
4.10 Grounding
Pole grounding
It is prohibited to connect any pole, DC+ or DC-, of
the photovoltaic system directly to PE.
Drive grounding
All non-current-carrying metal parts (module frames,
enclosures) and also the midpoint of the current
carrying conductors of the photovoltaic system must
be connected to the PE of the drive.
4.11 AC grid connection
4.11.1 More than one source of supply
It is not recommended to supply the drive
simultaneously from the photovoltaic cell and from
grid.
4.11.2 Toggle between AC and DC
If both the DC input and the AC input are used (for
example, when the energy from the photovoltaic
system is not sufficient), it is not allowed to switch
directly between AC and DC supply. When switching
from one supply to the other, it is mandatory to wait
until the drive is discharged.
The minimum AC-DC switchover delay is 30 s for RSI
A-C and RSI MR5-MR6.
The minimum AC-DC switchover delay is 60 s for RSI
MR7-MR10.
DANGER
Electric shock
Death or serious personal injury
‐To completely isolate the equipment,
use a two-pole disconnect switch for
the photovoltaic input (suitable for DC)
and for the grid input (AC switch). Only
one of these switches is allowed to be
on at a time. The delay time must be
respected when changing from one
switch to the other.
DANGER
Electric shock
Death or serious personal injury
‐If it is necessary to connect the drive
simultaneously on AC and DC supply,
note that if the AC supply is lost, the
drive must be separated from the AC
supply grid.
4.11.3 Dual supply functionality
Sometimes a back up from the AC mains is needed in
case the power from the photovoltaic supply is not
enough, for example, during night time and cloudy
weather. The connection can be created in several
different ways. In this chapter, three alternative
solutions are described.
Common safety related topic in every solution is to
make sure that in case of possible malfunction of
drive there is no DC voltage connected into AC side.
DC voltage from photovoltaic system can make AC
supply side parts energized having dangerous
voltage, in case AC power is down. DC voltage can
go very far distance wise into AC side, as far as
galvanically possible. This can be very dangerous
especially during AC grid service. System must have
a way to prevent this happening.
Changeover switch
Using a manually operated changeover switch is the
most recommended way to make the switchover
between AC and DC supply. In this case, a digital
input can be programmed to select normal reference
when using AC supply or MPPT when using DC
supply. The changeover switch must have a potential
free auxiliary contact. See parameter P3.5.1.53 Mains
Supply On. In case of a failure, the changeover
switch also prevents the DC voltage from going into
the AC side.
AC and DC connected simultaneously without
control
In this case, there is no possibility to have any control
if AC or DC supply is used for energy source. Supply
always comes automatically from the source where
the voltage is higher. Therefore, photovoltaic
dimensioning is very critical. In addition to that, a
blocking diode on the DC side is needed to protect
solar panels in case their voltage is low. On the AC
side, function of the blocking diode is made by drive
rectifier diodes. However, in case of malfunction of
rectifier diodes also electromechanics separation is
needed in case AC supply goes down. It is mandatory
to separate the drive from AC supply in case of power
down. There are different methods to make the
separation. See one example in chapter Automatic
dual supply control.
Automatic dual supply control
This functionality can be used by activating the drive
relay output to control additional contactor on the AC
supply side. See the related programming in chapter
7.2.24. The functionality can have three different
operation modes:
• 0 - Always active (supply from AC and DC used
together)
Works in the same way as described in chapter
AC and DC connected simultaneously without
control, but AC supply is only used when the drive
is at Run state.
• 1 - Closed loop Irradiation
Controls the AC supply contactor based on
irradiation measurement on analog input.
• 2 - Closed loop Sensorless
Controls the AC supply contactor based on
periodic PV capacity checks.
20
English (GB)