GTE SYLVANIA SSPB 800 User manual

r
!
H
V
»
.
-
ii
i
•
i
*
’
>
•
n
/
4
;
•
-
rTT
,
1
<
i
si
'
1
'
ft
.
A
;
v
,
V
s
;
.
V
SSPB
•
N
<
4
’
«
*
.
1
>
J
*
t
i
»
POWER
CIRCUIT
BREAKER
INSTRUCTIONS
5
V i
,
i
w
'
4
'
•
1
*
£
4
]
*
r
m
n
>
.
V
I
V
’
'
*
m
<
f
-
-
W
/
B
/
«
»
i
V
^
r
WB
4
.
If
jj
1
\
SJS
.
7
*
*
-
.
-
X
1
.
r
*
4
-
"
‘
V
A
V
kff
:
*
sa
f
.
i
«
H
»
*
.
.
-
V
'
Li
*
V
t
3
«
u
1
<
|
r
4
/
A
\
K
i
•
II
"
>
•
*
INSTALLATION
OPERATION
MAINTENANCE
/
;
v
<
i
»
‘
•
i
A
£
i
vV
*
v
»
*
800
-
2000
AMPS
*
»
Sr
«
•
THE
BREAKER
THAT
LETS
YOU
CHANGE
ITS
MIND
(
3
D
syu
/
ANiA
H
i
I
If
;
V
.
'
!
rt
•
t
•
V
i
i
>
*
\
i
Courtesy of NationalSwitchgear.com

r
'
t
CONTENTS
e
*
o
#
I
,
Delivery
of
Equipment
1
.
Receiving
2
.
Installation
of
separately
shipped
elements
3
.
Storage
4
.
Handling
1
1
1
1
II
.
Operation
1
.
Manual
breakers
2
.
Electric
Breakers
3
.
Safety
tripping
4
.
Antt
-
pumplng
and
control
characteristics
.
,
5
.
Auxiliary
circuits
(
Cradle
/
Element
)
6
.
Auxiliary
circuits
{
Devices
)
7
.
Arrangement
of
cubicle
door
8
.
Static
sensors
,
9
.
Setting
static
trip
sensors
10
.
Current
sensors
11
.
Padlocking
12
.
Key
Interlocks
13
.
Devices
2
2
•
V
2
2
3
3
3
3
4
4
4
4
5
III
.
Maintenance
1
.
Frequency
of
inspnotlon
2
.
Arc
chutes
3
.
Poles
4
.
Breaker
pole
assembly
.
5
.
Auxiliary
contacts
.
.
.
6
.
Devices
.
7
.
Lubrication
0
6
6
6
.
*
7
7
7
IV
.
Adjustments
and
Inspections
8
-
12
V
.
Replacement
Procedure
13
*
16
VI
.
Replacement
Parts
List
17
*
19
VII
.
Tables
and
Curves
20
*
23
Courtesy of NationalSwitchgear.com

Y
'
i
y
••
i
<
-
u
INSTALLATION
-
OPERATING
-
MAINTENANCE
INSTRUCTIONS
SSPB
BREAKERS
800
-
1600
-
2000
AMP
FRAMES
i
The
complete
SSPB
line
encompasses
frame
sizes
from
800
to
4000
amperes
,
up
to
600
volts
A
.
C
.
Basic
sub
-
assemblies
Include
the
operating
mech
-
anism
,
contact
structures
,
arc
chutes
,
and
static
trip
device
.
The
operating
mechanism
offers
a
choice
of
either
manual
for
local
control
,
or
electrical
for
remote
operation
.
A
stored
energy
principle
of
operation
is
utilized
for
either
type
.
I
.
DELIVERY
OF
EQUIPMENT
•
'
i
-
i
1
.
Receiving
Each
shipping
section
of
switchgear
has
been
palletized
to
facilitate
moving
.
The
shipping
section
is
covered
with
a
transparent
plastic
cloth
to
inhibit
entrance
of
foreign
particles
and
permit
carrier
awareness
of
shipping
contents
.
Immediately
upon
receipt
of
equipment
,
examine
components
making
note
of
any
damages
incurred
in
transit
.
If
necessary
,
immediately
file
a
claim
with
the
delivering
carrier
and
notify
your
Sylvania
representative
.
CAUTION
:
The
drewout
breaker
elements
are
secured
to
their
cradles
installed
in
the
switchgear
assembly
.
In
order
to
withdraw
the
element
,
it
is
first
necessary
to
remove
the
two
bottom
shipping
bolts
holding
the
orange
shipping
plates
to
the
stationary
cradle
.
With
these
bolts
removed
,
the
breaker
may
be
cranked
(
counterclockwise
)
to
its
open
position
and
then
fully
withdrawn
.
In
the
withdrawn
position
,
the
remaining
four
shipping
bolts
and
orange
plates
should
be
removed
and
discarded
.
C
diate
use
must
be
stored
in
a
ventilated
room
anc
protected
from
dust
and
water
by
means
of
non
absorbent
covering
.
2
.
Installation
of
Separately
Shipped
Breakers
Insert
racking
handle
Into
cell
being
installed
with
breaker
and
turn
counterclockwise
until
cradle
is
in
withdrawn
position
.
White
lines
surrounding
collar
of
withdrawing
device
indicate
cradle
position
.
Three
white
lines
visible
ahead
of
cell
frame
or
front
of
closed
door
indicates
cradle
is
in
isolated
position
.
In
this
position
,
the
two
tele
-
scopic
rails
should
be
fully
withdrawn
to
accept
the
breaker
element
.
Remove
breaker
element
from
shipping
carton
in
the
manner
outlined
under
"
Handling
"
.
After
a
visual
inspection
for
damage
,
mount
element
on
rails
locating
holes
in
the
breaker
support
over
the
four
mounting
metric
bolts
(
8
mm
-
0.7
mm
thread
)
.
Secure
element
to
rails
with
lock
washers
and
8
mm
metric
nuts
using
a
13
mm
metric
wrench
or
Vi
inch
open
end
wrench
.
3
.
Storage
4
.
Handling
Although
the
SSPB
circuit
breakers
Include
hlgl
precision
components
,
they
will
only
remaii
reliable
if
handled
with
care
.
Never
rest
the
element
on
the
contact
jaws
.
Th
breaker
element
must
always
ba
laid
on
a
claar
flat
surface
either
upright
or
on
its
side
.
Th
breaker
can
be
easily
and
safely
transported
on
lift
truck
.
For
transporting
in
this
manner
,
a
palls
must
be
used
.
{
•
*
Toward
the
top
of
the
side
plates
of
the
break
*
element
,
lugs
{
two
on
each
side
)
are
provided
ft
lifting
.
Never
lift
element
by
its
contact
jaws
<
its
static
trip
sensor
box
.
1
C
r
immo
_
Courtesy of NationalSwitchgear.com

