Guardian SCC-50 User guide

Page 1
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
GUARDIAN
SCC-50(AQUAT)
Screw Compressor Controller
•Compressor status monitor with pressure, temperature, slide and load
displays
•Control by suction or remote pressure setpoint
•Control by suction equivalent or chiller temperature setpoint
•Alarm and trip monitoring with optional motor winding temperatures
•Compressor, pump, slide and speed control
•Economiser, heater and liquid injection control
•Automatic volumetric slide control via optional stepper motor
•Multiple compressor system control
•Local panel operation and set-up with optional remote pushbutons operation
•MODBUS communications for remote monitoring and set-up
•xx
•.
Operation and Setup Manual
GUARDIAN SCC-50 Screw Compressor Controllers provide suction pressure
setpoint control and alarm monitoring for one screw compressor. Alternatively the unit may
be set-up to control on water chiller, glycol chiller or equivalent temperature.
The SCC50 unit supersedes its SCC40 predecessor and provides increased response,
input/output signal capability, control and communication facilities.
The SCC50 still uses the SCC40 operator control Panel.
GUARDIAN
Tel. +44 (0) 1270 760599
Fax. +44 (0) 1270 766804
Email: [email protected]
www.Guardian-controls.com

Page 2
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Contents
SCC-50.....................................................................................................1
GETTING STARTED................................................................................5
BUTTON OPERATION SHORTHAND.................................................................................6
HARDWARE CONFIGURATION CHECKS.........................................................................6
CONFIGURE UNIT MODEL, SYSTEM No & ADDRESS ....................................................7
Enter Passcode.................................................................................................................7
Select Unit Model..............................................................................................................7
Select System No and Address.........................................................................................8
RS485 Communications ...................................................................................................8
UNIT MODELS.........................................................................................9
OVERVIEW ..........................................................................................................................9
Functions...........................................................................................................................9
Displays...........................................................................................................................10
Pushbuttons. ...................................................................................................................10
GENERAL SPECIFICATION..............................................................................................12
Consultant Mimic Format SCC-50 Standard .................................................................13
AVAILABLE UNIT MODELS..............................................................................................14
SCC-50 Input/Output Signals.........................................................................................15
SCC50 Fuse Ratings ......................................................................................................16
SCC50 FUSES and LED LAYOUT .................................................................................17
SCC-50 Termination Wiring -..........................................................................................18
Old Model SCC-40 Termination Wiring -.........................................................................19
SCC50-Auto VI Stepper Motor wiring..............................................................................20
SCC50 8-X Extension - Terminal Connections for Hazardous Area Panel....................21
SCC-50 Motor Monitor Temperature Signals.................................................................22
SCC-50 Motor Monitor Temperature Wiring...................................................................22
OPERATION..........................................................................................23
SCC40 PANEL LAYOUT ...................................................................................................23
LED LAMPS....................................................................................................................24
SYSTEM STATUS DISPLAYS........................................................................................25
SAFETY TRIP INDICATIONS.........................................................................................29
DISPLAY PUSHBUTTON OPERATION.........................................................................30
‘view’ ...............................................................................................................................30
‘type’................................................................................................................................30
CONTROL PUSHBUTTON OPERATION..........................................................................32
“mode”.............................................................................................................................32
“Mode-MANUAL”.............................................................................................................32
“Mode-AUTOMATIC”.......................................................................................................32
“RESET”..........................................................................................................................32
“Call Frig Engineer”.........................................................................................................33
“stop”...............................................................................................................................33
“start”...............................................................................................................................33
“Lower”............................................................................................................................33
“Raise”.............................................................................................................................33
SETTINGS CHANGE PUSHBUTTON OPERATION.........................................................34
“next”...............................................................................................................................34
“Accept”...........................................................................................................................34
“raise”..............................................................................................................................34
“Lower”............................................................................................................................34

