Service Manual
AIR-COOLED MODULAR CHILLER
SYJS-05-2021.B Edition: 2021-05

1
CONTENTS
1. Nomenclature ........................................................................................................................................................ 1
2. Feature .................................................................................................................................................................. 1
3. Specication .......................................................................................................................................................... 6
4. Dimension.............................................................................................................................................................. 8
5.Refrigerant system diagram...................................................................................................................................11
6. Installation ........................................................................................................................................................... 14
7. Controller Operation Instruction........................................................................................................................... 30
8. Wiring Diagram.................................................................................................................................................... 35
9. Commissioning, Operation and Maintenance...................................................................................................... 39
10. PCB Photo and Address Code Setting.............................................................................................................. 43
11. Fault Code ......................................................................................................................................................... 44
12. Trouble Shooting ............................................................................................................................................... 46
13. Unit Operating Range and Service Condition.................................................................................................... 48
14. Technical Parameters ........................................................................................................................................ 49
15.Modular pressure drop water ow......................................................................................................................51
16.Sensor Charistic..................................................................................................................................................55
17.Central control connection ..................................................................................................................................56
18.Appendixi table for manual updated information ................................................................................................ 63

1
1. Nomenclature
2. Feature
2.1 Product feature
Code Explanation for chiller
1 2 3 4 5 6 7 8 9 10
Chiller
system Compressor type
Capacity
(for
Centrifugal
chiller: Rt;
other: kW)
Product type Unit
character
Suitable
voltage Design number
C
Centrifugal chiller C 1 0 6 9
Heat
pump
R22 A Air
cooled A100-115V,
60Hz 1Fixed
frequency A-G
Screw
chiller
Air
cooled
I
0 2 3 7 R407C B Water
cooled W220-240V,
50Hz 2 Inverter H-Q
Water
cooled 0 0 1 2 R132 C Earth
source
E
115-220V,
50/60Hz 3DC
inverter R-Z
Earth
source R134A D 220-220V,
60Hz 4
Air-cooled
module chiller A R410A E 110V, 50-
60Hz 5
Light
chiller
Split-
packaged H
Cooling
only
R22 M 220V, 50-
60Hz 6
Single-
packaged R R407C N 127V, 60Hz 7
Water-cooled cabinet
chiller W R132 O 240V, 50Hz 8
Hydronic
system
Cassatte B R134A P 110-220V,
50/60Hz 9
Duct D R410A Q 330V, 50Hz A
Cabinet P 400V, 50Hz B
Wall
mounted S3300V, 50Hz C
6600V, 50Hz D
380-400V,
50Hz N
415V, 50Hz M
New appearance
New Y-shape design, more fashion
1
2
3
4
5
Structure
Motor
Compressor
Filter drier
Air cooling side
heat exchanger
EEV

2
Compressor
Best scroll compressor, low sound power level,
high EER, various protection: discharge temp.
protection, high/low pressure protection, over
currency protection and reverse protection, etc..
Air cooling side heat exchanger
By using calculation model and acquiring heat
exchanging ratio to optimize the windward air
speed and condensation temp.
Motor
Low sound power level axial fan, together with
the high efcient motor, making higher efciency
and lower sound power level.
EEV
High efcient EEV (thermostatic expansion
valve) to adjust the overheating degree of
system to control refrigerant volume. High
efcient evaporator to make part load and full
load COP the highest.
3
2
12
43
1
4
Compact design, reduce footprint
New Y-shape design, small oor area, only 1.56m², 28% footprint can be reduced.
2.18m² 1.56m²
1000mm
2185mm
780mm
2000mm
28% Floor
area reduced

3
High efciency system
The new series adopt more high efcient parts and unique design ensure the chiller high efciency EER up to
3.4.COP above 3.4 (R410A Series).
High Reliability
Backup operation function
The system has three modules, the actual operation of just two module, if one module malfunction another module
will start automatically according to the water temperature.
EEV control, the 1400
steps high-performance
electronic expansion valve
High efciency
compressor, adopts the
famous brand, low noise
level, high EER
High efciency heat exchanger, Condenser adopts the Copper tube &
hydrophilic aluminum n coil type structure, increase the heat exchange
efciency 20%.
Operation Operation Operation
Service
Stop StopMalfunction
Three phase fan motor
Three phase fan motor,compared
with one phase fan motor low starting
current,
high speed and more stable.
Shell & Tube heat exchanger
The new modular chiller adopt
Shell&Tube heat exchanger avoid
dirty plugging,
higher efciency and reliability.
Safety and protection
Phase reverse protection, high and
low pressure protection, freeze
protection, overheat protection,
overload protection, etc.
Pressure sensor control
Through the pressure sensor
real-time monitoring, realize the
system quickly,
accurately control, ensure the unit
efcient and stable operation.
Filter drier
Filter drier,absorb moisture in the
system, avoid the emergence of
the "ice block"

