
Document Number 129-408 RWD44U Controller Installation and Commissioning Guide
October 5, 2009
Page 4 of 10 Siemens Industry, Inc.
Display Explanation, Continued
PS 1 – Application Number Selection:
X2
AnG
changeover by analog
diG
changeover by digital
⇔
Selecting X2 or X1 as the
main sensor
Commissioning
Guide Commissioning is implemented via push buttons on the controller. The push buttons
have the following functions:
Press
Button to enter the PS page OR edit and save the value when the page
appears with the logo
Press
Button for viewing the next page OR to increase the value.
Press
Button for viewing the previous page OR to decrease the value.
Changing a parameter
1. Press the SEL λbutton.
:
2. Press the + σor –τbutton to increase or decrease the flashing parameter.
3. Press the SEL λbutton to save the value (During PS mode, the values are saved only after exiting the PS mode).
NOTE: A 9-pin port is provided for optional commissioning via Siemens software tool. See Software Tool
(Optional Programming).
Initial Program
Settings
(New Controller)
There are five levels of parameter setting (PS) modes: PS1 through PS4, and a
setpoint mode. Each PS has a set of default parameters, which can be changed during
commissioning.
When powered the first time, the controller will proceed to PS1 with default
application 10. See below for commissioning steps.
PS 1 – Application Settings
Select number of compressor stages
Select reversing valve output – On or Off during no demand
After completing PS1, the user has the option to progress to setpoint mode (only for new RWD) by waiting for
two seconds and default parameters will be accepted. If parameters PS2 through PS4 need to be adjusted,
press the +▲button immediately to the next PS (see Commissioning Flowchart).
Ni 1000, Pt 1000, 0 to 10V
Enter X1 sensor calibration offset (Ni or Pt only)
Enter X1 active sensor range (0 to 10 Vdc only)
32°F to 122°F
(0°C to 50°C)
Select auxiliary sensor X2
Ni 1000, Pt 1000, 0 to 10 Vdc
Enter X2 sensor calibration offset (Ni or Pt only)
±
Enter X2 active sensor range (0 to 10 Vdc only) -100 to 2400 32°F to 122°F