Page 3
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
“RESET”..........................................................................................................................34
ALARM ACCEPT AND RESET PUSHBUTTON OPERATION.........................................35
SETPOINTS .......................................................................................................................37
CONTROL MODES............................................................................................................39
GENERAL.......................................................................................................................39
i) MANUAL ......................................................................................................................39
ii) LOCAL AUTOMATIC...................................................................................................39
iii) REMOTE AUTOMATIC..............................................................................................39
SCC50 8-X EXTERNAL CONTROL PANEL OPERATION...............................................40
CONTROL..............................................................................................42
COMPRESSOR CONTROL OPERATION.........................................................................42
POWER UP.....................................................................................................................42
READY/WAITING ...........................................................................................................42
STARTING......................................................................................................................43
RUNNING .......................................................................................................................44
STOPPING......................................................................................................................46
MODES CHANGES ........................................................................................................46
TWO SPEED MOTOR CONTROL.....................................................................................47
MANUAL MODE 2-SPEED.............................................................................................47
VARIABLE SPEED MOTOR CONTROL...........................................................................47
TWO COMPRESSOR-SINGLE MOTOR OPERATION.....................................................49
SET-UP OF AUTO VI.............................................................................50
Auto VI Operation:............................................................................................................50
Procedure..........................................................................................................................51
Auto VI Commissioning Parameters...............................................................................52
TIMER SETPOINTS ...........................................................................................................54
SETUP ...................................................................................................56
Compressor Settings........................................................................................................56
Unit Settings:...................................................................................................................56
System Settings ..............................................................................................................58
xxxxx...............................................................................................................................59
Analog.............................................................................................................................60
PT....................................................................................................................................60
Test.................................................................................................................................61
Done................................................................................................................................61
TWO SPEED MOTOR CONTROL SELECTION ............................................................62
MOTOR TEMPERATURE MONITOR SETUP...................................................................63
Motor Temperature Monitor Setup Selection ..................................................................63
Motor Temperature Monitor DISPLAY & ALARM LIMITS...............................................64
TRANSDUCER SETUP & CALIBRATION.....................................................................65
COMMUNICATIONS..............................................................................69
MONITOR HIGHWAY MODBUS COMMUNICATIONS.....................................................69
MODBUS REGISTER ALLOCATION .............................................................................70
MODBUS FORMAT TYPES............................................................................................71
MODBUS SYSTEM SETTINGS ADDRESS ...................................................................72
CONTROL HIGHWAY COMMUNICATIONS.....................................................................73
Control Highway Communication Wiring.........................................................................74
MAIN SET-UP/ COMMISSIONING PARAMETERS..............................74
Setup / Commissioning Parameters ...............................................................................79
PRESSURES..................................................................................................................79
TEMPERATURES...........................................................................................................80

Page 4
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
EQUIVALENTS...............................................................................................................80
DIFFERENTIALS ............................................................................................................81
TIMERS...........................................................................................................................82
Settings display and change facilities............................................................................83
SCC-50 Enclosure wiring: for trips negative..................................................................85
SCC-50 Enclosure wiring: for trips positive...................................................................86
Standard Wallbox Internal wiring.....................................................................................87
Standard SCC 40 Drawing..............................................................................................88
FITTING NEW EPROM..........................................................................89
Index ..................................................................................................................................90

Page 5
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
GETTING STARTED
Guardian Controllers provide refrigeration engineers with
•ACCURATE CONTROL
•ULTIMATE FLEXIBILITY
•ASSURED MONITORING
•RELIABLE ALARMS
This manual provides refrigeration designers, installers, service mechanics and supermarket
personnel with the necessary information to achieve the above objectives.
All users require to know a few basic facts about this controller before successfully starting to
perform their design, commissioning, maintenance or operating functions.
a) All GUARDIAN controllers need to be set up with a unit model selection and other basic
settings for setpoints, timers and addresses.
b) The shorthand used in the following chapters for concisely expressing button pressing and
selection sequences to do all this set-up needs to be understood.
c) Mains power input voltage and hardware switch and link option selections (if any are
required) must correspond to the selected unit model configuration.
d) Since each controller can be configured in a number of different ways to perform flexible
refrigeration control then an understanding of how to find out what unit model is currently
selected, what it does and how it is connected, is also necessary.