4
Modular design
Max 1040 kW with 16 modules, exible
combination, more convenient for
design and transportation.
Standard of water lter
Standard of water lter prevent the
destruction of the impurities in water
system, provide the unit reliability.
Standard of target type ow switch
Standard of target ow switch, prevent
non-work personnel wrong operation.
Easy to Installation
Water System Installation Sketch
Make up water tank
One-way valve
Automatic vent valve
Water lter
Thermograph
Pressure gauge
Pump
Softness joint
Expansion tank
Electronic device
for water treatment
Stop valve
(Placed in the highest point of the water system)
Drain valve
Air-conditioning
terminal devices
Bypass valve
Drain valve
2.2 Technical Features
2.2.1 The modular design, capacity can be broadened.
The unit uses modular design module, a plurality of modules are connected together, the unit can be connected
to 16 separate unit module, can be done to expand the width capacity between 65kW-1040kW; at the same time
each individual module no distinction between them, both it can be used as a host; also be used as auxiliary use,
high design and installation exibility.
2.2.2 A combination of convenience, balanced operation, automatic control.
When module combination, water pipe and communication line need to connect to each other. The advanced
microcomputer control system will automatically achieve uniform load distribution unit, so the unit is always in
the best operating condition, and does not consume unnecessary energy. While for the whole unit, the system
running time is basically same which can increase the overall life of the unit and operate at low load in some
modules.

5
2.2.3 Efcient intelligent control
Features:
Ability autoregulation
Linkage centralized control technology
Self-diagnostic technology
Lock function
Winterized function
With a strong self-protection and self diagnostic functions:
Compressor high and low voltage protection, power supply reverse (lack of) of protection, frost protection in
cooling mode, the unit frost protection in winter water systems, compressor overcurrent protection, compressor
discharge temperature protection, anti-overheating protection, ow switches protection, sensor fault protection.
2.2.4 Environmental protection:
R410A refrigerant, higher cooling (heating) efciency. Improve air conditioning performance, do not damage the
ozone layer.
2.2.5 Ultra-wide operating range
50 degrees in ultra-high temperatures cooling, but also can meet the ultra-low temperature of minus 15 degrees in
heating operation.
2.2.6 Low noise:
World-class scroll compressor, low noise fan, low noise operation.
2.2.7 Precise throttle mode:
Reliability using electronic expansion throttling way to ensure the system.

6
Item CA0035EAND CA0070EAND
Cooling
Cooling capacity kW 30 65
Power input kW 9.4 19.2
Running current A 15.8 34.6
Heating
Heating capacity kW 33 70
Power input kW 9.6 19.1
Running current A 16.2 34.4
EER 3.19 3.39
COP 3.44 3.66
Max.Power input kW 16.3 28
Max. running current A 27.5 55
Power supply 3N/380V/50Hz 3N/380V/50Hz
Power factor 0.85 0.85
Refrigerant throttle type Electronic expansion valve
Capacity control 100% 50%,100%
Compressor
Brand DAIKIN DAIKIN
Type Scroll comprossor
Quantity 1 2
Input power KW 9 18
Refrigerant Type R410A
Charge kg 5.5 6*2
Air side heat
exchanger
Type (Slit n & efcient inner grooved copper tube)Inner grooved
copper pipe & hydrophilic aluminum n coil
Fan power KW 0.7 1.5
Air volume m³/h 12700 12700×2
Fan type Axial ow fan
Fan quantity 1 2
Water side heat
exchanger
Type Plate heat exchanger Shell & Tube heat exchanger
Rated water ow m³/h 5.6 12
Inlet/outlet pipe DN65 R 2"
(external screw thread)
Water dirt coefcient m2.℃/KW 0.018 0.018
Standard pressure Mpa 1.0 1.0
Water resistance kPa 40 45
Sound pressure level 1m away dB(A) 60 65
Sound power level 1m away dB(A) 76 83
External dimension
Unit length mm 918 2060
Unit width mm 1038 780
Unit height mm 1810 2170
Package
dimension
Unit length mm 1075 2200
Unit width mm 940 830
Unit height mm 1950 2280
Weight
Unit weight kg 270 630
Gross weight kg 290 645
Operation weight kg 280 670
Safety & functional
protections
High/low Pressure Protection,Water Lackage delay Protection, Freeze Protection,Overload &
Overheat Protection, Phase Loss, Phase Sequence Protection
Note:
1. Nominal refrigerating condition: water outlet temperature is 7°C, ambient temperature is 35°C, and water ow is 0.172[m3/
(h·kW)].
2. Nominal heating condition: water outlet temperature is 45°C, ambient temperature is 7°C for dry bulb and 6°C for wet bulb,
and water ow is listed in the above table.
3. Unit operating range: conforming to GB/T 18430.1& GB/T 18430.2.
4. Scaling factor of circulating water: 0.018m2·°C/kW.
5. The specications in the table may vary with changes in product design without prior notice.
Model
3. Specication