C
>
(
X
o
»
-
_
>
until
there
is
no
apparent
spring
resistance
*
to
-
the
operator
.
To
fully
charge
the
springs
manually
requires
approximately
15
reversals
or
oscillations
of
the
handle
.
The
control
panel
or
front
escutheon
differs
from
the
manually
operated
breaker
in
that
two
push
!
!
.
OPERATION
1
.
Manually
Operated
Breakers
With
the
manually
operated
SSPB
breaker
,
a
simple
rotary
motion
of
the
operating
handle
in
the
counterclockwise
direction
for
approximately
90
degrees
charges
the
springs
for
a
close
-
open
opera
-
tion
.
Rotation
clockwise
back
to
its
normal
vertical
position
initiates
the
spring
release
for
closing
.
The
closing
speed
is
completely
independent
of
the
operator
.
A
position
indicator
located
on
the
front
escutcheon
indicates
the
position
of
the
main
contacts
:
red
for
"
on
"
or
"
closed
"
,
green
for
"
off
"
or
"
open
.
The
breaker
may
be
tripped
manually
by
depress
*
ing
the
manual
trip
button
.
Through
linkages
,
this
action
causes
the
mechanism
trip
latch
to
be
dis
-
placed
collapsing
the
operating
springs
and
thereby
opening
the
breaker
contacts
.
If
breaker
is
equipped
with
a
lock
-
out
device
or
undervoltage
release
,
refer
to
paragraph
4
operating
instructions
.
(
buttons
are
furnished
,
one
for
initiating
closing
of
main
contacts
(
red
)
and
one
for
opening
(
green
)
.
In
addition
,
a
spring
indicator
is
Included
(
yellow
)
for
charged
,
and
(
black
)
for
discharged
condition
.
2
.
Electrically
Operated
Breakers
For
electrical
operation
,
a
fractional
horsepower
,
high
torque
gearmotor
provides
energy
for
charging
the
springs
.
Charging
requires
approximately
5
seconds
.
Recharging
takes
place
automatically
after
the
breaker
is
closed
.
A
limit
switch
removes
the
gearmotor
supply
voltage
at
the
end
of
travel
.
The
supply
voltage
at
the
motor
terminals
may
be
between
90
to
110
%
of
the
rated
voltage
.
After
the
springs
are
charged
,
the
closing
springs
are
held
by
an
electromagnetically
operated
latch
.
When
the
breaker
is
closed
by
depressing
the
manual
close
button
located
on
the
front
escutch
-
eon
the
closing
latch
Is
displaced
,
thereby
col
-
lapsing
the
springs
and
closing
the
main
contacts
.
This
action
is
initiated
with
remote
closing
by
energising
the
electromagnet
.
The
breaker
may
be
manually
tripped
locally
or
electrically
tripped
from
remote
locations
.
In
the
event
of
power
loss
,
it
is
possible
tn
manual
-
ly
charge
the
springs
of
an
electrically
operated
breaker
for
close
-
open
operation
.
The
emergency
operating
handle
is
identical
in
appearance
to
the
handle
used
on
manually
operated
breakers
.
The
method
of
spring
charging
differs
from
the
menual
-
hn
»
th
*
i
handle
Is
rotated
3
.
Safety
Tripping
If
the
breaker
is
inserted
or
withdrawn
with
its
main
contacts
in
the
closed
position
,
a
mechanical
linkage
automatically
trips
the
breaker
before
separation
of
the
main
contacts
during
withdrawal
or
before
closing
of
the
main
contacts
during
insertion
.
The
same
device
prevents
the
closing
of
the
breaker
between
positions
'
test
'
and
'
service
’
.
4
.
Anti
-
Pumping
and
Control
Characteristics
Anti
-
pumping
its
assured
in
both
the
local
and
remote
control
operations
.
If
the
local
close
button
is
held
depressed
or
a
remote
closing
signal
main
-
tained
,
it
will
be
necessary
to
interrupt
this
action
,
after
tripping
breaker
,
to
effect
a
subsequent
closing
.
If
tripping
is
a
result
of
overload
or
short
circuit
current
and
the
breaker
Is
equipped
with
a
local
reset
lockout
device
,
it
is
necessary
to
completely
depress
the
trip
button
in
order
to
effect
a
sub
-
sequent
closing
.
By
padlocking
the
local
trip
buttoh
in
a
depressec
position
,
it
is
impossible
to
close
the
breakei
»
h
*
istefi
holding
th
<
•
I
-
*
t
_
-
A
-
.
!
•
M
Courtesy of NationalSwitchgear.com

i
u
•
O
I
L
>
.
L
.
I
i
required
to
operate
electrically
operated
breaker
*
.
Two
of
these
terminals
are
made
continuous
through
the
test
-
service
position
In
order
to
pro
'
vide
power
for
the
spring
charging
motor
.
Tht
remaining
four
are
for
closing
and
tripping
.
charged
closing
springs
cannot
be
released
.
Maintaining
a
remote
tripping
signal
nullifies
any
remote
or
local
closing
action
.
It
is
possible
to
depress
the
local
close
button
causing
the
dosing
spring
to
release
;
however
,
the
main
contacts
will
not
close
until
the
remote
tripping
signal
Is
re
-
moved
.
Should
it
be
desired
to
prevent
accidental
closing
when
the
local
trip
button
is
released
,
an
undervoltage
release
device
with
lockout
must
be
used
for
remote
tripping
.
Where
electrically
operated
breakers
equipped
with
an
undervoltage
release
are
closed
by
a
constant
signal
,
there
are
two
possible
methods
of
operating
,
depending
upon
whether
the
closing
electro
-
magnet
and
undervoltage
release
are
energized
by
the
same
source
or
separate
sources
.
w
In
some
applications
,
it
may
be
necessary
tc
electrically
connect
the
breaker
in
the
cradle
.
service
position
differently
from
that
in
the
tes
'
position
.
This
can
be
accomplished
by
removing
the
test
or
service
terminal
.
After
the
fixed
second
ary
isolating
contact
block
has
been
removed
,
i
‘
is
only
necessary
to
remove
the
terminal
by
un
screwing
the
fixing
screw
and
breaking
the
bridge
between
the
test
and
service
contacts
at
the
necl
'
provided
for
this
purpose
.
To
protect
the
auxiliary
wires
from
physically
coming
in
contact
with
moving
parts
when
the
breaker
is
being
Inserted
or
withdrawn
,
an
enclosec
passage
,
located
8
t
the
point
of
exit
from
th
<
stationary
isolating
terminal
block
,
is
provided
.
Common
Source
:
Voltage
drops
-
breaker
trips
Voltage
restores
-
breaker
automatically
closes
Separate
Source
;
Voltage
drops
-
breaker
trips
Voltage
restores
*
breaker
re
-
mains
open
6
.
Auxiliary
Circuits
(
Devices
)
Auxiliary
contacts
may
be
added
as
an
accessory
either
on
electrically
or
manually
operate
<
breakers
.
A
built
-
in
time
differential
of
15
milli
seconds
is
available
between
contact
group
posi
tions
1
-
8
and
9
-
16
for
sequence
logic
.
Contac
positions
9
-
16
act
simultaneously
with
mail
contacts
.
/
The
closing
signal
must
be
momentarily
removed
in
order
to
reclose
the
breaker
.
If
a
closing
signal
is
maintained
even
when
the
closing
spring
is
dis
-
charged
,
the
breaker
will
automatically
close
at
the
completion
of
spring
charging
.
This
would
occur
where
voltage
is
applied
simultaneously
to
the
charging
motor
and
closing
electromagnet
.
The
latch
keeping
the
closing
spring
charged
cannot
be
released
if
the
breaker
is
in
the
closed
position
.
7
.
Arrangement
of
Cubicle
Door
The
cubicle
door
for
drawout
air
circuit
breake
elements
is
provided
with
an
opening
permittini
entry
of
the
control
board
or
front
escutcheoi
plate
.
A
.
retracting
collar
surrounding
the
escutch
eon
plate
permits
the
operator
to
rack
the
breake
element
from
the
service
position
to
the
test
o
fully
open
position
without
opening
the
cubic
!
door
.
It
is
,
therefore
,
possible
to
store
breaker
without
fear
of
unauthorized
personnel
havin
access
to
them
.
5
.
Auxiliary
Circuits
(
Cradle
/
Element
)
The
SSPB
breaker
can
be
equipped
with
a
maxi
-
mum
of
24
secondary
isolating
contacts
.
Each
con
-
tact
is
designed
to
accept
two
V
*
"
quick
disconnect
lugs
per
terminal
.
The
secondary
Isolating
blocks
may
contain
up
to
twenty
-
four
(
24
)
terminals
,
twelve
(
12
)
on
each
side
,
which
may
be
used
for
breaker
operation
and
alarm
circuits
.
Internal
wiring
of
breakers
is
num
-
bered
in
conformity
with
standard
wiring
diagrams
.
The
terminals
of
the
secondary
or
stationary
iso
-
lating
contacts
on
the
cradle
are
arranged
and
con
-
nected
In
a
manner
to
permit
interchangeability
of
similar
elements
.
8
.
Static
Seniors
Static
sensors
consists
of
separate
printed
circuit
for
long
time
,
short
time
,
instantaneous
,
am
ground
fault
tripping
.
Components
are
pre
-
age
»
and
factory
calibrated
to
Insure
utmost
trlppin
accuracy
.
No
field
calibration
is
.
required
.
Sine
cards
have
been
designed
for
plug
-
ln
field
installs
tlon
,
it
is
possible
to
change
systems
by
simpl
'
Siv
tArminafc
nf
the
sprnnHarv
iftol
&
ttno
block
are
Courtesy of NationalSwitchgear.com