Page 6
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
BUTTON OPERATION SHORTHAND
To assist in easy set-up of control setpoints, delays, timers and other configuration settings,
the sequence of button presses and subsequent displays will be shown in this handbook as
below:
ii) A button symbol, followed by text means press that button. “@accept”
iii) A double button, followed by text means press that button repeatedly. “@:@raise”
iv) A display box with the window above it shows the result of the last button press on
the display.
DISCHARGE FILTER
==== 2.0b
“@:@raise”
DISCHARGE FILTER
==== 2.5b
v) DISCHARGE FILTER DISCHARGE FILTER
H.P. ==== trip ====
Means the display alternately flashes between identifier and trip message
HARDWARE CONFIGURATION CHECKS
Prior to switching on the GUARDIAN controller check that the hardware unit is the correct
type for the incoming mains voltage.
When satisfied that the correct type of controller is available then the following checks should
be made prior to controller installation or replacement
a) Ensure mains supply is wired correctly to the appropriate TERMINAL WIRING drawing for
the model selected.
b) Ensure that any transducer selector switches specified on the TERMINAL WIRING
diagram are in the correct state.
c) Ensure any shorting link selector pins specified on the TERMINAL WIRING diagram are
correctly fitted.
d) Ensure that probes are wired to the terminal WIRING DIAGRAM and the correct type of
thermistor or pressure transducer probes are fitted.
e) The RS485 highway connections (if required) are wired to the correct terminals and the
screen drain wire is continuous to earth.

Page 7
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
CONFIGURE UNIT MODEL, SYSTEM No & ADDRESS
Enter Passcode
Before any permanent change of controller settings are made then the correct entry of the
appropriate passcode is necessary.
The settings available for change on each passcode are as follows; Passcode
Passcode level 1 setpoints, low & high alarm settings 07
Passcode level 2 low & high trip settings and all level 1 09
Passcode level 3 system settings and levels 1 & 2 15
Enter passcode 15
DISCHARGE
FILTER “@view”= “SETPOINT” “@next” “@next”
pASS codE
DISCHARGE FILTER DISCHARGE FILTER
==-= ==12
“@:@raise” ==-= ==15 “@accept”
Press “view” to select “SETPOINT”, then press the “next” button twice to enter
the passcode settings.
Press “raise” repeatedly until passcode 15 is selected and then press “accept”
Select Unit Model
Enter Passcode as button sequence above.
“@:@view”= “SYSTEM”
SUCTION
OIL “@:@type”= “SAFETY TRIPS”
==sE tUP=
DISCHARGE FILTER
==== =yEs
“@accept”
DISCHARGE FILTER DISCHARGE FILTER
==== Unit
“@accept” ==== SC30
“@:@raise”
DISCHARGE FILTER
==== SC40
“@accept”
Press ‘view’ repeatedly until ‘SYSTEM’ is selected.
Press ‘type’ repeatedly until ‘SAFETY TRIPS’ is selected. Press ‘accept’
‘Unit’ is displayed press ‘accept’
Display shows unit model currently selected which may be wrong.
Press ‘raise’ repeatedly until correct model is displayed (e.g.SC30) and then press ‘accept’
which causes the display to wink briefly and display the new unit model selection
(e.g SC40 )