7
Model
Item CA0100EAND CA0130EAND
Cooling
Cooling capacity kW 98 130
Power input kW 28.9 38.4
Running current A 53.2 75.4
Heating
Heating capacity kW 103 135
Power input kW 28.7 38.2
Running current A 52.8 75
EER 3.39 3.39
COP 3.59 3.53
Max.Power input kW 45.6 56
Max. running current A 82.5 110
Power supply 3N/380V/50Hz 3N/380V/50Hz
Power factor 0.85 0.85
Refrigerant throttle type Electronic expansion valve
Capacity control 33%,67%,100% 25%,50%,75%,100%
Compressor
Brand DAIKIN DAIKIN
Type Scroll comprossor
Quantity 3 4
Input power KW 27 36
Refrigerant Type R410A
Charge kg 5.8*3 5.8*4
Air side heat
exchanger
Type (Slit n & efcient inner grooved copper tube)Inner grooved
copper pipe & hydrophilic aluminum n coil
Fan power KW 2.3 3
Air volume m³/h 12700×3 12700×4
Fan type Axial ow fan
Fan quantity 3 4
Water side heat
exchanger
Type Shell & Tube heat exchanger
Rated water ow m³/h 17.7 24
Inlet/outlet pipe R 2"
(external screw thread)
R 2 1/2"
(external screw thread)
Water dirt coefcient m2.℃/KW 0.018 0.018
Standard pressure Mpa 1.0 1.0
Water resistance kPa 50 60
Sound pressure level 1m away dB(A) 67 68
Sound power level 1m away dB(A) 85 86
External dimension
Unit length mm 2060 2060
Unit width mm 1603 1603
Unit height mm 2170 2170
Package
dimension
Unit length mm 2200 2200
Unit width mm 1650 1650
Unit height mm 2280 2280
Weight
Unit weight kg 960 1090
Gross weight kg 990 1125
Operation weight kg 1010 1245
Safety & functional
protections
High/low Pressure Protection,Water Lackage delay Protection, Freeze Protection,Overload &
Overheat Protection, Phase Loss, Phase Sequence Protection
Note:
1. Nominal refrigerating condition: water outlet temperature is 7°C, ambient temperature is 35°C, and water ow is 0.172[m3/
(h·kW)].
2. Nominal heating condition: water outlet temperature is 45°C, ambient temperature is 7°C for dry bulb and 6°C for wet
bulb, and water ow is listed in the above table.
3. Unit operating range: conforming to GB/T 18430.1& GB/T 18430.2.
4. Scaling factor of circulating water: 0.018m2·°C/kW.
5. The specications in the table may vary with changes in product design without prior notice.
Model

8
4. Dimension
CA0035EAND
6
Unit Base Diagram
••••

9
CA0070EAND
Unit Base Diagram
Water Outlet
Water Inlet
Draining Valve
Electric control cabinet
0001
527
1320
2170

10
CA0100EAND CA0130EAND
7
Unit Base Diagram
5281
0551
1320
0712

11
5. Refrigerant system diagram
HPs
dry evaporator
4wv
TXV
Tewo
Tewi
heat exchanger
Td Ps
Ts
Tdef1 Tdef2

12
WVA
Dry evaporator
heat exchanger
COMP D
INV
D
E
C
S
Segregator
TXV
Accumulator
T
e A1
T
e A2
T
ewo
T
ewi
Drier
heat exchanger
T
e A1
T
e A2
Drier
heat exchanger
T
e A1
T
e A2
Drier
WVA
heat exchanger
COMP A
INV
D
E
C
S
Segregator
TXV
Accumulator
T
d A
T
e A1
T
e A2
T
s A
LPs
A
HPs
A
Drier
Accumulator
Accumulator
Segregator
SYSTEM D
SYSTEM B
SYSTEM ASYSTEM C
Segregator
TXV
TXV

