Groupe Atlantic NAVISTEM B2000 User manual

CONTROL PANEL FOR
CLASSIC BOILERS
NAVISTEM B2000
MANUFACTURER:
SITE DE CAUROIR
C
O
L
L
E
C
T
I
V
E
P
R
O
D
U
C
T
Route de Solesmes
FR - 59400 CAUROIR
Instructions
for installation,
use and
maintenance
Document No. 0TA0Z0110-C / 01.02.2018
FR EN DE ES IT NL

Page 2 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

CONTENTS
1. WARNINGS AND COMPLIANCE ....................................................................................... 4
2. TECHNICAL SPECIFICATIONS ......................................................................................... 6
2.1. General ......................................................................................................................................................... 6
2.2. Dimensions ................................................................................................................................................... 6
2.3. Delivered unit ................................................................................................................................................ 6
2.4. Technical data ............................................................................................................................................... 7
2.5. Thermostat module ....................................................................................................................................... 8
2.6. Basic control panel equipment ...................................................................................................................... 9
2.7. Regulation/Regulator .................................................................................................................................. 10
3. INSTALLATION .................................................................................................................. 12
3.1. Installation of the control panel ................................................................................................................... 12
3.2.Fittingsensors(bulbsorowsensors)........................................................................................................ 13
3.3. Electrical connection ................................................................................................................................... 16
4. ADDITIONAL ACCESSORIES.......................................................................................... 24
4.1. Temperature sensors .................................................................................................................................. 24
4.2. Remote control QAA75 ............................................................................................................................... 25
4.3. Other accessories ....................................................................................................................................... 26
5. USING THE CONTROL PANEL........................................................................................ 27
5.1.Start-up(Commissioning) ........................................................................................................................... 27
5.2.Breakdownmaintenance............................................................................................................................. 28
6. HYDRAULIC DIAGRAMS AND CONFIGURATIONS ..................................................... 31
6.1. Symbols used in the diagrams .................................................................................................................... 31
6.2. List of diagrams........................................................................................................................................... 31
7. SPARE PARTS LIST.......................................................................................................... 72
Edition: 02 / 2018 Page 3 / 76
NAVISTEM B2000 - Installation, use and maintenance

1. WARNINGS AND COMPLIANCE
Unpacking and reservations
With the carrier present, carefully check the general appearance of the packaging and
of the control panel. If in doubt, do not use the appliance.
Inthecaseofanydispute,stateanyappropriatereservationstothecarrierinwriting
within48hoursandsendacopyofthislettertotheAfter-Salesservice.
Storage
The control panel:
• mustbearrangedhorizontallyinaplacewherethetemperatureisbetween0°C
and+50°C
• must be protected from humidity.
Symbols used in this document
INFORMATION: Thissymboldrawsattentiontocomments.
!WARNING: Failure to comply with these instructions may cause damage to the
installation or to other objects.
!
DANGER: Failure to comply with these instructions may cause injury and serious
material damage.
DANGER: Failuretocomplywiththeseinstructionsmaycauseelectrocution.
Compliance with European Directives
Low voltage (2006/95/CE)
• ThisappliancecomplieswithallrequirementsoflowvoltagedirectiveEN60730-
1 + EN60730-2-9.
• This appliance is not intended for use by persons (including children)
whose physical, sensory or mental abilities are reduced, or persons
without experience or knowledge, unless they have been able to
benet, through someone responsible for their safety, from supervision or prior
instruction concerning the use of the appliance.
• Childrenmustbesupervisedtoensuretheydonotplaywiththeappliance.
Page 4 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