Page 8
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Select System No and Address
e.g. setup unit for system 65 compressor number 1 at address 195
Enter setup as button sequence as above
SUCTION OIL
==sE tUP=
DISCHARGE FILTER
==== =yEs
“@accept”
DISCHARGE FILTER
DISCHARGE FILTER
==== Unit
“@accept” ==== sC40 “@next”
DISCHARGE FILTER
DISCHARGE FILTER
==== Sn01
“@:@raise” ==== Sn65 “@accept”
DISCHARGE
FILTER “@next”
==== Cn01
“@accept”
DISCHARGE
FILTER “@next”
==== A=01
“@:@raise”
DISCHARGE FILTER
==== A195
“@accept”“@:@next”
DISCHARGE FILTER
==== donE
“@accept”
RS485 Communications
When the correct system number, case/compressor number and highway address have been
entered as above then the controller can communicate with the GUARDIAN Consultant
Terminal PC for central alarm monitoring and temperature display. Control setpoints, defrost
times and alarm limits may then be sent to the controller from the PC.
For further details see page 63

Page 9
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
UNIT MODELS
Guardian controllers may be configured in a number of different ways dependent on unit
model selection. Each unit model fulfils a different refrigeration temperature monitoring and
control requirement. In order to perform the required refrigeration control then each model
has different uses for the controller’s input output signals. This section gives details of all the
model variations available for the controller and the way to connect the wiring to the plant
devices and measuring transducers. OVERVIEW
Functions
The GUARDIAN SCC-50 controller provides facilities for:-
MONITORING
Measurement of pressures, temperatures, load and slide inputs for control, alarm and
trip display
Calculation of differential pressures and superheat temperatures for control, alarm and trip
display.
Detection of di
g
ital input states or safet
y
trip inputs.
ALARMS
Detection after a preset guardtime of pressure and temperature High/Low alarms when the
compressor is in operation. Alarms are indicated by alternating a =Hi= or =Lo=
message on the appropriate temperature or pressure display.
TRIPS
Detection of pressure and temperature High/Low trips which stop the compressor. Trips are
indicated by the flashing red TRIPPED lamp and an alternating 'TRIP' message on the
appropriate temperature/pressure display.
All measurement values are frozen after detection of a trip condition. This facility provides
information on the compressor state, pressures and temperatures when the trip occurred
until after the RESET pushbutton has been pressed.
Detection of safety trips which stop the compressor.
Trips are indicated by the flashing red TRIPPED lamp and an appropriate message.
Trips vary dependent on pack model configuration.
ie :- L.P. ,H.P. ,LEU=,fLo= alternating with a trIP message on the
appropriate display.
CONTROLS
Oil pump, motor and economiser startup and run sequences using preset timers and limits
Compressor status is indicated by LED lamps on the control panel.
Compressor capacity slide valve raise / lower control dependent on suction pressure or
slide control setpoint. The slide valve is automatically lowered when over-current limit or high
discharge pressure are detected or the compressor is stopped.
Suction pressure or slide control initiation of other compressors in the system via a RS485
link when in REMOTE mode.
Oil heater and liquid injection control on oil sump and discharge temperatures.
VI control using internal stepper motor control signals, condenser FAN control and extra
injection selection

Page 10
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Displays
i). SUCTION, DISCHARGE, OIL & FILTER.
SUCTION OIL
2.1b 11.7b
4-digit 7-segment LED displays for display of
measurements setpoints/limits for temperatures and
pressures
DISCHARGE FILTER
The contents change dependent on ‘view’ and
10.2b 11.5b ‘type’ selections
ii). CAPACITY%.
CAPACITY%
100
3-digit 7-segment LED displays for display of loading timers
and capacity.
iii). MOTOR LOADING%.
MOTOR LOAD%
105
3-digit 7-segment LED displays for display of timers and
motor load.
iv). COMPRESSOR No.
No
1
1-digit 7-segment LED display
Pushbuttons.
All pushbuttons are embossed, tactile membrane switches.
start, stop, raise & lowe
r
used to control compressors when in manual mode.
RESET used after a trip to reset the compressor.
Mode, view & type used in conjunction with appropriate LED displays to select
control, display or settings change facilities.
accept, next used in conjunction with raise, lower and appropriate LED
displays during setpoint and limit settings changes.
Unaccepted alarms and trips are acknowledged by pressing accept.
Pushbuttons on the local control panel permit operator display of setpoints, pressures,
temperatures, alarm and trip settings and compressor runhours and status.
Setpoints, alarm and trip settings may be changed from the panel after entry of the
appropriate passcode.

