GVS K-Bus ADUD-01/02.3 User manual

KNX Universal Dimming Actuator,
1/2/4-Fold_V1.0
ADUD-01/02.3
ADUD-02/02.3
ADUD-04/02.3
KNX/EIB Home and Building Control System
User manual

Attentions
1.Please keep devices away from strong magnetic field, high temperature,
wet environment;
2.Do not fall the device to the ground or make them get hard impact;
3.Do not use wet cloth or volatile reagent to wipe the device;
4.Do not disassemble the devices.

When using this product, please pay attention to analysis of the following
troubleshooting.
NO.
Exception
Possible cause
Solution
Remark
1
Lamp flickers in the
low brightness
Lamp driver works
unstably at low voltage
Increase the min.
brightness appropriately
to debounce
Use the user defined
curve, and set the
output value when 1%
as the min. brightness
that can be stable
2
There is no obvious
differences for LED in
the high brightness
The LED has reached
the highest brightness
after a certain voltage
Decrease the max.
brightness appropriately
to avoid the invalid
control
Use the user defined
curve, and set the
output value when 100%
as the control value of
LED highest brightness
3
Flicker or unstable
when LED startup
Lamp driver needs an
extra startup voltage for
stable output
Enable the additional
startup characteristic
and set its parameter, to
avoid the flicker when
startup
4
The min. control value
when lamp off is
higher than the value
when lamp on
Lamp driver needs an
extra startup voltage for
lamp on normally
Enable the additional
startup characteristic
and set its parameter, to
improved dimming
effect
5
Lamp flickers in
dimming
Lamp dose not support
dimming
Check the lamp
characteristic supports
dimming or not
If there is no
improvement, it is
suggested to
replace the lamp or
driver
Incompatible between
lamp and driver power
supply
Check the lamp is
matched to the driver or
not
Incompatible of load
type or dimming curve
Adjust the ETS
parameter and check
again
Brightness changed in
dimming is too fast
Extend the dimming
time and change the
dimming curve
Incompatible of
dimming curve if only
flicker in a partial curve
in the middle
Use the user defined
curve to adjust the
flickering curve
If only flicker in the high
brightness
Decrease the max.
brightness value

NO.
Exception
Possible cause
Solution
Remark
5
Lamp flickers in
dimming
Lamp driver is not good
enough, unstable
voltage, compatibility
issue
Test with an additional
incandescent lamp or
electronic dummy load
in parallel
If there is no
improvement, it is
suggested to
replace the lamp or
driver
6
The dimmable range is
not 0-100%, not a good
experience with user
operation
It is the limitation of the
operation voltage range
and effect of lamp
driver
Use the user defined
curve, and set the
output value when 1%
as the min. brightness,
set the output value
when 100% as the
control value of lamp
highest brightness
7
Lamp is still brighter at
lower brightness, and
have a small
dimmable range
Incompatible of
dimming curve
Change the curve to one
with a lower change
value, such as
quadratic, cubic,
exponential, logarithmic,
even use the user
defined curve
Possible the min.
brightness is high
Check and decrease the
min. brightness
8
Switch off abnormally
or can not turn on
Operation voltage
failure
Check and reconnect
Configure the
monitoring the
group addresses of
abnormal status
objects, re-check to
confirm there is an
alarm telegram or
not, if still exist
alarm and improve
again according the
alarm telegram
The connected lamp
has been overloaded
and caused the
protection of
over-temperature
Reduce the load power
Output terminal is
short-circuit and trigger
the protection
Reconnect the wiring
and test that there are
no problems before
power up again
The inrush current of
lamp driver is too big
and trigger the
protection of over-load
Reduce the load power
Change to trailing edge
Change a better lamp or
driver
Bus voltage failure
Bus diagnostics and
confirm to connect
normally
9
LED can not turn off
Incompatible between
lamp driver and dimmer
Test with an additional
incandescent lamp or
electronic dummy load
in parallel
If there is no
improvement, it is
suggested to
replace the LED or
driver
Connect an external
switch actuator channel
with output in
series,linking the switch
object together to work
simultaneously
Change a better LED or
driver

