQUENCES ALLEGEDLY ATTRIBUTABLE TO A BREACH OF THE WARRANTY OR
DAMAGES UNDER DECEPTIVE TRADE PRACTICES OR SIMILAR CONSUMER PROTECTION
ACTS. THE FOREGOING CONSTITUTES GREEN TURTLE’S EXCLUSIVE OBLIGATION.
(f) Customer assumes the risk of and agrees to indemnify Green Turtle against and hold
Green Turtle harmless from all liability relating to (i) assessing the suitability for
Customer’s intended use of the PHIX Cartridge System and of any system design or
drawing and (ii) determining the compliance of Customer’s use of the PHIX Cartridge
System with applicable laws, regulations, codes and standards. For PHIX Cartridge
Systems resold by Customer, Customer retains and accepts full responsibility for all
warranty and other claims relating to, or arising from, Customer’s PHIX Cartridge System
which include or incorporate PHIX Cartridge System or components manufactured or
supplied by Green Turtle, and Customer is solely responsible for any and all
representations and warranties regarding the PHIX Cartridge System made or
authorized by Customer. Customer will indemnify Green Turtle and hold Green Turtle
harmless from any liability, claims, loss, cost or expenses (including reasonable legal
fees) attributable to Customer’s PHIX Cartridge System or representations or warranties
concerning same.
(d) Within a reasonable time after verification by Green Turtle that the PHIX Cartridge
System fails to meet the warranty set forth above, Green Turtle shall correct such failure
by, at Green Turtle’s option, either (i) modifying or repairing the PHIX Cartridge System
or (ii) replacing the PHIX Cartridge System. If Green Turtle is unable to modify, repair or
replace a PHIX Cartridge System to conform to the warranty set forth above, then
Green Turtle shall, at Green Turtle’s option, either refund to Customer or credit to
Customer’s account the purchase price of the PHIX Cartridge System less depreciation
calculated on a straight-line basis over Green Turtle’s stated Warranty Period. Warranty
does not include labor, transportation, or other installation or removal costs or expenses.
THESE REMEDIES SHALL BE BUYER’S EXCLUSIVE REMEDIES FOR BREACH OF WARRANTY.
(e) EXCEPT FOR THE EXPRESS WARRANTY SET FORTH ABOVE, GREEN TURTLE MAKES NO
OTHER REPRESENTATIONS OR WARRANTIES, EXPRESS OR IMPLIED, STATUTORY OR
OTHERWISE, REGARDING THE PHIX CARTRIDGE SYSTEM, THEIR FITNESS FOR ANY PURPOSE,
THEIR QUALITY, THEIR MERCHANTABILITY, THEIR NON-INFRINGEMENT, OR OTHERWISE.
Table of contents
Popular Water Filtration System manuals by other brands

Sharp
Sharp FZ-A61MFR Operation manual

ClearPlus
ClearPlus Carbon Premium CP-CS-5810SXT Series Owner's manual & installation guide

Henden
Henden HCF100 Installation & owner's manual

enviroswim
enviroswim ES-3 installation guide

Whirlpool
Whirlpool EveryDrop S3RFWG60NP Usage instructions

Hydrotech
Hydrotech 89 BIF owner's manual