Page 11
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
The compressor may be selected to operate in one of three control modes:-
MANUAL, LOCAL or REMOTE MODES.
Safety interlocks, alarm, trip, startup and shutdown sequence controls are automatic in
all three modes.
In MANUAL mode, the each compressor may be individually started and stopped and the
pack capacity raised and lowered by operator pushbutton control from the local panel.
In LOCAL automatic mode, the compressor is started and stopped under control of the
suction pressure setpoint.
REMOTE automatic mode allows up to eight RCC-40 units to be connected via a two-wire
communication link (RS485) to provide 8-unit system control.

Page 12
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
GENERAL SPECIFICATION
Power 110 or 230 Vac 50 Hz 30VA (dependent on model type)
Operation 0 to 50ºC
Approx. Dimensions:
Control panel: 300 x 220mm
Control unit: 300 x 230 x 90mm
The GUARDIAN SCC-50 control unit comprises a printed circuit board xx for mounting at the
rear of the compressor pack control panel with the display unit mounted on the door and has
overall dimensions:- 300 x 230 x 90mm.
The unit is fitted with two-part screw-clamp terminals for the connection of the
appropriate input/output signals. (See input/output section)
The GUARDIAN SCC40 control panel comprises a membrane, pushbutton and display
panel mounted on the front of the control unit.
The membrane front panel has a Black background with white lettering and blue buttons with
dimensions 300x220mm.
A display panel membrane with text in Chinese Characters is now available.

Page 13
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Consultant Mimic Format SCC-50 Standard

Page 14
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
AVAILABLE UNIT MODELS
The Guardian SCC-50 controllers are available in two models, with the following options:
SCC-50 Standard
6 pressures
6 temperatures
xx
9 output relays
4 12V dc inputs
4 Mains inputs
8 Trips
2 Analogue outputs
1 Real time clock
xx
SCC-50 Auto VI
6 pressures
6 temperatures
9 output relays
4 Stepper Motor Control outputs
4 12V dc inputs
4 Mains inputs
8 Trips
2 Analogue outputs
1 Real time clock
8-X EXTENSION for REMOTE PUSHBUTTONs
8 remote pushbutton inputs.
local communication with SCC50 via 12C BUS connector.
SCC50 MOTOR TEMPERATURE MONITOR.
6 PT100 or PT1000 Temperature inputs
communication with SCC50 via RS485 control Highway.
SCC controllers powered at 110V ac are available on request but require to be set up prior
to delivery.
Guardian SCC50 Product Order Codes
MG0103 Guardian SCC 50 Standard Screw Comp Controller with AMPS
MG0104 Guardian SCC 50 AUTO VI Screw Comp Control with AMPS
MG0101 Guardian SCC 50 Motor Temperature Monitor Extension
MG0355 Guardian SCC 50 8-X Input Extension
Transducers
MT0116 Pres.Trans. 25ba, 4-20ma .
MT0200 PT1000 Resistance Therm. TI3974
MT0201 PT1000 100mm Probe Sen-0162c
MG0126 Stepper motor 7230 R11