Electromagnetic compatibility (2004/108/CEE)
• Thisapplianceconformswithallrequirementsoftheelectromagneticcompatibility
directive EN61000 - 6 - 1, EN61000 - 6 - 3.
• This is a class A appliance. In a residential environment, this appliance may cause
radio-electric interference. In this case, the user may be asked to take appropriate
measures.
Environmental compatibility
• This appliance contains electrical and electronic elements which must not be
thrownawaywithhouseholdwaste.
• Locallegislationmustbecompliedwith.
Installation and maintenance rules
The control panel must be installed and maintained by an approved professional in
accordancewiththeprevailingregulationsandcodeofpractice,inparticular:
• Complywithrulesinforceandwithspecicinstructionsandnormsapplicablein
the country of installation.
!
WARNING: Thecontrolpanelisclassiedasanappliancewhichisnotaccessibletothe
public(closedelectricaloperatingzone).
!
WARNING: The control panel must only be used for the purpose for which it was
designed; any other use must be considered inappropriate and therefore
dangerous.
!WARNING: Theappliancemustbeshelteredfromrain,snowandfrost.
!DANGER: Thecontrolpanelandtheheatregulatorsinsideitcannot beexposedto
temperatureshigherthan45°Cwheninoperation.
INFORMATION: Thisproductmustbeassembled,usedandmaintainedincompliancewith
the information provided in these technical instructions.
DANGER: Alwaysturnthecontrolpanelobeforecarryingoutanyworkonit.
!DANGER: Alwaysturnthecontrolpanelobeforecarryingoutanyworkontheburner,
boiler or other heating elements (pumps, valves, etc.) controlled by the
control panel.
Edition: 02 / 2018 Page 5 / 76
NAVISTEM B2000 - Installation, use and maintenance

2. TECHNICAL SPECIFICATIONS
2.1. General
The NAVISTEM B2000 control commands the boiler's burner and heating circuits
depending on the installation. All elements of the installation can thus be handled and
commanded easily from one place.
The control panel's capacities can be increased by adding accessories:
• AdditionalheatingregulatorRVS46(+displayAVS37)
2.2. Dimensions
gure 1 - Dimensions (in mm)
2.3. Delivered unit
• Sheet metal casing
• Thermostat module
• Heating regulator RVS63
• Boiler sensor
• Instructions for servicing, installation and technical guidelines
• Electrical diagram
• Instructions for regulator RVS63
• Assemblykit(screws)
540
438
147
172
Page 6 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

2.4. Technical data
Name of manufacturer YGNIS INDUSTRIE
Unique reference NAVISTEM B2000
Single-phase power supply 230 VAC 50Hz
Rated current 16 A
Casing protection index IP20
Reference operating
temperature T45
Degree of pollution Degree of pollution II
Protection index Class I
(surgevoltage=800V)
Safety thermostat 110°CMaximumTemperature
(+0/-9°C)
Burner thermostat setting at
speed 1 35…95°C(+/3°C).Tosettothe
maximumvalueof95°C
Burner thermostat setting at
speed 2 Inactive for a NAVISTEM
B2000 control panel
Electrical consumption Depends on appliances
plugged in (burners, pumps,
mixingvalves)
Maximum installation
altitude 2,000 m
Relative humidity 5 to 95%
Terminal output power Voltage: 230V AC (+10%/-
15%)
Amperage: 5 mA to 2 A.
GWFI plastic interface 550°C
Type of printed circuit
board(s) coating EPOXY FR4 FT glass
Other technical data See instructions for regulator
RVS63
!
WARNING: The control thermostat must be set to its maximum setting to avoid
interferencewiththeelectronicregulatorRVS63.
Edition: 02 / 2018 Page 7 / 76
NAVISTEM B2000 - Installation, use and maintenance

2.5. Thermostat module
gure 2 - Thermostat module
Legend
1: F1: 6.3 AH 250 V AC Burner / Boiler fuse
2: F2:6.3AH250VACHeatingregulatorfuse(RVS63)
3: F3:6.3AH250VACadditionalheatingregulatorfuse(soldasanaccessory)
4: Safetythermostat(resetbutton)
5: First speed and second speed control thermostat (inactive on a
NAVISTEMB2000controlpanel).
6: ON/OFFswitchforburnerpowersupply
7: Thermometer: indication of the boiler's temperature
8: LEDindicatingaproblemwiththesafetythermostat(boilertemperaturetoo
high)
9: LEDindicatinganexternalproblem
10: LEDindicatingaproblemwiththeburner
11: Positionfortheburner'sremoteresetbutton(optional)
12: PositionforTUVswitch(optional)
21
10
9
8
7
6
5
4
3
12 11
Page 8 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

2.6. Basic control panel equipment
1: Thermostat module
2: Connector for alarm relay board
3: AdditionalpowersupplyconnectorRVS46
4: Burner connection terminal
5: Connection terminal to release the burner's
operation
6: Powersupplyandconnectionterminalof
safety devices specific to the installation
7: Accessory terminal for three-phase burner
powersupply(notincludedwithcontrolpanel.
Tobeorderedasanaccessory).
gure 3 - Basic control panel equipment
1
4
2
3
5
6
7
Edition: 02 / 2018 Page 9 / 76
NAVISTEM B2000 - Installation, use and maintenance