•
_
H
ordering
cards
from
your
nearest
Sylvania
office
,
When
ordering
ground
fault
,
it
is
necessary
to
indicate
whether
the
system
is
three
or
four
wire
.
On
a
four
wire
system
,
a
neutral
CT
will
be
furnished
with
the
logic
card
.
This
CT
must
be
installed
in
the
neutral
bus
and
wired
to
the
10
.
Current
Sensors
Multi
-
ratio
window
type
current
transforms
mounted
at
the
rear
of
the
circuit
breaker
elemsi
provide
signal
source
for
the
static
trip
sensor
Since
these
sensors
for
initiating
breaker
trip
derh
all
necessary
energy
from
the
current
monitored
,
r
external
energy
source
is
required
.
(
Any
oth
<
accessory
for
breaker
tripping
must
be
provide
with
a
separate
power
source
.
)
To
change
tripping
range
of
breaker
,
transpose
o
«
wire
on
each
of
three
current
transformers
.
Terrr
nels
are
marked
to
indicate
primary
current
settin
When
making
this
change
on
a
four
wire
syste
with
ground
fault
indication
,
it
is
necessary
\
change
the
current
transformer
located
in
tf
neutral
bus
(
rear
of
switchboard
)
accordingly
.
breaker
in
accordance
with
included
instructions
.
The
ground
fault
logic
card
includes
a
retractable
target
that
indicates
tripping
under
ground
fault
conditions
.
11
.
Padlocking
Ail
SSPB
breakers
are
provided
with
means
fc
using
a
maximum
of
three
padlocks
(
1
/
4
"
to
3
/
8
shackels
)
to
lock
the
breaker
in
the
opened
c
tripped
position
.
To
apply
padlocks
,
it
is
necessar
to
place
the
breaker
in
the
tripped
position
b
depressing
the
local
trip
buton
.
While
holding
th
trip
button
depressed
,
withdraw
horizontal
ba
located
adjacent
to
trip
button
and
apply
padlock
!
With
this
bar
withdrawn
,
the
trip
button
is
held
ii
the
depressed
position
,
thereby
preventing
closing
.
9
.
Setting
of
Static
Trip
Sensors
In
order
to
prevent
damage
to
static
sensor
pins
,
the
following
procedure
should
be
followed
when
selecting
or
changing
sensor
settings
.
1
.
Loosen
two
bottom
screws
holding
trans
-
parent
plastic
shield
.
2
.
Raise
shield
to
clear
bolt
heads
and
lift
out
.
3
.
Select
values
of
sensors
desired
,
4
.
Place
thumb
and
forefinger
on
shorting
bar
end
pull
bar
forward
until
shorting
pins
are
cleared
,
5
.
Raise
or
lower
shorting
bar
to
pre
-
selected
sensor
value
,
12
.
Key
Interlocks
I
i
If
the
cradle
is
provided
with
a
key
interlock
,
thi
following
procedure
should
be
followed
for
lockini
the
breaker
out
:
Withdrew
breaker
element
to
fully
disconnec
position
by
turning
crank
counterclockwise
t
<
stop
.
(
This
operation
may
be
performed
witl
cell
door
ooened
or
closed
.
)
Turn
kev
ii
6
.
Return
shorting
bar
to
pins
until
fully
reseated
,
7
.
Replace
protective
shield
and
tighten
Courtesy of NationalSwitchgear.com

i
u
C
-
I
1
c
II
when
energized
by
a
voltage
source
of
65
%
tc
130
%
of
rated
voltage
.
An
auxiliary
contact
ir
series
with
the
coil
opens
and
removes
supply
voltage
when
breaker
is
open
.
*
'
cylinder
to
remove
.
If
key
will
not
rotate
in
cylinder
,
turn
cradle
crank
approximately
15
degrees
to
permit
alignment
.
When
stops
are
aligned
,
key
will
rotate
for
removal
.
With
this
interlocking
system
,
it
is
possible
to
re
-
move
the
element
from
the
cradle
for
either
maintenance
or
replacement
without
permitting
element
insertion
until
the
key
has
been
returned
to
the
key
cylinder
block
.
*
Undervoltage
Trip
(
U
.
V
.
)
When
the
voltage
sour
drops
below
30
%
of
rated
voltage
,
the
breaker
tripped
.
In
the
region
of
30
%
to
60
%
of
rah
voltage
,
tripping
may
or
may
not
occur
.
No
tri
ping
action
will
occur
when
the
supply
voltage
Shunt
Trip
(
S
.
T
.
)
This
device
will
trip
the
breaker
60
%
to
100
%
of
rated
voltage
.
13
.
Optional
Devices
Stationary
‘
Contacts
A
Arc
Chuta
*
»
7
.
Lifting
Lug
*
Control
Board
*
1
totld
State
Control
Trip
.
Button
Mowing
Secondary
»
IvOUting
Contacts
Manual
Hindu
*
Pofltlpn
*
indicator
Auxiliary
>
Contact
Block
*
i
Salary
fihuttar
{
optional
)
Fined
Bocondary
UoUtlng
1
Contact
!
f
<
i
\
Courtesy of NationalSwitchgear.com