Contents
Chapter 1 Summary -----------------------------------------------------------------------------------------------------1
Chapter 2 Technical Data -----------------------------------------------------------------------------------------------3
2.1. Load type -------------------------------------------------------------------------------------------------------- 5
2.2. Operation mode ------------------------------------------------------------------------------------------------- 8
Chapter 3 Dimension and Connection Diagram ----------------------------------------------------------------------9
3.1. Dimension drawing --------------------------------------------------------------------------------------------- 9
3.2. Connection Diagram ------------------------------------------------------------------------------------------ 10
Chapter 4 Project Design and Programming ----------------------------------------------------------------------- 11
Chapter 5 Parameter setting description in the ETS ---------------------------------------------------------------13
5.1. KNX Secure ---------------------------------------------------------------------------------------------------- 13
5.2. Parameter window "General" ---------------------------------------------------------------------------------17
5.3. Parameter window "Output setting" ------------------------------------------------------------------------- 20
5.3.1. Parameter window "Channel" ---------------------------------------------------------------------------22
5.3.2. Parameter window "User defined dimming curve" --------------------------------------------------- 32
5.3.3. Parameter window "Extension function" -------------------------------------------------------------- 35
5.4. Parameter window "Logic" ------------------------------------------------------------------------------------49
5.4.1. Parameter window "AND/OR/XOR" ---------------------------------------------------------------------50
5.4.2. Parameter window "Gate forwarding" ------------------------------------------------------------------52
5.4.3. Parameter window "Threshold comparator" ---------------------------------------------------------- 54
5.4.4. Parameter window "Format convert" ------------------------------------------------------------------ 56
5.4.5. Parameter window "Gate function" ---------------------------------------------------------------------57
5.4.6. Parameter window "Delay function" --------------------------------------------------------------------59
5.4.7. Parameter window "Staircase lighting" ----------------------------------------------------------------59
Chapter 6 Description of Communication Object ------------------------------------------------------------------ 61
6.1. "General" Communication Object ---------------------------------------------------------------------------- 61
6.2. "Output setting" Communication Object -------------------------------------------------------------------- 62
6.3. "Logic" Communication Object -------------------------------------------------------------------------------67
6.3.1. "AND/OR/XOR" Communication Object ----------------------------------------------------------------67
6.3.2. "Gate forwarding" Communication Object -------------------------------------------------------------67
6.3.3. "Threshold comparator" Communication Object ----------------------------------------------------- 68
6.3.4. "Format convert" Communication Object --------------------------------------------------------------69
6.3.5. "Gate function" Communication Object ----------------------------------------------------------------71
6.3.6. "Delay function" Communication Object ---------------------------------------------------------------72
6.3.7. "Staircase lighting" Communication Object ----------------------------------------------------------- 73

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
1
Chapter 1 Summary
KNX Universal Dimming Actuator,1/2/4-Fold (hereinafter referred to as Dimmer) has 1/2/ 4 output
channels, and it can connect with dimmable lamps (such as incandescent lamps, halogen lamps,
energy-saving lamps, LED, etc.), and you can dim, preset scene, switch these lamps or other operations
via the bus. In addition, as well as KNX Data Secure.
This dimmer is a modular installation device for fast installation in the distribution board on 35 mm
mounting rails to DIN EN 60 715, the output adopts screw terminal to realize electrical connection. Bus
connection is directly connected via KNX terminal, the additional power supply is not required except
KNX bus.
You can build the various scenes with the dimmer, such as watch movie, entertainment, dinner and
rest, and so on; its brightness value can be set as any value (1-100%); it is able to set the duration time
to dim up or down to the target brightness and the gradual speed to extend the luminaries life and save
energy.
The physical address assignment and parameter settings can be used with the engineering tool
software ETS (version ETS5 or above) with the .knxprod file.
In use you need to note the type of connected electrical load, thus reasonable select them and
note their technical performance. If the technical performance of the selected load is not consistent
with the technical performance of the dimmer, it is possible to affect the dimming effect.
The manual provides detailed technical information about the dimmer, including installation and
programming details, and explains how to use the dimmer in conjunction with examples in actual use.

