Attaching the accessories to the switch 安装附件到交换机
4
3
Install the grounding cable before installing the switch in the rack.
为了防止机箱安装到机柜后无法安装接地线,请先将接地线安装到交换机侧面的接地点上。
The installation positions of the accessories in the following figure are for illustration only.
Determine installation positions for the accessories based on the installation requirement.
以下图中附件的安装位置仅供参考,请根据实际安装场景的需要选择合适的安装位置。
The device provides multiple installation positions for chassis rails on two sides. Determine the
installation position for the chassis rails based on the rack depth. Ensure that slide rails can reach
out of chassis rails after their installation.
设备侧面板提供了多个滑道导轨安装位,用户可根据机柜的深度,调整滑道导轨的安装位置;为保
证设备安装后的稳定性,当滑道与滑道导轨安装完成后,请确保滑道的头部露出滑道导轨。
If the rack depth is in the range of 692 to 854 mm (27.24 to 33.62 in), use the short chassis rails
and long slide rails provided with the switch for installation.
If the rack depth is in the range of 401 to 692 mm (15.79 to 27.24 in), purchase long chassis rails
and short slide rails yourself for installation. You need to install the long chassis rails as follows
based on the rack depth:
Not reaching out or reaching out of the chassis for a rack with a depth in the range of
499 to 565 mm (19.65 to 22.24 in).
Not reaching out of the chassis for a rack with the depth in the range of 401 to 499
mm (19.65 to 19.61 in).
Reaching out of the chassis for a rack with the depth in the range of 565 to 692 mm
(22.24 to 27.24 in).
如果机柜前后方孔条间距在692~854mm范围内,请使用标配的长滑道短导轨配合安装。
如果机柜前后方孔条间距在401~692mm范围内,请使用选配的短滑道长导轨配合安装。因短滑道
长导轨有正装(导轨不会超出设备)和反装(导轨会超出设备)之分,当机柜前后方孔条间距在
499~565mm范围内,长导轨正装和反装都可以;当机柜前后方孔条间距在401~499mm范围内,
请使用长导轨正装方式安装;当机柜前后方孔条间距在565~692mm范围内,请使用长导轨反装方
式安装。
The installation procedure is the same for using long and short chassis rails. The following
procedure uses the short chassis rails as an example.
采用长滑道短导轨安装交换机到机柜与采用短滑道长导轨安装交换机到机柜的方式相同,本文以采
用长滑道短导轨安装交换机到机柜为例。
Before installing cage nuts, mark their installation positions on the rack posts.
安装浮动螺母前,建议用户先使用记号笔在机柜方孔条上标注浮动螺母安装位置。
Installing the switch in a 19-inch rack 安装交换机到19英寸机柜
Attach cage nuts to the square holes in
the rack posts.
安装浮动螺母到机柜方孔条上
Attach slide rails to the rack posts.
安装滑道到机柜
1
2
The switch provides a grounding sign at the primary grounding point but not at the auxiliary
grounding point.
交换机主接地点标有接地标识,备用接地点上无接地标识。
The grounding screws provided with the switch are applicable to both the primary and auxiliary
grounding points.
交换机随机附带的接地螺钉同时适用于主接地点和备用接地点。
Install cage nuts and slide rails 安装浮动螺母与滑道
1
Grounding cable installation position (two options) 接地线安装位(二选一)
Primary grounding point
(near the power module side)
主接地点(靠近电源侧)
Auxiliary grounding point (near
the network port side)
备用接地点(靠近端口侧)