General
information
Our systems must be installed by an
authorise sanitary/heating and electri-
cal company. Check the components
for transport damage. The GENO®-
EWT-L blower air preheater must be
protected against frost. Do not install
PVC lines in the immediate vicinity of
significant heat sources.
1 | Intendeduse The GENO®-EWT-L blower air pre-
heater is used for electrical heating of
the drawn-in outside air in private or
public swimming pools, Jacuzzis, etc.,
and is only allowed to be operated
when the blower is running.
2 | Technical specifications
Blower air preheater GENO®-EWT-L 1.5
Connection data
Nominal connection diameter [DN] 50 (2" female thread)
Protection/protection class IPX4 / I
Power supply [V/Hz] 230 / 50
Cable cross section [mm²] 1.5
Fuse protection (slow-blow) [A] 10
Performance data
G Control thermostat [°C] 30 - 90
Heat output [kW] 1.5
Dimensions and weights
A Connection height [mm] 382
B Total housing width [mm] 260
C Connection width [mm] 171
D Housing width [mm] 75
E Total height [mm] 602
F Connection height [mm] 505
HDistance to wall [mm] 47
Ambient data
Stainless steel housing 1.4404
Ambient temperature [°C] 40
Order no. 208 495
Fig. 1. Installation and dimensional drawing EWT-L blower air pre-
heater
3 | Installation
requirements
Please observe local installation direc-
tives, general guidelines and technical
specifications. The installation loca-
tion should be easily accessible, must
not be prone to fire or at risk of
flooding. Establish the connection
with exposure to stress.
4 | Scope of
supply
GENO®-EWT-L blower air preheater
made of stainless steel incl. control
thermostat, flexible hose connec-
tions, with PVC nipples, wall fas-
tening materials and operation man-
ual.
5 | Installation
Install flexible hose connections on
the GENO®-EWT-L blower air pre-
heater. Installation is made in the full
flow between the pool and blower.
The installation should be > 0.3 m (A)
above the water surface (B), and is al-
lowed to be horizontal or vertical
(Fig. 2 and Fig.3).
Fig. 2: Horizontal installation (above pool level)
Fig. 3: Vertical installation (above pool level)
If installed below the water surface
(B), a pipe loop approx. 1 m (A) above
the water surface is required (Fig. 4).
Edited by: KONS-nkes-mrie G:\BA-208499-INTER_GENO-EWT-L.DOCX
Fig. 4: Horizontal installation (below pool level)
Note: Pay attention to the flow direc-
tion, no shut-off valves should be in-
stalled between the GENO®-EWT-L
blower air preheater, client's blower
and swimming pool.
Caution! Measures must be taken in
the control technology to ensure that
the GENO®-EWT-L blower air pre-
heater will always be switched off
when the blower is at a standstill.