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
2
The functions are summarized as followed:
Switch, Relative dimming/Absolute dimming
Status feedback of switch, brightness, as well as abnormal status (short-circuit, over-voltage,
over- temperature and operating voltage failure)
Reset behaviour after download/bus failure/bus recovery
6 dimming curves, including Linear, Exponential, Cubic, Quadratic, Logarithmic, Root and
User defined curves
Leading edge/Trailing edge phase cut dimming
Manual operation and Output indication function
Central control function (Only apply for 2/4-fold)
Individual or parallel output (Parallel can expand the load capacity, only apply for 2/4-fold)
Staircase lighting, Flashing switch and Delay switch, as well as Scene, Threshold, Forced
operation, Safety operation and Operation hours counter
Logic function, with AND, OR, XOR, Gate forwarding, Threshold comparator, Format convert,
Gate function, Delay function and Staircase lighting
Support the KNX Data Secure

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
3
Chapter 2 Technical Data
Power Supply
Bus voltage
21-30V DC,via the KNX bus
Bus current
<6mA/24V, <5.5mA/30V (1 fold)
<7mA/24V, <6mA/30V (2 fold)
<7.5mA/24V, <6.5mA/30V (4 fold)
Bus consumption
<165mW (1 fold)
<180mW (2 fold)
<195mW (4 fold)
Output
Dimming channel
1/2/4 folds, separate phase connection
Max. output capacity
300W (per channel, Incandescent/ Halogen/ LED,
trailing edge)
Parallel: 2 channels 500W /3 channels 750W/
4 channel 1000W
Unrated voltage
110~230 V AC (50/60HZ)
Protection
Short-circuit, Over-voltage, Over-temperature
Standby loss
Approx. 0.7W
Power loss
≤2W / per channel
Connection
KNX
Bus connection terminals
Outputs
Screw terminals
Wire Range
0.2—2.5mm2(1 fold)
0.2—6.0mm2(2/4 fold)
Operation and
display
Programming button and Red LED
For assigning the physical address

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
4
Green LED flashing
For displaying application layer running normally
Channel button
For manual switching or dimming
Channel indication LED
Indicates channel status of the load
Man./Auto. button
Change the Man./Auto. mode
Man./Auto. LED
Indicate the Man./Auto. mode status
Temperature
Operation
–5 °C ... + 45 °C
Storage
–25 °C ... + 55 °C
Transport
– 25 °C ... + 70 °C
Environment
Humidity
<93%, except dewing
Mounting
On 35mm mounting rail
Dimension
36 x 90 x 64 mm (1 fold)
72 x 90 x 64 mm (2 fold)
144 x 90 x 64 mm (4 fold)
Weight
0.2kg (1 fold)
0.3kg (2 fold)
0.5kg (4 fold)

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
5
2.1.Load type
Load type
Max. Load capacity (110V)
Max. Load capacity (230V)
Leading edge
Trailing edge
Leading edge
Trailing edge
Incandescent lamp
10...150W
10...150W
10...300W
10...300W
HV Halogen lamp
10...150W
10...150W
10...300W
10...300W
LV Halogen lamp with Electronic
transformer
10...150W
10...150W
10...300W
10...300W
HV LED
2...30W
2...150W
2...60W
2...300W
LV LED with Electronic transformer
2...40W
2...150W
2...80W
2...300W
LV LED with Constant current driver
(Down light, Spotlight)
2...40W
2...150W
2...80W
2...300W
LV LED with Constant voltage driver
2...40W
2...150W
2...80W
2...300W
Resistive load
Capacitive load
Inductive load
LED load

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
6
Individual or parallel outputs can be selected for 2/4-fold dimmer, and the parallel can expand the
load capacity. Load type as following:
Load type
Max. Load capacity (110V)
Parallel with 2 channels
Parallel with 3 channels
Parallel with 4 channels
Leading edge
Trailing edge
Leading edge
Trailing edge
Leading edge
Trailing edge
Incandescent lamp
300W
300W
400W
400W
500W
500W
HV Halogen lamp
300W
300W
400W
400W
500W
500W
LV Halogen lamp with Electronic
transformer
300W
300W
400W
400W
500W
500W
HV LED
-
300W
-
400W
-
500W
LV LED with Electronic transformer
-
300W
-
400W
-
500W
LV LED with Constant current driver
(Down light Spotlight)
-
300W
-
400W
-
500W
LV LED with Constant voltage driver
-
300W
-
400W
-
500W
Load type
Max. Load capacity (230V)
Parallel with 2 channels
Parallel with 3 channels
Parallel with 4 channels
Leading edge
Trailing edge
Leading edge
Trailing edge
Leading edge
Trailing edge
Incandescent lamp
500W
500W
750W
750W
1000W
1000W
HV Halogen lamp
500W
500W
750W
750W
1000W
1000W
LV Halogen lamp with Electronic
transformer
500W
500W
750W
750W
1000W
1000W
HV LED
-
500W
-
750W
-
1000W
LV LED with Electronic transformer
-
500W
-
750W
-
1000W
LV LED with Constant current driver
(Down light,Spotlight)
-
500W
-
750W
-
1000W
LV LED with Constant voltage driver
-
500W
-
750W
-
1000W