I
“
sw
*
IH
.
MAINTENANCE
the
arc
.
This
operation
enables
doubling
the
of
the
arc
chutes
,
After
two
cycles
,
it
is
necess
to
replace
the
arc
chutes
.
1
.
Frequency
The
frequency
of
maintenance
depends
essentially
on
the
conditions
of
service
of
the
breaker
,
fre
-
quency
of
operation
,
fault
tripping
,
relative
humid
*
ity
,
or
presence
of
dust
.
The
mechanical
endurance
of
the
breaker
is
20
,
000
operations
with
the
main
contacts
being
guaranteed
for
the
life
of
the
breaker
.
Arc
chutes
and
the
arcing
contacts
are
guaranteed
a
minimum
of
1500
•
make
-
break
operations
at
the
nominal
current
and
voltage
(
0.2
to
unity
power
factor
)
,
10
make
-
.
break
operations
at
10
times
rated
current
,
or
3
make
-
break
operations
at
rated
short
circuit
.
To
insure
performance
,
it
Is
recommended
that
breakers
be
inspected
every
six
months
if
exposed
to
dust
,
every
3000
operations
or
every
six
months
if
left
idle
.
In
general
,
breakers
should
be
inspected
at
least
once
a
year
.
3
.
Poles
(
Fig
.
6
)
Insulating
barriers
are
located
on
each
side
of
arcing
area
for
each
pole
.
With
a
piece
of
clean
,
cloth
,
wipe
barriers
to
remove
any
deposits
.
o
2
.
Arc
chutes
(
Fig
.
5
)
Remove
arc
chute
by
depressing
or
raising
back
part
of
retaining
lever
61
and
rotating
clockwise
90
degrees
.
Lift
arc
chute
upwards
clearing
arcing
horns
.
Close
breaker
and
check
gap
setting
of
arci
horns
.
If
gap
exceeds
1.5
mm
(
0.059
inches
)
,
adji
contacts
by
loosening
bolt
#
VI
(
Fig
.
6
)
setting
g
to
0.9
mm
t
0.1
mm
(
0.035
t
0
,
004
inches
)
ai
tightening
bolt
by
torquing
to
0.8
mm
-
kg
.
(
5.8
l
ft
.
)
.
Remove
both
fixed
and
movable
arci
horns
along
with
insulating
barriers
when
thicknt
of
arcing
pads
erodes
to
approximately
0.5
m
(
0.020
inches
)
.
Main
contacts
may
have
spots
on
them
witho
affecting
the
breaker
.
These
contacts
can
l
cleaned
with
a
very
fine
emory
cloth
and
thoroug
ly
wiped
to
remove
any
particles
.
Do
not
replai
main
contacts
as
they
are
guaranteed
for
the
life
<
the
breaker
.
©
/
/
!
BBB
&
With
drawout
breakers
,
clean
the
main
isolatir
contacts
of
the
breaker
and
the
corresponds
cradle
contacts
with
a
piece
of
clean
cloth
soake
in
trichlorethylene
.
Apply
a
light
coat
of
Sylvani
SSPB
-
01
grease
to
the
cleaned
surfaces
.
Fig
.
s
Wipe
the
insulating
surfaces
clean
with
a
dry
piece
of
doth
,
The
two
insulating
barriers
covering
the
inside
of
the
arc
chute
walls
may
be
blackened
.
In
that
case
,
they
can
be
wiped
clean
of
carbon
deposits
to
restore
them
to
their
original
quality
.
At
the
end
of
3000
make
-
break
operations
at
rated
current
,
or
10
times
at
rated
current
,
or
3
times
at
rated
short
circuit
,
it
is
recommended
that
the
4
.
Breaker
Element
Pole
Assembly
(
Fig
.
7
}
The
pole
assemblies
are
maintained
under
0
.
m
-
Kg
.
(
2.9
lb
.
-
ft
.
)
pressure
by
each
of
six
bolt
(
three
per
side
)
located
on
the
outside
surface
o
the
breaker
element
.
They
may
be
identified
a
i
-
_
a
.
»
Courtesy of NationalSwitchgear.com

B
i
A
:
0
*
t
A
•
•
*
Y
"
n
U
!
I
4
f
i
;
g
±
a
0
—
3
I
I
0
I
..
J
3
c
<
l l
L
J
Si
-
fts
.
a
£
tfi
>
.
vAfiNl
6
M
.
.
7
.
Lubrication
FI
®
.
7
A
breaker
normally
lubricated
and
operating
in
dust
-
free
and
non
-
corrosive
atmosphere
regular
over
a
period
of
two
years
can
undergo
its
norm
cycle
mechanical
endurance
without
any
lub
eating
.
As
such
ideal
service
conditions
are
hard
encountered
,
it
is
advisable
to
check
periodical
5
,
Auxiliary
Contacts
(
Fig
,
8
)
The
auxiliary
contacts
located
on
the
front
right
hand
side
of
the
element
should
not
be
cleaned
or
adjusted
.
A
faulty
relay
should
be
replaced
by
the
lubricating
,
particularly
when
unusual
ceosii
placing
the
breaker
contacts
in
the
closed
position
and
removing
hold
-
down
screws
V
3
.
Auxiliary
con
-
tacts
are
only
found
on
electrically
operated
breakers
as
a
standard
item
since
one
of
the
or
friction
is
observed
during
Inspection
.
All
rubbing
surfaces
(
metal
to
metal
)
are
to
I
lubricated
with
a
thin
film
of
high
-
tempcratui
high
-
pressure
lubricant
equal
to
Sylvania
SSPB
-
0
Hardened
grease
and
dirt
should
be
removed
I
use
of
trichlorethylene
solvent
.
The
main
sha
trip
rod
,
intermediate
manual
control
shaft
,
fre
return
charging
spring
and
gear
train
for
electric
operation
do
not
require
lubrication
since
they
a
contacts
are
required
for
isolating
the
shunt
trip
coil
when
the
breaker
is
open
,
(
m
6
,
Devices
Under
voltage
,
shunt
trip
,
and
solid
-
state
trip
devices
do
not
require
maintenance
.
In
case
of
provided
with
sealed
bearings
.
Do
not
lubricate
ar
releases
or
grounding
terminal
.
failure
,
replace
the
complete
device
.
'
v
Courtesy of NationalSwitchgear.com