Page 15
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
SCC-50 Input/Output Signals
Analogue inputs
An IP12 A1 Suction pressure 4 to 20mA -1 to 24 bar g
An IP 11 A2 Discharge pressure 4 to 20mA -1 to 24 bar g
An IP 10 A3 Oil pressure 4 to 20mA -1 to 24 bar g
An IP 9 A4 Filter pressure 4 to 20mA -1 to 24 bar g
An IP 8 A11 Remote pressure control or
vibration input 4-20mA
4-20mA -1 to 24 bar g
0 to 100%
An IP 7 future 4 to 20mA -1 to 24 bar g
An IP 4 A5 Suction temperature PT1000 -50 to 125°C
An IP 3 A6 Discharge temperature PT1000 -50 to 125°C
An IP 2 A7 Oil separator temperature PT1000 -50 to 125°C
An IP 1 A8 Oil heater temperature PT1000 -50 to 125°C
An IP 5 Chiller temperature PT1000 -50 to 125°C
An IP6 Future PT1000 -50 to 125°C
An IP 9 A9 Slide position potentiometer 0 to 10Vdc 0 to 125%
An IP 16 Slide position using Howden SPI (4-20ma) 4-20ma 0 to 125%
An IP 10 A10 Load current from AMPS Transducer 0 to 10Vdc 0 to 125%
An IP 15 Load current from xxx: 5A CT 0 to 5 AMP ac 0 to 125%
Digital inputs
Trip 1 Discharge temperature high dt-H
Trip 2 L.P. cutout L.P.
Trip 3 H.P. cutout H.P.
Trip 4 Oil level LEuL
Trip 5 Oil diff/ flow switch FLO
Trip 6 motor circuit breaker nncb
Trip 7 Emergency stop StoP
Trip 8 Safety (motor thermistor) SFtY
12/24V dc inputs
Input A Slide at 50%/ max demand unload
Input B Optional keyswitch
Input C Slide at minimum 0%
Input D Slide at maximum 100%
Mains inputs
Input E Oil pump running
Input F Compressor running
Input G Refrigeration (inhibit if Rneg)
Input H High setpoint/start
Input I External RESET pushbutton
Relay outputs
R1 Pump motor running 3 Amp inductive 110/240V ac with suppressers
R2 Compressor motor
R3 Slide valve load
R4 Slide valve unload
R5 Economiser
R6 Liquid injection
R7 Oil heater
R8 Injection 2 or Fans-1
R9 bypass valve or Fans-2
RA Alarm c/o contacts Not supressed ; if external relay fit suppressers
RB Compressor Trip c/o contacts Not supressed
Analog outputs
An OP1 Capacity control by variable speed motor 0 to 5V dc
An OP2 Motor control speed
Low power digit outputs
Dig OP C Not used 12vdc
Dig OP D Auto VI Stepper Motor PHASE 1 12vdc
Dig OP E Auto VI Stepper Motor PHASE 2 12vdc
Dig OP F Auto VI Stepper Motor PHASE 3 12vdc
Dig OP G Auto VI Stepper Motor PHASE 4 12vdc

Page 16
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Calculated inputs
A17 Suction equivalent temperature A1(R22/NH3) -50 to 100°C
A18 Discharge equivalent temperature A2(R22/NH3)
-50 to 100°C
A19 Suction superheat A17-A5
A20 Discharge diff pressure A2-A1 -1 to 24 bar g
A21 Oil diff pressure A3-A2
-1 to 24 bar g
P_st/no_P/Filt syphen system A3-A1
A22 Filter differential pressure, Filter After Pump
Filter differential pressure, Filter Before Pump A4-A3
A2-A4 -1 to 24 bar g
A23 Compressor hours run 0 to 65000 hrs
SCC50 Fuse Ratings
FUSE Rating Littlefuse part CCT protection Terminal
s
F101 125 mA 0453 .125 Com 2 RS485 B line TB11-2
F102 125 mA 0453 .125 Com 2 RS485 A line TB11-3
F103 125 mA 0453 .125 Com 1 RS485 B line TB4-2
F104 125 mA 0453 .125 Com 1 RS485 A line TB4-3
F105 1 A - T 0454 001. Display CN1
F106 1 A - T 0454 001. Extension CN2
F201 1 A - T 0454 001. 24 Vdc supply TB12A-1
F202 1 A - T 0454 001. 12 Vdc supply TB12-4
F203 125 mA 0453 .125 24 Vdc supply TB5-2
F204 3.5 A - T 0454 03.5 24 Vac Incoming TB3-1
F401 125 mA 0453 .125 24 Vdc supply TB10A-4
TB10-4
TB6-16
TB6-12
TB6-8
TB6-4
TB7A-5
F402 125 mA 0453 .125 5 Vdc supply TB7-5