2.7. Regulation/Regulator
gure 4 - Regulation/Regulator
1: DisplayAVS37(suppliedwithaccessoryRVS46)
2: DisplayAVS37(basicNAVISTEMB2000controlpanelequipment)
3: AdditionalregulatorsoldasaccessoryRVS46(withdisplay)
4: RegulatorRVS63(basicNAVISTEMB2000controlpanelequipment)
5: Regulationelectronicboard(basicNAVISTEMB2000controlpanelequipment)
2.7.1. Heating regulator RVS63 + display AVS37
Theregulatorallowsthefollowing:
• Commandofaone-speed,two-speedormodulatingburner
• Command of a direct heating circuit
• Command of two heating circuits or one heating circuit and one mixing valve
protectingtheheatexchangerreturntemperature
• Commandofdomestichotwaterpreparation
• Cascade with one or more other boilers tted with a SIEMENS regulator (LPB
communicationbus).
1 2
3
4 5
Page 10 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

!WARNING: The RVS 63 regulator is protected with a 6.3 A fuse. The total load of
the consuming elements (pumps, mixing valves, isolation valves, etc.)
connected to this regulator must not be more than 6.3 A.
!WARNING: Themaximumamperageoneachofthecommandedoutputsmustnotbe
more than 2 A. The heating regulator relays cannot accept a higher load.
!DANGER: UsersoftheNAVISTEMB2000controlpanelmustfollowtheprecautionsof
useindicatedintheinstructionsoftheRVS63regulatorincludedwiththis
additional accessory.
INFORMATION: The electrical connection diagrams (pumps, valves, temperature sensors,
etc.)areprovidedinaccordancewiththeinstallation'shydraulicconguration,
see«Hydraulicdiagramsandcongurations».
2.7.2. NAVISTEM B2000 regulation board
Thisboardallowsthefollowing:
• connection of an isolation valve or boiler pump
• sending of a summary of errors to the RVS63 regulator
!WARNING: Themaximumamperageoneachofthecommandedoutputsmustnotbe
more than 2 A. The regulation board relays cannot accept a higher load.
2.7.3. Additional heating regulator RVS46 (+ display AVS37)
Regulatornotincludedinthebasiccontrolpanel(soldasanadditionalaccessory)
• Slave heating regulatory enabling a heating circuit with mixing valve to be
commanded.
• Amixingvalveprotectingthereturntemperature:protectionagainstcondensation
inthestainlesssteelheatexchangerwhentheRVS63outputsarealreadybeing
usedtomanagetwoheatingcircuits.
!
WARNING: The RVS 46 regulator is protected with a 6.3 A fuse. The total load of
the consuming elements (pumps, mixing valves, isolation valves, etc.)
connected to this regulator must not be more than 6.3 A.
!
WARNING: Themaximumamperageoneachofthecommandedoutputsmustnotbe
more than 2 A. The heating regulator relays cannot accept a higher load.
!DANGER: UsersoftheNAVISTEMB2000controlpanelmustfollowtheprecautionsof
useindicatedintheinstructionsoftheRVS63regulatorincludedwiththis
additional accessory.
INFORMATION: The electrical connection diagrams (pumps, valves, temperature sensors,
etc.)areprovidedinaccordancewiththeinstallation'shydraulicconguration,
see«Hydraulicdiagramsandcongurations».
Edition: 02 / 2018 Page 11 / 76
NAVISTEM B2000 - Installation, use and maintenance

3. INSTALLATION
3.1. Installation of the control panel
!
WARNING:
Thecontrolpanelmustbettedandinstalledinthepositionintendedfor
this on
the boiler.
3.1.1. Opening the control panel
Removethescrewsonthecover.
gure 5 - Opening the control panel
DANGER: Keep the screws from the control panel's cover. They are specic and
ensure grounding continuity.
3.1.2. Fitting above the boiler
• Pass the three capillaries (thermometer, control
thermostat, safety thermostat) through the
oblong hole on the boiler's upper jacket.
• Passtheboilerowsensorthroughthesame
oblong hole.
• After installing the capillaries, clip the control
panel to the boiler's upper jacket using studs.
• Fit the control panel to the boiler's upper jacket
usingthesheetmetalscrewsincluded.
gure 6 - Fitting the control panel
Page 12 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