'
O
{
1
U
-
^
t
!
,
4.4
*
j
(
'
•
ri
•
i
L
-
L
.
«
_
/
/
B
.
CIRCUIT
BREAKER
1
.
Breaker
A
ssembly
(
Fig
.
10
)
a
.
Tightening
of
pole
assembly
Tighten
six
screws
(
1
)
painted
torquing
to
0.4
m
-
kg
{
2.9
AsBti
IV
.
ADJUSTMENTS
AND
INSPECTIONS
The
following
adjustments
and
inspections
were
performed
at
the
factory
following
installation
of
various
accessories
.
These
procedures
may
be
followed
for
field
adjustment
and
inspections
,
realizing
that
tolerances
are
based
upon
the
life
of
normal
mechanical
endurance
for
breakers
.
For
normal
service
,
the
limits
of
admissible
wear
has
been
included
.
When
these
limits
are
reached
,
it
is
necessary
to
either
readjust
the
components
to
the
dimensions
shown
,
or
to
replace
com
-
ponents
if
these
dimensions
cannot
be
met
.
A
.
CRADLE
ACCESSORY
1
.
Limit
switch
for
position
indication
(
1600
A
and
2000
A
frames
only
)
a
.
Service
position
(
Fig
.
9
)
.
Adjust
screw
(
10
)
to
insure
operation
of
the
limit
switch
3
mm
±
0.5
(
0.118
t
0.020
inches
)
before
the
service
position
stop
.
(
Eliminate
play
by
pulling
on
telescopic
rails
while
making
adjustments
.
B
A
r
i
=
i
3
c
J
Fla
.
to
«
£
p
VVlNJiB
-
2
.
Pole
(
Fig
.
11
)
a
.
Adjustment
of
arcing
contacts
With
breaker
In
closed
position
,
bolt
(
3
)
and
gap
arcing
contacts
<
3
A
O
w
0
a
o
O
o
#
•
o
1
o
a
-
*
l
o
©
II
0
Flo
.
11
Fig
.
9
b
.
Test
position
Adjust
the
support
(
11
)
and
the
two
screws
(
12
)
to
insure
the
operation
of
the
limit
switch
3
mm
(
0.118
Inches
)
before
the
test
position
in
the
direction
of
withdrawal
.
(
Eliminate
play
by
pushing
on
rail
while
making
adjust
-
ment
)
.
c
.
Isolated
position
Adjust
the
support
(
11
)
and
the
two
screws
(
12
)
to
insure
operation
of
the
limit
switch
2
mm
(
0.079
inches
)
before
the
stop
of
the
isolated
position
.
(
Eliminate
play
by
pushing
on
rail
when
making
adjustments
)
.
±
0.1
mm
(
0.035
t
0.004
ir
Tighten
bolts
torquing
to
0.9
(
5.8
lb
.
-
ft
.
)
.
NOTE
:
All
arcing
contacts
of
th
<
pole
must
be
within
0.1
mm
inches
)
of
each
other
.
LIMIT
OF
WEAR
:
1.5
mm
inch
)
.
b
.
Torquing
requiraments
1
)
Flexible
braid
(
7
)
800
amp
—
0
.
B
m
-
kg
(
5.8
lbs
.
-
ft
.
)
1600
-
2000
emp
-
1.3
m
-
kg
(
9.4
lbs
.
-
ft
.
)
Courtesy of NationalSwitchgear.com

or
trips
.
Therefore
,
using
ho
restore
release
crank
to
its
reset
latched
position
.
3
.
Overload
and
short
circuit
release
a
,
Tripping
(
Fig
.
12
)
1
)
Adjustment
.
With
breaker
in
closed
position
and
release
reset
,
back
off
red
nut
until
nearly
all
threads
arc
exposed
.
Tighten
same
nut
until
distance
between
tripping
striker
(
11
)
di
'
il
luy
(
12
)
of
llte
ldU
.
li
(
13
)
shown
in
the
normal
position
is
1
t
0.5
mm
(
0.039
*
0.020
inches
)
.
b
,
Resetting
1
)
Breaker
equipped
with
signal
dication
with
memory
for
overlt
end
at
IUII
uiicuit
release
(
with
without
Indication
.
)
(
Fig
.
14
)
.
a
)
Adjustment
.
When
breakers
equipped
with
this
accessory
is
necessary
to
place
breakei
open
position
and
adjust
sci
(
16
)
to
effect
latching
the
lease
.
A
very
distinct
cl
Indicates
latching
.
To
insur
margin
of
safety
,
unscrew
^
eturn
.
b
)
Place
breaker
in
open
posit
and
check
to
see
that
1.5
r
(
0.059
inch
)
clearance
is
av
able
.
LIMIT
OF
WEAR
:
Nonlal
HEP
VARNISH
1
*
CIS
o
O
O
ID
IS
U
Fig
.
12
2
)
Inspection
.
Place
breaker
in
closed
position
and
check
to
see
that
there
is
a
minimum
clearance
of
0.5
mm
(
0.020
inches
)
between
the
tripping
striker
(
11
)
and
lug
(
12
)
of
the
.
latch
(
13
)
shown
in
the
normal
position
.
LIMIT
OF
WEAR
:
0.1
mm
(
0.004
inches
)
.
To
test
tripping
of
breaker
by
the
release
crank
,
place
a
wire
hook
as
shown
in
Fig
.
13
and
hold
while
applying
a
momentary
signal
of
12
-
18
volts
D
-
C
.
to
the
tripping
actuator
EX
.
When
release
un
-
latches
,
slowly
allow
release
crank
to
withdraw
until
breaker
trips
open
.
ing
.
EXTREME
POSITION
POSITION
L
ATf
-
HEO
QP
ftEStT
*
IT
O
,
o
o
,
i
5
-
i
«
HFfl
VAOM
-
SH
Fig
.
14
1
«
2
)
Breaker
equipped
with
signs
dication
on
overload
and
shor
cult
tripping
with
local
rest
(
Fig
'
s
16
end
16
)
.
a
)
Adjustment
.
Insert
wire
ho
<
shown
In
Fig
.
13
and
hoi
lease
crank
(
14
)
while
app
momentary
signal
of
9
-
18
DC
to
the
tripping
actuator
When
release
unlatches
,
sli
allow
release
crank
to
with
*
to
tripped
position
show
&
r
HpQK
13
NOTE
:
Restraining
release
crank
(
14
)
while
performing
this
test
results
in
the
blocking
of
resetting
m
4
P
lltUL
.
aL
.
1
«
Courtesy of NationalSwitchgear.com

