
31-5000553 Rev.1 19
ENGLISH
Wire Connections (cont.)
•Outdoor units areofparallel connection viathreelines with polarity.
•The main unit,centralcontrol and allindoorunits are ofparallelconnection via twolineswithout polarity.
•There are threewaysof connecting thelinecontrol and indoorunits:
A.One wired controllertocontrol multiple units,i.e.2-9 indoor units,asshown in thefigureat the topofpage 18, (1-3
indoorunits). The indoorunit3 is thewirecontrolled main unitandothers are thewiredcontrolled sub units.Thewired
controllerand the mainunit(directly connected totheindoor unit ofwiredcontroller) are connectedviathree wires
withpolarity. Other indoorunitsand the mainunitare connected viathreelines with polarity.SW01on the mainunitof
wiredcontrol is setto0 while SW01onother sub unitsofwired control aresetto 1, 2andso on inturn.(Please refer to
thecode setting Aatpage 14)
B.One wired controllercontrolsone indoor unit,asshown in thefigureat the bottomofpage 18 (indoorunit4-8). The
indoorunits and thewiredcontroller are connectedviathree lines withpolarity.
C.Two wired controllerscontrolone indoor unit,asshown in thefigure(page 18) (indoorunit9). Either ofthewired
controllerscan be settobe the mainwiredcontroller while theotheris set tobethe auxiliary wiredcontroller.The main
wiredcontroller and indoorunits,and the mainandauxiliary line controlsareconnected via threelineswith polarity.
Note: ForDC motor/low ESPducttype, the PCBcomeswith the terminalblocks.Please be suretopay attention todo
thewiring according tothelabels. The powerlinesand signal linesgothrough the metalwirehole separately withthe
protectivesleeve of theconnectingline.
Wiregauge size andbreakersize for totalindooramp draw.
CurrentNEC guidelines andlocalcodes will trumpthischart.
•The electrical powerlineand signal linesmustbe tightened.
•Every indoor unitmusthave a groundconnection.
•The power wireshouldbe size upifit exceeds thepermissiblelength.
•Shielding of thewireof all theindoorand outdoor unitsshouldbe connected andgroundedat one pointinthe outdoor
unit.The far endofthe shielding wireshouldbe wrapped backandtaped.
•Signal lines shouldnotexceed 3280ft (1000m).
Wired Controller ABC Chart
•The shielding layerofthe controller wiremustbe grounded attheequipment end, andtapedback at theterminalend.
•The total lengthofthe controller wireshallnot be morethan820ft (250m).
Items Cross Section
(mm²)Length
(mm) Rated Current of
OverflowBreaker
(A)
Rated Current of
Residual Circuit
Breaker(A)
GroundFault
Interrupter (mA)
Response Time (S)
Cross
Sectional Area
ofSignal Line
<6 2.5 20 6 6A,30mA,0.1S orbelow
2coreX0.75-
2.0mm2
6and<10 2.5 20 10 10A,30mA,0.1S orbelow
10and<16 4 25 16 16A,30mA,0.1S orbelow
16and<25 6 30 25 25A,30mA,0.1S orbelow
25and<35 10 50 32 32A,30mA,0.1S orbelow
TotalCurrent
ofIndoor
Units(A)
LengthofControllerWireft(m) WiringDimensionsAWG(mm²)
820(250) 18(0.75)x3 coreshielding line
ELECTRICALWIRING