ELECTRICAL CONTROL
Edition:2006/08/10
zIf the wind speed is set to high or medium before going to bed, the wind speed shifts to
medium or low. If the wind speed is set to low before going to bed, the wind speed keep
unchanged.
3.3 Protection of malfunction of temperature sensitive resistance.
zThe temperature sensitive resistor is short circuit or open circuit, the machine doesn’t work.
zDuring defrosting, don’t detect if the temperature sensor short circuit or open circuit.
zDetect the temperature of coil pipe is below -40ď, then think the temperation circuit of coil
pipe is open.
zDetect the temperature of coil pipe is above 95ď, then think the temperation circuit of coil pipe
is short .
zDetect the temperature of inlet air is below -20ď, then think the temperation circuit of inlet air
is open.
zDetect the temperature of inlet air is above 90ď, then think the temperation circuit of inlet air
is short.
3.4 Emergency switch imput:
zPress the switch of emergency operation, then buzzer rings once and unit enters the automatic
operation mode. (emergency operation)
zIf the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter enter test run
mode.
zPress the switch again, and then closes.
zThe unit can receive remote control.
zEnter emergency operation from timer mode, then timer is cancelled.
zTest run:
1) The temperature sensor of inlet air doesn’t work, and compressor starts (but subject to the
limit of 3minute delay excluding the first time), and high wind, cooling, and air door is
open.The indoor fan motor runs, running indicator lights up, compressor relay and the one
of outdoor fan motor is closed
2) During test run:
zThe prevention of freezing of evaporator doesn’t work.
zOver current control doesn’t work.
zThe control of current peak expiration doesn’t work.
zTemperature control doesn’t work.
zTemperature expiration control doesn’t work.
zThe test run is over after 30 minutes,then the unit turn off
3.5 Executive function after 2 seconds by remoter control:
After receiving remote control signal, the mainboard doesn’t enter the corresponding
instruction task until 2 seconds elapse.
zF The memory function of power down is available, and the auto recovery function of power on is
optional. (In auto, heating, cooling, or defrosting status, press the “sleeping” button 10 times within 5
seconds, and the auto recovery function of power on can be set on/off. If the buzzer rings 4 times, the
the auto recovery function of power on is available; If the buzzer rings 2 times, the the auto recovery
function of power on is unavailable.)
3.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and the impulse
from fan motor is not detected, then stop outputting voltage to indoor fan motor, send alarm signals.
3. 7 Manual defrosting: when the wire controller is on, choose high wind, 30ď, and press the sleeping
button for 6 times within 5 seconds, and after the buzzer rings 3 times, the air conditioner
enter manual defrosting mode, which is the same as heating defrosting.