tripped
position
and
the
crank
(
TO
)
resting
against
stop
(
20
)
,
adjust
link
(
21
)
to
allow
1
*
0.5
mm
(
0.039
t
0.020
inch
)
clearance
.
Press
the
local
trip
-
ping
pushbutton
(
23
)
while
adjusting
screw
(
24
)
to
effect
resetting
of
the
release
.
A
distinct
click
will
be
heard
when
the
release
crank
latches
.
Unscrew
one
turn
to
insure
a
morgin
cf
frafoty
in
ro
«
#
tting
.
K
>
SUiDMlAJ
FI
*
.
»
8
2
)
Inspection
.
Place
breaker
In
the
closed
position
and
inspect
to
see
that
a
minimum
of
0.5
mm
(
0.020
inch
)
exists
between
lever
(
28
and
lug
(
12
)
of
the
lever
(
13
)
shown
in
the
normal
position
.
LIMIT
OF
WEAR
:
0.1
mm
(
0.004
inch
)
.
Holding
the
striking
pin
(
29
)
as
illustrated
in
Fig
.
23
,
apply
rated
voltage
to
the
holding
coil
,
ptacing
'
release
bar
in
unlatched
position
.
Remove
voltage
and
allow
release
.
bar
to
slowly
withdraw
observing
b
)
Inspection
.
With
the
breaker
in
the
open
position
,
press
the
trip
button
(
23
)
Fig
.
16
and
check
travel
of
release
bar
.
Distance
between
maximum
position
of
reset
and
latch
should
be
0.5
mm
(
0.020
inch
)
.
Check
play
between
lever
(
24
)
and
adjustment
screw
(
24
)
for
a
minimum
of
0.2
mm
(
0.008
inch
)
.
Press
the
push
-
button
fully
to
check
for
a
minimum
clearance
of
0.2
mm
(
0.008
inch
)
between
lug
(
12
)
of
the
latch
(
13
)
and
the
bottom
of
the
slot
.
4
.
Voltage
Tripping
Devices
(
Accessory
)
A
.
Tripping
(
Fig
.
17
and
18
)
1
)
Adjustment
.
Place
breaker
in
open
position
and
unscrew
adjusting
reset
screw
(
30
)
.
With
release
bar
in
latched
on
position
resulting
from
breaker
being
in
open
position
,
adjust
linkage
(
26
)
to
provide
1
t
0
,
5
mm
(
0
,
039
*
0.020
Inch
)
between
lever
(
28
)
and
lug
(
12
)
of
HOQ
5
Courtesy of NationalSwitchgear.com

With
contact
blocks
removed
,
adjust
no
(
32
)
until
distance
shown
in
Fig
.
19
i
44.5
±
0.5
mm
(
1.753
i
0.020
inch
)
.
LIMIT
OF
WEAR
:
Overall
travel
of
auxil
iary
contact
should
not
exceed
0.1
mn
(
0.004
inch
)
.
6
.
Limit
switch
on
Trip
Rod
(
Accessoryj
Limit
switch
for
signal
indication
of
trip
ing
on
overload
and
short
circuit
.
A
.
Adjustment
(
Fig
.
20
)
.
Place
breaker
it
closed
position
with
overcurrent
an
short
circuit
release
bar
latched
.
Dr
form
strip
(
36
to
obtain
clearanc
between
strip
(
36
)
and
spring
pin
(
37
]
breaker
tripping
.
NOTE
:
In
order
to
prevent
block
-
ing
of
the
release
bar
from
being
reset
when
breaker
opens
,
it
is
necessary
to
return
release
bar
to
its
(
atched
position
by
means
of
the
hook
illustrated
in
Fig
.
23
.
B
.
Resetting
1
)
Adjustment
.
With
the
breaker
in
the
open
position
and
the
release
bar
latched
as
illustrated
in
Fig
.
14
,
adjust
screw
(
30
)
lengthening
link
-
age
until
stirrup
is
against
stop
(
29
)
,
then
back
off
Vi
turn
.
2
)
Inspection
.
Place
breaker
In
latched
position
as
illustrated
In
Fig
.
18
.
Check
for
minimum
clearance
of
2
mm
(
0.079
inch
)
.
LIMIT
OF
WEAR
:
Non
-
Latching
Flfl
,
20
B
.
Inspection
.
Check
operation
of
micro
switch
by
tripping
breaker
.
7
.
Limit
switch
on
voltage
release
<
Accessory
)
The
undervoltage
release
device
can
b
<
equipped
with
two
separate
limit
switches
One
will
indicate
when
the
undcrvoltag
release
bar
is
latched
and
the
other
wil
indicate
undervoltage
coil
being
energized
.
A
.
Limit
switch
for
Latch
Indication
.
Plac
bar
in
latched
position
as
shown
ii
Fig
.
17
and
18
.
In
this
position
,
th
limit
switch
contacts
will
be
closac
Deform
strip
(
38
)
Fig
.
21
to
provide
.
maximum
gap
setting
of
1
mm
(
0.03
!
inch
)
between
strip
(
38
)
and
lug
(
39
)
NOTE
:
This
adjustment
must
be
pei
formed
without
applying
voltage
to
th
undervoltage
holding
coil
.
Followin
adjustment
,
operate
voltage
reieas
device
permitting
release
bar
to
ur
latch
.
Inspect
limit
switch
to
see
tha
contacts
open
.
5
.
Auxiliary
Contact
Block
Support
Adjust
•
mant
(
Fig
.
19
)
.
4
«
,
i
?
?
'
1
^
Efif
*
4
|
37
I
91
Pi
*
21
hr
rs
-
T
ri
99
Courtesy of NationalSwitchgear.com

8
.
Limitswitch
for
Vollay
*
limitation
.
This
limitswitch
has
no
adjustments
.
Check
position
of
contacts
by
applying
and
removing
voltage
to
holding
coil
of
solenoid
.
8
.
dosing
Adjustment
Electrically
Operated
Breakers
A
.
Adjustment
(
Fig
,
22
)
.
Placo
breaker
in
tripped
position
with
closing
springs
fully
charged
.
Adjust
screw
(
44
)
to
obtain
4
*
0.5
mm
(
0.158
t
0.020
inch
)
clearance
between
lever
(
46
)
and
end
of
screw
(
44
)
.
Adjust
screw
(
46
)
on
trip
button
for
4
t
0.5
mm
(
0.158
±
0.020
inch
)
clearance
between
strip
(
47
)
and
screw
end
(
46
)
.
NOTE
:
Breakers
fitted
with
a
D
.
C
.
electromagnetic
for
closing
have
a
series
resistance
(
economizer
)
which
is
placed
in
series
with
the
coil
,
after
pickup
,
thereby
reducing
current
consumption
to
a
minimum
.
To
adjust
,
hold
1
mm
(
0.039
inch
)
gap
setting
of
the
electro
-
magnet
and
deform
limitswitch
strip
until
contacts
close
.
luni
.
Applying
voltage
to
the
relay
allows
lever
(
58
)
to
come
into
contact
with
adjusting
stop
(
60
)
.
Adjust
stop
(
60
)
for
a
clearance
of
0.6
t
0.4
mm
(
0.024
±
0.016
inch
)
.
Remove
voltage
,
allowing
lever
(
59
)
to
rise
,
check
for
clearance
of
0.1
mm
(
0.004
inch
)
between
lever
(
50
)
ond
pin
*
w
(
61
)
.
LIMIT
OF
WEAR
:
0.1
mm
(
0.004
inch
)
©
0
,
*
9
.
Tripping
-
By
L
ocal
Mechanical
Pushbutton
.
If
the
breaker
is
fitted
with
a
signol
system
for
overload
and
short
circuit
tripping
with
local
reset
,
adjustments
should
be
carried
out
as
previously
outlined
.
In
other
cases
,
adjust
screw
(
24
)
{
Fig
.
24
)
for
obtaining
clearance
of
2
+
0.5
•
0.0
mm
(
0.079
+
0
:
158
inch
)
between
strip
(
26
)
and
the
end
of
the
screw
(
24
)
.
44
l
'
/
3
H
<
9
>
t
V
>
!
Plfl
.
22
B
.
Anti
-
Pumping
Inspection
.
Mechanically
operated
breaker
.
Oepress
trip
button
and
hold
while
charging
and
unlatch
closing
springs
.
Breaker
contacts
must
remain
open
.
Electrically
operated
breaker
.
Close
breaker
by
depressing
local
close
button
and
allow
gear
motor
to
charge
stored
energy
springs
.
While
holding
close
button
depressed
,
depress
trip
button
.
Breaker
must
trip
and
remain
tripped
until
close
button
is
released
for
next
cycle
of
operation
,
C
.
Undervoltage
lockout
(
Fig
.
23
)
.
When
the
undervoltage
release
is
provided
with
lockout
to
prevent
breaker
re
-
closing
upon
voltage
restoration
,
the
m
©
©
iMMtOJOiO
Fig
.
24
12
.
Courtesy of NationalSwitchgear.com