Page 17
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
SCC50 FUSES and LED LAYOUT
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
TB1-17
TB1-18
TB1-19
TB1-20
TB1-21
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB3-1
TB3-2
TB3-3
TB3-4
TB3-5
TB3-6
TB3-7
TB3-8
TB3-9
TB3-10
TB3-11
TB3-12
TB6-4
TB6-3
TB6-2
TB6-1
TB6-8
TB6-7
TB6-6
TB6-5
TB6-12
TB6-11
TB6-10
TB6-9
TB6-16
TB6-15
TB6-14
TB6-13
TB10A-4
TB10A-3
TB10A-2
TB10A-1
TB7-4
TB7-3
TB7-2
TB7-1
TB7A-3
TB7A-2
TB7A-1
TB7A-5
TB7A-4
TB7-5
TB8-3
TB8-2
TB8-1
TB8-6
TB8-5
TB8-4
TB8-9
TB8-8
TB8-7
TB8-12
TB8-11
TB8-10
TB9-3
TB9-2
TB9-1
TB9A-3
TB9A-2
TB9A-1
TB9-6
TB9-5
TB9-4
TB11-3
TB11-2
TB11-1
TB12A-
3
TB12A-
2
TB12A-
1
TB12-3
TB12-2
TB12-1
TB12-4
TB12-5
TB4-1
TB4-2
TB4-3
TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6
TB10-4
TB10-3
TB10-2
TB10-1
1
2
3
4
5
6
CN 2
EARTH
1
2
3
4
5
6
ON
RL 1
RL 2
RL 3
RL 4
RL 5
RL 6
RL 7
RL 8
RL 9
RL A
RL B ip T8
ip T7
ip T6
ip T5
ip T4
ip T3
ip T2
ip T1
TRIP INPUT
STATUS
RELAYOUTPUT
STATUS
F202 OK
F201 OK
EXT OUTPUT
STATUS
C D E F G
F105 OK COM 2
F105 OK
F401 OK
F203 OK
INPUT
STATUS
A B C D
H
G
F
E
RxTx
Rx
Tx
COM 1
F106 OK

Page 18
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
SCC-50 Termination Wiring -

Page 19
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
Old Model SCC-40 Termination Wiring -
N.B. The Compressor Run Signal (TB3 Terminal 11) must be supplied to the Controller
from the Delta Contactor of a Star-Delta System, or the Top of Ramp of a Soft Start
System.
Xxx …xxx

Page 20
GUARDIAN SCC-50 Operator Manual Issue V1.0b 09/05/02
SCC50-Auto VI Stepper Motor wiring
Table of contents
Other Guardian Controllers manuals
Popular Controllers manuals by other brands

Watlow
Watlow Power Series Specifications

Solarwize
Solarwize RSC-PV1230 user manual

TennaTronix
TennaTronix TurboTuner-2 user manual

BoomToneDJ
BoomToneDJ EZ Strobe user manual

VERDER
VERDER Carbolite Gero EVT 12/450B Installation, operation and maintenance instructions

Bitzer
Bitzer CiC System technical information

Rain Bird
Rain Bird ESP-LX manual

SOMFY
SOMFY animeo LON 4 DC/E installation guide

Chicago Pneumatic
Chicago Pneumatic ES 4000 STANDARD Instruction

Honeywell
Honeywell HON 5020 User and maintenance manual

Ildvr Digital Technology USA
Ildvr Digital Technology USA IKB-2888 user manual

EUCHIPS
EUCHIPS Walldim202 user manual