13
Part name Sign Function Data Note
Compressor /
Capacity control, meet water
temp. request by opening
and closing xing frequency
compressor.
0.953Ω 20°C
Pressure HPS High pressure protection 4.15Mpa,OFF
Pressure sensor Ps
In cooling and heating,
compressor superheat
adjustment, abnormal pressure
protection
protection
PS8040A150NH4-L
Electronic expansion
valve
In heating, refrigerant ow
control φ6.4
4-way valve 4WV Changing over between cooling
and heating
AC220V electried in
heating; powered off in
cooling or defrosting
Temp. sensor
Td Check the dis. temp. of
compressor
R100=6.5K±2.5%
B0/100=4010±3%
Ts Check the suction temp. of
compressor
R25=5K±3%
B0/100=3470±3%
Ta Check ambient temp and control
defrost condition
Tdef1,Tdef2 Check frost condition of outdoor
heat exchanger
Tewi check temp.of inlet water
Tewo check temp.of outlet water
Heater CHI Used to heat oil in xing
frequency compressor 40W, 220V, double

14
6. Installation
6.1 Symbol Precautions
Symbol description
Dear user,
For the better understanding of this Manual and the proper operation of the chiller, the marks and symbols used in
this Manual are described as follows:
It is likely to cause death, serious injury and other severe accidents if the user fails
to do as required.
It is possible for severe accident to occur.
WARNING
CAUTION
WARNING
CAUTION
■Installation and maintenance must be carried out by professionals experienced in this type of unit in accordance
with applicable local codes and rules on installation and maintenance. We are not liable for any unit damage or
casualty due to non-conformance with this requirement.
■The power supply must be switched off prior to maintenance and relocation of the unit; otherwise, personal
injury or death may be caused by electric shock. Do not touch such hot components as compressor and exhaust
pipe directly.
■When the water system contains water, control the startup and shutdown of the water pump via the water pump
output point on the unit controller; otherwise, the anti-freezing protection of the unit will not work, causing the
freezing crack to the heat exchanger. If the unit is to idle for a long time in winter, drain the water from the water
system via the drain valve to prevent the freezing crack of the heat exchanger, the water pipe and other parts on
water side. Furthermore, the water pump shall be power off to avoid starting up against frost without water.
■To prevent the heat exchanger on water side from being frozen due to foreign matters entered, a self-contained
water lter must be installed on the water return pipe of the unit (specic installation position is shown in water
system diagram).
■Dregs and dirt in the water pipe network including lter and heat exchanger may seriously damage the heat
exchanger and water pipe. Installers and users must ensure the quality of chilled water, not use anti-icing
mixtures containing salt and prevent the entry of air into the water system, because the salt and air can oxidize
and corrode steel parts inside the heat exchanger.
■No unit is allowed to be installed near such places that are dirty, oily, salty, exposed to a large amount of sulfur
gas and where the unit parts may be subjected to corrosion, such as toilet vent, operation room vent and
sewage treatment equipment.
■If the unit is operated below 0°C, it must be installed at a place at least 300 mm above the ground, so as to
avoid
icing of unit base plate and to ensure the normal operation of the unit even though the snow reaches this height;
in addition, the unit shall be placed on a plane (with maximum deviation per meter of not more than 2 mm).

15
6.2 Site requirements
1) Noise considerations
■The unit is placed in the non-noise sensitive areas
■The damping pad on the unit below (not supplied with the standard model damping pad, user-owned)
■Install rubber shock absorbers on all water pipeline
■Seal all wall gap at room
Note demanding applications should consult an acoustic engineer
2) Ground
Install it on a hard, easy deformation of mounting pads or a concrete foundation to withstand the total weight of
the living unit at runtime (including all piping, refrigerant, oil, water).
Referring operating weight parameter table. After placing a good unit, machine leader and level of assurance
in the width direction should 1/4 "(6.35mm) within. Haier company equipment problems as the basis of design
or construction caused inappropriate will not take any responsibility.
3) Shock absorbers
■Provide rubber shock absorbers for the unit all the water pipes (Haier company standard models do not random
with shock absorbers, user-owned).
■Use a exible tube connecting wire electrical lines.
■Isolate all pipe hanger to ensure that they are not supported by the main structural beams of the building, so as
to avoid vibration transmitted live and work areas.
■Ensure that the pipeline will not add additional pressure to the unit.
Be careful not to use metal tube shock absorbers, because the frequency range of plant operation, the damper
is ineffective.
4) Frost protection
Note
In the case of low ambient temperature in winter, overnight shutdown period, heat exchangers and water pipes
may freeze inside, causing damage to equipment and piping. To prevent freezing, never allow the unit off
(because the unit has an automatic antifreeze function), as well as possible icing must put all the water
discharge pipe; hot side 65 to increase drainage and air-conditioned sides need to water line installation valve,
care must be taken to be installed at the lowest point of the water circuit, if the drainage more difcult case, you
can use anti-freeze mixture of ethylene glycol or propylene glycol (ratio table below).
Freezing and boiling points of ethylene glycol solution (anti-freeze glycol concentration table):
Freezing point
°C
Glycol
concentrations% Density (20°C)mg/
cm³ Freezing point °C Glycol
concentrations% Density (20°C)mg/
cm³
-10 28.4 1.034 -40 54 1.0713
-15 32.8 1.0426 -45 57 1.0746
-20 38.5 1.0506 -50 59 1.0786
-25 45.3 1.0586 -45 80 1.0958
-30 47.8 1.0627 -30 85 1.1001
-35 50 1.0671 -13 100 1.113