!
*
•
•
*
V
.
"
REPLACEMENT
PROCEDURE
A
.
Arc
Chute
(
Fig
.
25
)
.
To
remove
arc
chute
,
raise
retaining
lever
(
61
)
,
rotate
lever
90
degrees
to
clear
path
,
and
remove
arc
chute
by
lifting
upwards
.
The
reverse
procedure
is
followed
for
repositioning
ere
chutes
,
making
sure
the
respective
arc
chutes
fit
over
arcing
horns
(
62
)
.
2
.
Insulating
strips
.
When
replacing
contacts
,
it
is
recommended
that
the
insulating
strips
be
replaced
also
.
Using
a
screwdriver
,
remove
two
fasteners
(
4
)
retaining
in
-
sulating
strip
(
3
)
,
Replace
strips
using
new
fasteners
.
C
.
Auxiliary
Contact
Block
(
Fig
.
27
)
.
When
removing
contact
blocks
(
1
-
4
)
,
place
breaker
in
closed
position
before
loosening
contact
cradle
bolt
V
3
.
Slide
cradle
free
of
V
3
and
remove
contact
assemblies
,
To
replace
contact
blocks
,
reverse
procedure
making
sure
wires
turned
to
their
original
positions
.
The
same
procedure
is
followed
for
removing
or
replacing
contact
blocks
6
-
8
,
except
the
breaker
is
placed
in
the
open
position
,
are
rc
-
Flfl
,
25
1
I
)
B
.
Arcing
Contacts
and
Insulating
Strips
(
Fig
.
26
)
.
1
.
Arcing
contacts
.
With
breaker
In
open
position
,
loosen
retaining
bolts
VI
and
remove
contact
by
sliding
forward
.
Replace
with
new
contact
leaving
retaining
bolt
VI
loose
.
Close
breaker
and
loosen
bolt
V
2
(
two
per
contact
)
approximately
1.5
mm
(
0.059
inch
)
or
until
contact
clears
locating
boss
E
,
then
remove
by
lifting
upwards
.
Replace
with
new
contact
,
checking
to
see
that
contact
seats
in
locating
boss
before
tightening
bolt
V
2
.
With
0.9
mm
(
0.035
inch
)
feeler
gauge
,
position
contact
(
1
)
and
tighten
bolt
VI
.
i
Ifsl
:
Fl
*
.
27
D
.
Overload
and
/
or
Short
Circuit
Release
.
Remove
wire
*
from
plu
*
(
+
)
and
minus
(
-
)
terminals
on
solid
-
state
control
panel
located
on
front
of
breaker
element
.
Place
breaker
in
closed
posi
-
tion
and
apply
an
IB
volt
DC
9
millisecond
pulse
to
plus
and
minus
wires
going
to
EX
trip
actuator
.
I
With
voltage
applied
,
breaker
should
trip
.
Repeat
procedure
,
reducing
voltage
in
Incre
-
ments
until
12
volts
DC
Is
reached
.
At
this
level
,
breaker
should
not
trip
.
Do
not
attempt
to
adjust
actuator
.
{
Test
sets
are
available
as
an
accessory
for
rh
»
*
If
2
[
vi
O
KA
It
CCDO
k
Courtesy of NationalSwitchgear.com

Br
~
®
-
o
Flfl
.
28
E
.
Undervoltage
and
Shunt
Trip
Release
(
Fig
.
28
)
.
To
remove
trip
device
(
8
)
,
place
breaker
in
open
position
and
remove
coil
wires
from
terminal
block
(
81
)
located
on
rear
of
breaker
.
By
removing
pin
(
86
)
and
muuniiny
nuis
(
82
)
,
the
device
may
be
removed
.
When
replacing
trip
device
,
lubricate
and
adjust
as
described
in
Chapter
IV
under
Voltage
Tripping
Devices
.
F
.
Secondary
isolating
Contact
Block
(
Fig
.
29
)
.
Removal
of
contact
block
is
accomplished
by
removing
wiring
and
mounting
screws
illustra
-
ted
in
Fig
.
29
.
H
.
Closing
Solenoid
(
Fig
.
31
,
32
)
.
Slide
coil
and
housing
from
plunger
(
Fig
.
31
)
after
removing
coil
wires
from
terminal
block
(
4
)
and
four
mounting
bolts
(
11
)
.
(
Fig
.
32
)
If
breaker
is
equipped
with
closing
preventer
which
would
be
mountkl
adjacent
to
the
closing
solenoid
,
the
coil
and
housing
cannot
slide
sideways
.
It
is
.
G
.
Motor
(
Fig
.
30
)
.
To
gain
access
to
motor
,
remove
(
3
)
.
After
removing
wires
from
terminal
block
(
4
)
and
mounting
nuts
(
6
)
,
lift
motor
from
gear
train
.
When
replacing
motor
,
check
to
see
that
clearance
exists
between
pinion
and
gear
.
No
further
adjustment
is
required
after
motor
is
protective
cover
(
5
)
held
by
two
bolts
Courtesy of NationalSwitchgear.com