3.1.3. Fitting to the side of the boiler
• Pass the three capillaries (thermometer,
controlthermostat,safetythermostat)through
the oblong hole 1on support2.
• Fit the control panel 3 with the studs to
support2ttedontheboiler'ssidejacket.
• Fit the control panel to the support on the
boiler's side jacket using the sheet metal
screwsincluded.
gure 7 - Fitting the control panel
• Rotation of the interfaces so that they can be
read by the user
gure 8 - Rotation of the interfaces
!WARNING: Follow the direction of rotation indicated on the diagram above (anti-
clockwise)
3.2.
3.2.1. Tri-lobal thimble
1Foam seal Ø 8
2Tri-lobal thimble
3Staple
gure 9 - Tri-lobal thimble
12
3
1
23
Edition: 02 / 2018 Page 13 / 76
NAVISTEM B2000 - Installation, use and maintenance

gure 10 - Installation of sensors
A: Foam seal Ø 8 mm
B: Sensor
• To getacorrecttemperaturereading,insertthe sensors with the Ø 8 mmfoam
seal.
• The minimum curve radius of the capillaries is 5 mm.
• Afterinstalling,blockthesensorswiththestapleincludedinthethimbleunit.
!DANGER: Donotlltheprotectivetubeswithoil.Donotuseheatconductingpaste
or similar products.
!WARNING: Donotdamageordeterioratethecapillarieswhentting.
3.2.2. LRP NT plus - LRP
Position of sensors
1F4: Safety thermostat
2F5:
B2:
Control thermostat
Boilersensor(QAZ36)
Thermometer
3B7: Return sensor (immersion sensor,
QAD36). Not supplied with the control
panel
gure 11 - LRPNT Plus
A
A
B
B
1 or 2 sensors 3 sensors
2
3
1
Page 14 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

Position of sensors
1F4: Safety thermostat
2F5:
B2:
Control thermostat
Boilersensor(QAZ36)
Thermometer
3B7: Return sensor (contact sensor, QAD36).
Notsuppliedwiththecontrolpanel
gure 12 - LRP
3.2.3. LRR
Position of sensors
1F4: Safety thermostat
2F5:
B2:
Control thermostat
Boilersensor(QAZ36)
Thermometer
3B7: Return sensor (immersion sensor,
QAZ36) to be ordered as an accessory.
Notsuppliedwiththecontrolpanel
gure 13 - LRR
3.2.4. LR
Position of sensors
1F4: Safety thermostat
2F5:
B2:
Control thermostat
Boilersensor(QAZ36)
Thermometer
3B7 Return sensor (immersion sensor,
QAZ36) to be ordered as an accessory.
Notsuppliedwiththecontrolpanel
gure 14 - LR
3
2
1
2
3
1
1
3
2
1
2
Edition: 02 / 2018 Page 15 / 76
NAVISTEM B2000 - Installation, use and maintenance

3.2.5. LRK
Position of sensors
1F4: Safety thermostat
2F5:
B2:
Control thermostat
Boilersensor(QAZ36)
Thermometer
3B7: Return sensor (immersion sensor,
QAZ36)tobeorderedasanaccessory.
Notsuppliedwiththecontrolpanel
4S11: RT Recuperator thermostat (not included
withthecontrolpanel).
gure 15 - LRK
3.3. Electrical connection
INFORMATION: The electrical diagram is attached to the control panel. It is stuck under the
cover.
!WARNING: Do not pull the electrical cables and remove them from heat sources.
!WARNING: Only carry out electrical connections, in particular connection to the main
supply,whenallotherttingandinstallationworkiscompleted.
!
WARNING: Installationscarriedoutbythecustomer(cableruns,gasorfuelpipes,etc.)
mustnotbettedtotheboiler'sjacket!
!
WARNING: Thecontrolpanelmustbettedandinstalledinthepositionintendedfor
this on the boiler.
1
2
3
4
1
2
Page 16 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

AArea for signal cables (VLV: voltage less than
20VDC).
B Areaforlowvoltagecables(LV:between
50VACand400VAC).
gure 16 - Cabling
DANGER: ComplywiththecablingareasandseparationofLVandVLVcables.
B
A
Edition: 02 / 2018 Page 17 / 76
NAVISTEM B2000 - Installation, use and maintenance