16
6.3 Installation
■Drawing of Overall Dimension
■Reference Position of Base
1. The bearing capacity of base is designed as per the weight of unit during operation.
2. The base may be of U-steel (designed by users as per overall dimensions of the unit) or
concrete structure and shall have flat surface.
3. A 10-20 mm rubber shock pad shall be placed between the unit andthe base.
4. The unit and the base may be fastened with ø16 or ø18 anchor bolts.
Unit Base Diagram
CA0035EAND
Unit Base Diagram
••••
■
■

17
CA0070EAND
◆Unit Base Diagram
CA0100EAND/CA0130EAND
◆Unit Base Diagram
Water Outlet
Water Inlet
Draining Valve
Electric control cabinet
0001
527
5281
0551
1320
1320
2170
0712

18
Selection Installation Position
■For the better cooling (heating), the installation position of the chiller unit shall be selected as per the followings:
■The unit shall be installed at a place where the hot air exhausted by the unit is not sucked back, that exhausted
by other unit is not sucked and sufcient space is reserved for the unit maintenance.
■Exhaust and suction channels of the chiller unit shall be free of any barrier that will block the air ow.
■The unit is installed at a well ventilated place to improve the heat exchange.
■The installation position shall have enough strength to withstand the unit weight and the vibration
during operation.
■The unit shall not be installed at a place that is dirty, oily, salty and exposed to a large amount of sulfur gas.
■The chiller unit shall not be installed at such place where ammable gas may leak. Because the ammable gas
leaked and accumulated around the unit may lead to explosion.
■The chiller unit shall not be installed at such a place exposed to strong wind or typhoon or accumulated
rainwater and snow. If possible, auxiliary equipment for preventing rainwater, snow and direct sunshine may be
provided.
■The unit base shall be made of concrete or support. Full consideration must be given to oor strength, drainage
(water is drained from the unit during operation) and pipe and wire route in the base construction. If the base is
not strong enough, the unit may fall down, causing unit damage or personal injury.
■The chiller unit shall be rmly fastened with anchor bolts to prevent falling down due to earthquake or strong
wind In order to withstand strong wind and earthquake, the unit must be positioned properly and can not be
installed at such a place exposed to strong wind.
■Depending on installation conditions, vibration may be transferred to tted parts, and base plates and walls may
produce vibration and noise. Therefore, proper vibration protections
(e.g. setting shock pad, dumper bracket, etc.) shall be provided.
■Edges and corners must be positioned correctly. The improper installation may lead to instability, resulting in
bending of mounting feet. Any improper installation may cause the falling down of the unit, leading to
personal injury.
■The unit shall be positioned so as to minimize the impact on residences.
■Pre-installation Preparation
■Cargo inspection
All units are rmly bolted on wood trays, subject to ex-factory inspection and lled with accurate amount of
R410a refrigerant and refrigeration oil for the unit operation. Upon the receipt, you shall carefully inspect cargoes
for any damage during transport and conrm all ordered parts and accessories are delivered.
You shall inform delivery man of any damage immediately. And you shall inform problem to us other than
appearance damage immediately.
■Handling
You shall handle the unit by a forklift or crane. If a crane
is used, the top and side panel of the unit shall be protected
by appropriate spacers (as shown in the gure). During the
handling, the unit shall be kept horizontal and not be inclined
for more than 30°, and the unit damage due to violations shall
be avoided.
■Disassembly
Place the unit at a desired position, cut binding tapes, remove
the external crate, unscrew bolts and remove the wood base
from the unit bottom.
Spacer
Spacer
<30°, Lifting rope
(two pieces)