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
7
Note:
It is not permitted to connect inductive and capacitive loads together at the same output.
However, mixing of loads such as capacitive + resistive loads or inductive + resistive loads is allowed
to connect, but power reduction needs to be considered. It is more advisable to connect the same type
of loads for an output.
The max. load capacity depends on the surge current and power loss of the lamp, these types of
lamp will cause large heating and high surge current in leading edge mode, especially LED lamp, so it
is not recommended to drive LED in leading edge mode, make sure the connected lamp do not trigger
over-load or over-heating protection.

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
8
2.2.Operation mode
Dimmer system is dimming in leading or trailing edge.
1.Dimming in leading edge:
Explanation of the dimming system: turn off dimmer in leading edge and turn on in trailing edge. As
shown in the following figure, no voltage input from zero point until dimmer is turned on. It is suitable
for inductive loads.
2.Dimming in trailing edge:
Explanation of the dimming system: turn on dimmer in leading edge and turn off in trailing edge. As
shown in the following figure, dimmer will be turned on the zero-crossing point, during this moment, the
voltage is very low and there is no inrush current to the load. In this way, there is no minimum load
requirement, so that allows for better performance of a single lighting or a very small load and extends
the life of the lamp, as well as reduce the interference to the power grid. It is suitable for resistive or
capacitive loads.

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
9
Chapter 3 Dimension and Connection Diagram
3.1.Dimension drawing
1-Fold
2-Fold
4-Fold

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
10
3.2.Connection Diagram
Individual 4 channels
Parallel with 2 channels
Parallel with 3 channels
Individual 1 channel Individual 2 channels Parallel with 2 channels Parallel with 4 channels
①Programming button ②Programming LED
③KNX bus connection terminal ④Input, Output, load terminal
⑤Channel indication LED: in normal mode, LED off is the lamp off, LED on is the lamp on; in manual
mode, flashing slowly is dimming manually. Flashing fast is channel abnormality (Short-circuit,
Over-voltage, Over-temperature, Operating voltage failure)
⑥Channel button: when no ETS configuration, press to switch on/off; in manual mode, short press to
switch on/off, long press for dimming up/down, long press then release to stop dimming
⑦⑧Man./Auto. operation switch button and status indicating LED:
Long press to switchover Man. and Auto. mode, LED on is Man. mode and off is Auto. mode.
Reset the device to the factory configuration: press the programming button and hold for 4 seconds
then release, repeat the operation for 4 times, and the interval between each operation is less than 3
seconds

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
11
Chapter 4 Project Design and Programming
General function
General function includes device In operation setting, central control (Switch, Dimming), safety
function, as well as manual operation and output indication function.
In addition, central control function only applies for 2/4-Fold Dimmers, and it is not supported by
1-Fold Dimmer.
Output channel
There are 1/2/4 output channels according the product type, support to switch, relative
dimming/absolute dimming, feed back the status of switch, brightness and the abnormal status
(short-circuit, over-voltage, over- temperature and operating voltage failure), as well as reset behaviour
after download/bus failure/bus recovery. Individual or parallel outputs can be selected, and the parallel
can expand the load capacity, which only applies for 2/4-fold.
Load types and dimming curves can be independently configured, as well as extension functions
including Staircase lighting, Flashing switch, Delay switch, Scene, Threshold, Forced operation, Safety
operation and Operation hours counter.
For output function, the definition of function priority: Manual > Forced > Safety > other functions,
after exiting higher priority, the next priority action needs to be executed.
Application
Maximum of
communication
objects
Maximum
number of group
addresses
Maximum
number of
associations
Secure group
addresses
KNX Universal Dimming Actuator,
1-Fold/1.0
237
280
280
160
KNX Universal Dimming Actuator,
2-Fold/1.0
237
280
280
200
KNX Universal Dimming Actuator,
4-Fold/1.0
237
280
280
280

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
12
Logic function
Up to support 8 channels of logic, each channel up to support 8 inputs and 1 logic result.
Logic function support functions, including AND, OR, XOR, Gate forwarding, Threshold comparator,
Format convert, Gate function, Delay function and Staircase lighting.