I
1.1
therefore
,
necessary
to
remove
horseshoe
retain
-
ing
washer
(
8
)
and
linkage
pin
from
plunger
so
complete
assembly
may
be
lifted
out
.
Coil
may
be
removed
from
housing
as
illustrated
in
Fig
.
31
.
When
replacing
,
make
adjustments
03
dc
scribed
in
Chapter
IV
,
Voltage
Tripping
Devices
.
shown
.
When
replacing
limitswitch
,
follow
adjustment
instructions
outlined
In
Chapter
IV
,
Limit
-
switch
On
Trip
Rod
.
r
k
0
G
s
rtfs
>
G
-
©
X
-
G
e
B
X
'
©
0
©
©
Closing
Preventer
(
Fig
.
32
)
.
The
closing
pre
-
venter
(
19
)
located
directly
behind
the
closing
solenoid
,
may
be
removed
by
removing
coil
wires
and
two
holddown
bolts
from
base
(
5
)
.
When
replacing
closing
preventer
,
make
adjust
ments
as
described
in
Chapter
IV
,
Undervoltage
Lockout
.
I
.
(
m
J
.
Fixed
Secondary
Isolating
Contact
Plocks
(
Fig
.
33
)
.
Removal
of
blocks
may
be
simplified
L
-
by
removing
three
screws
(
1
)
in
wire
guard
and
removing
holddown
screws
(
2
)
as
illustrated
.
Undervoltaga
and
Shunt
Trip
Limitswitch
*
(
Fig
.
35
)
.
,
1
.
Limitswitch
for
trip
indication
.
To
remo
\
the
limitswitch
(
28
)
for
indicating
trippir
by
undervoltage
or
shunt
tripping
,
brea
connections
and
remove
screws
(
178
!
When
replacing
limitswitch
,
follow
adjus
ment
Instructions
outlined
In
Chapter
l
\
Limitswlich
On
Voltage
Wen
*
#
.
©
0
©
©
0
G
z
nrwygnc
;
Qj
FI
*
.
33
L
K
.
Limitswitch
for
Fault
Indication
(
Fig
.
34
)
.
The
limitswitch
for
fault
indication
located
on
the
underside
of
the
element
may
be
removed
by
*
1
iit
Courtesy of NationalSwitchgear.com

2
.
Limitswitch
Operating
on
Undervoltage
.
Limitswitch
{
29
)
used
to
indicate
voltage
being
applied
to
holding
coll
of
solenoid
may
be
removed
by
breaking
connections
end
removing
screws
(
43
)
,
When
replacing
limitswitch
,
move
arma
-
ture
of
solenoid
to
see
that
limitswitch
does
not
prevent
solenoid
from
closing
.
Adjustment
may
be
made
by
bending
limitswitch
lever
.
0
(
i
t
1
*
»
(
I
*
Courtesy of NationalSwitchgear.com

L
H
*
c
*
t
^
i
_
<
•
J
«
.
121
REPLACEMENT
PARTS
<
ictoMlflcatton
Quantify
Raqulrad
Ripiaflarmnl
Part
No
,
OMcrlptlon
Part
Franwf
1600
Figure
No
.
2000
600
1
a
630
-
2000
-
0071
12
12
Fixed
arcing
-
contact
0
6
2
12
12
Moving
arcing
-
contact
636
-
2000
-
0072
9
6
5
630
-
0600
-
0060
3
Arc
-
chute
66
536
-
2000
*
0060
3 3
Arc
-
chute
15
536
*
0000
-
0006
1
Ex
-
Tripping
Actuator
1
1
27
10
2
NO
+
2
NC
Auxiliary
Contacts
636
-
0000
*
0210
30
15
536
-
2000
-
0033
Motor
-
48
V
AC
-
DC
30
15
Motor
-
110
V
AC
-
DC
536
-
2000
-
0030
1
1
i
30
15
1
536
-
2000
-
0034
1
Motor
-
125
V
AC
-
DC
30
15
1
Motor
•
220
V
AC
-
DC
636
-
2000
0031
1
15
30
1
536
-
2000
-
0035
1
Motor
-
240
V
AC
-
DC
31
16
Electromagnet
110
V
80
Cy
1
1
536
-
2000
-
0040
31
16
1
Electromagnet
230
V
60
Cy
536
2000
-
0041
1
31
Electromagnet
125
V
DC
16
1
536
-
2000
-
0044
1
31
1
Electromagnet
240
DC
1
530
2000
-
0045
16
1
1
Electromagnet
48
DC
31
16
536
-
2000
-
0043
r
Courtesy of NationalSwitchgear.com

i
VI
.
REPLACEMENT
PARTS
-
CONTINUED
MiflicimMi
Part
No
.
D
*
Mrl
|
M
4
«
n
PI
No
.
r
>
Koy
Interlock
for
Draw
-
out
ACB
Printed
Circuit
Board
*
long
time
Printed
Circuit
Board
-
ihort
time
Printed
Circuit
Board
•
Inttantarveou
*
Printed
Circuit
Board
•
ground
fault
Solid
State
Relay
without
Cards
Safety
Shutter
•
BOO
A
Safety
Shutter
-
1600
A
Safety
Shutter
•
2000
A
Flexible
Crank
Standard
Crank
Shunt
Trip
Device
-
110
VAC
Shunt
Trip
Device
-
220
VAC
Shunt
Trip
Device
*
460
VAC
Shunt
Trip
Device
-
48
VDC
Shunt
Trip
Devtee
•
126
VDC
Shunt
Trip
Device
*
240
VDC
Undervoltage
Trip
Device
-
110
VAC
Undervoltage
Trip
Device
•
220
VAC
Undervoltegc
Trip
Device
-
460
VAC
Undervoltage
Trip
Device
•
46
VDC
Undervoltege
Trip
Device
-
126
VDC
Undervoltege
Trip
Device
240
VDC
Undervoltege
Time
Deity
Devtee
•
110
VAC
Undervoltage
Time
Daley
Devtee
•
220
VAC
Undervoltage
Time
Deley
Devtee
•
400
VAC
Undervoltege
Time
Deley
Dev
lot
•
40
VDC
Undervoltege
Time
Deley
Device
•
125
VDC
Undervoltege
Time
Delay
Davlca
•
240
VDC
Not
Shown
636
-
•
0500
3
536
-
0000
-
0002
3
636
-
00000003
636
-
0000
-
0004
3
630
-
0000
-
0005
3
636
-
0000
-
0001
4
636
-
0003
-
0020
636
-
1603
-
0020
636
-
2003
-
0020
1
1
Not
Shown
636
-
2000
-
0091
Not
Shown
636
-
2000
-
0090
536
-
0000
-
0100
26
8
636
-
0000
-
0101
8
28
636
-
0000
-
0102
2
$
6
638
-
<
103
8
28
4
638
-
0000
-
0104
8
28
836
-
0000
-
0108
8
26
6304
)
000
-
0110
8
28
6300000
-
0111
8
28
63600000112
8
28
'
63000000113
53000000114
8
28
28
8
5300000
-
0115
63000000120
28
8
8
28
63600000121
0
28
83600000122
8
28
63600000123
6
28
63600000124
28
0
63600000126
.
•
8
28
Courtesy of NationalSwitchgear.com
Other manuals for SSPB 800
1
This manual suits for next models
4
Other GTE SYLVANIA Circuit Breaker manuals