3.3.1. Control panel cabling diagram
gure 17 - Control panel cabling diagram
T6.3AH
250VAC
T6.3AH
250VAC
T6.3AH
250VAC
1
1234 5 6 1 2 34567891 2 3
F1
F1 F1
F2
F2 F2
F3
F3 F3 LL N
N
A2 B1 A1
21 121422 11
L
N
T1
T2
S3
B4
B5
T6
T7
T8
5
4
3
N
L
1234
6
7
N
3 31 12 2
N Y2 Y1
12345 67891 2 3456
11 01 9 8 7 6 5 4 3 2 1
1
2
3
1
Z
U
UTSUTSRQP
L N
QX4
QX4
FX4
EX2
QX3
N
M
UX
BX4
RVS 63
QX2
N
Y6
N
Y5
Q6
N
QX1
N
Y2
N
Y1
Q2
N
Q3
N
SK2
SK1
4
S3
T2
T1
N
L1
S3
L1
N
L
nnnnpnnpnkhfbbb
a
X50X30
X60
LPB
BSB
M
M
BX3
M
H3
M
B12
M
BX2
M
BX1
M
B1
M
H1
M
B9
M
B3
M
B2
G+
CL-
CL+
CL-
CL+
CL-
CL+
MB
DB
NAVISTEM B2000
Burner
power supply
Command for
1st-stage
of burner
230 V AC general
power supply
External safety interlock
Burner operation authorisation
or connection of external
regulation to control 1st stage
Optional
power supply
Safety
thermostat
Control thermostat
Command for
2nd-stage
of burner
Mixing valve 2
Boiler pump of
2-channel valve for
boiler isolation
Pump for circuit 2
Pump for circuit 1
DHW pump
output
Return
sensor
Sensor
Sensor
Cascade
ow sensor
External
sensor
DHW sensor
LPB BUS
for circuit 2
for circuit 1
0/10V
Regulation board
Programmable
output
Prog
sensor input
Prog client
input
(0 to 10V or contact)
Ambient
sensor input
QAA75
Boiler
ow sensor
Mixing valve 1
Prog client
input
Page 18 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance

3.3.2. Burner cables and ow sensor
• Passtheburnerconnectionandtheboilerow
sensor cables through the rubber membrane 1
andpositionthembetweentheinsulationand
the boiler's jacket.
gure 18 - Burner cables and ow sensor
!WARNING: Do not remove or alter the boiler's insulation. Ensure there is no direct
contactbetweenthecablesandtheheatexchanger.
3.3.3. Other cables
Theothercablesofthedierentelements(pump,mixingvalves,circuittemperature
sensors,errorrelay,powersupplycables,etc.)canbedirectlypositionedattheback
of the control panel via the cable glands.
1: Cable gland for sensors and signals
2: Cableglandforpumpandmixingvalvecables
3: Cableglandsforpowercables
4: Position for the three-phase burner supply
cable gland
5: Position for the alarm relay board cable gland
6: Position for gland foroptional regulator
1
4
1
253
66
gure 19 - Other cables
Edition: 02 / 2018 Page 19 / 76
NAVISTEM B2000 - Installation, use and maintenance

3.3.4. Connection of the control panel's electrical power supply and external safety con-
nections
A Controlpanel'selectricalpowersupply:230V
AC 50 Hz
Maximumintensity:16A
Type of cable: 3 G 2.5 mm²
B Externalsafetyconnections:230VAC50Hz
Remove the shunt between 3 and 4 to
connect the external safety elements
Maximumintensity:16A
Type of cable: 2.5 mm²
gure 20 - Connection of the control panel's electrical
power supply and external safety connections
!
WARNING: Do not reverse phase and neutral.
WARNING: Neveruseasocketforthepowersupply.
WARNING: Thecontrolpanelmustbepoweredbyspecialprotectedlinesleavingthe
boiler room's electric panel via all-pole circuit breakers.
WARNING: The protective earth conductor must be longer than the phase and neutral
conductors.
A
B
Page 20 / 76 0TA0Z0110-C
NAVISTEM B2000 - Installation, use and maintenance
Table of contents
Other Groupe Atlantic Control Panel manuals
Popular Control Panel manuals by other brands

Rosslare
Rosslare HLX-24TH Series user manual

Roger Technology
Roger Technology B70 1DCHP quick start guide

Jung
Jung SP 9 KNX operating instructions

Festo
Festo CDPX-X-E2-W EX2 Series manual

SILENT KNIGHT
SILENT KNIGHT INTELLIKNIGHT 5808 Installation and operation manual

Nordelettronica
Nordelettronica NE269 instruction manual