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
13
Chapter 5 Parameter setting description in the ETS
5.1.KNX Secure
Dimmer is a KNX device that complies with the KNX secure standard. That is, you can run the
device in data secure mode.
Fig.5.1 (1) "KNX Secure" parameter window
The device with KNX secure will be displayed notes on ETS, as shown as Fig.5.1(1).
If secure commissioning is actived in ETS project, the following information must be considered during
device debugging:
It is essential to assign a project password as soon as a KNX Secure device is imported into a
project. This will protect the project against unauthorized access.
The password must be kept in a safe place – access to the project is not possible without it (not
even the KNX Association or device manufacturer will be able to access it)!
Without the project password, the commissioning key will not be able to be imported.
A commissioning key is required when commissioning a KNX Secure device (first download). This
key (FDSK = Factory Default Setup Key) is included on a sticker on the side of the device, and it must be
imported into the ETS prior to the first download:
On the first download of the device, a window pops up in the ETS to prompt the user to enter the
key, as shown in Fig.5.1 (2) below.
The certificate can also be read from the device using a QR scanner (recommended).

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
14
Fig.5.1(2) Add Device Certificate window
Alternatively, the certificates of all Secure devices can be entered in the ETS beforehand.
This is done on the "Security" tab on the project overview page, as shown in Fig.5.1(3) below.
The certificates can be also added to the selected device in the project, as shown in Fig.5.1(4).
Fig.5.1(3) Add Device Certificate
Fig.5.1(4) Add Device Certificate
There is a FDSK sticker on the device, which is used for viewing FDSK number.
Without the FDSK, it will no longer be possible to operate the device in KNX Secure mode
after a reset.
The FDSK is required only for initial commissioning. After entering the initial FDSK, the ETS will
1.1.8 KNX Universal Dimming Actuator,4-Fold

KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
15
assign a new key, as shown in Fig.5.1(5) below.
The FDSK will be required again only if the device was reset to its factory settings (e.g. If the device
is to be used in a different ETS project).
Fig.5.1(5)
Example:
If this application in the project needs to be tried with another device, it is no longer the original
device. When the application is downloaded to a new device, the following prompt will appear on the
left of Fig.5.1(6), click yes, the Add Device Certificate window will appear, then enter the initial FDSK of
the new device, and you need to reset the device to the factory settings (it is not required if the device is
still factory default; If it has been used, it will be required to reset, otherwise the following error
message will appear on the right of Fig.5.1(6)), and then the device can be successfully downloaded
again.
Fig.5.1(6) Example
Whether the device is replaced in the same project, or the device is replaced in a different project,
the processing is similar: Reset the device to the factory settings, then reassign the FDSK.
FDSK
-.-.- KNX Universal Dimming Actuator,4-Fold
1.1.8 KNX Universal Dimming Actuator,4-Fold
1.1.8 KNX Universal Dimming Act...
This manual suits for next models
2
Table of contents
Other GVS Controllers manuals
Popular Controllers manuals by other brands

Trinamic
Trinamic TMCM-6110 Firmware user manual

Jetec
Jetec ISOMOVE Use and maintenance guide

Johnson Controls
Johnson Controls tyco Power Pro Series Reference manual

Grundfos
Grundfos LLC 1000W Installation and operating instructions

Elotech
Elotech R 1140 operating manual

PS Automation
PS Automation PSF Series operating instructions

Kutai electronics
Kutai electronics ADVR-053 Operation manual

Mitsubishi Electric
Mitsubishi Electric MELSERVO-J5 MR-J5-G Series user manual

Sven
Sven VR-P5000 manual

Siemens
Siemens OpenAir manual

Sentera Controls
Sentera Controls MT Mounting and operating instructions

Artecta
Artecta Domotion DLC-4 RGB manual