Commercial Air Conditioner
8. Controller functions
For HDU-50HT03/H,HDU-42,50,60CA03T3/H, the indoor unit can be controlled by wired controller
YR-E06.
9. Electrical Control Functions
9.1 For indoor unit
1. General notes for the function
1.1 The electric system can control the following functions of the commercial air conditioner.
Operation mode includes auto run, cooling, dehumidifying, venting, and heating. It can set the
compulsory cooling, and indoor fan motor has auto, high, med, low three selection. And it can set
TIMER ON, TIMER OFF, TIMER ON/OFF and SLEEP; auto check water level in the container and
control the drainage; swing controlled by synchro-motor; equipped with compressor 3-minutes
protection; overload protection; freezing protection; sensor broken down protection, etc. Also it can
check communication failure and measure indoors room temperature, indoor coil temperature.
Operation panel adopts LCD display, receiving the indication by pressing buttons, and it can realize
remote control function, also is responsible to measure indoor room temperature and it adopts
serial communication type with main board.
1.2 LED indication: when the unit is switched on by the controller, the POWER LED will be ON,
when being switched off, the POWER LED will be OFF. If the controller is in TIMER and SLEEP
mode, the TIMER LED will be on; if it is not in TIMER and SLEEP mode, the TIMER LED will be off.
When the compressor is running, the compressor LED will be on; when it stops, this LED will be off.
1.3 Temperature compensation control: select the 4 degree compensation when use ambient
temperature sensor on the indoor PCB( include: remote control type and wired control type use
indoor ambient temperature sensor).
1.4 There is set temperature in AUTO mode as default.
1.5 Do not receive the remote OFF signal when enter defrost mode.
2. Control modes selection
2.1 Auto fan speed selection
The following Tr stands for room temperature, Ts stands for set temperature.
2.1.1 In cooling mode
If it is the first time to enter auto fan mode(fan motor is stop), when Tr>Ts+2, it is in High speed; Tr
≤Ts, it is in Low speed; Otherwise, it is in Med speed. If the current mode is auto high speed, when
Tr<Ts+2, fan speed will turn to med speed automatically. If the current mode is auto med speed,
when Tr>Ts+3, it will turn to high speed, Tr<Ts,
it will turnto
low speed.
If current
mode is low
Temp. reducing
Med
Ts+2℃
High
Ts+3℃
High
speed, when
Ts+1℃
Med
Tr>Ts+1, it
will turn to med Ts Low
speed. When fan Low
speed changes from low to
Temp. arising