3
80-150 kW Frame & Header Kits Manual
1 INTRODUCTION
This technical data contains information for dimensioning & assembly
of a cascade system kit for the Evo S.
Frame and header kits are available 'in line' congurations only.
GENERAL DESCRIPTION OF FRAME & HEADER KITS
A requirement to spread the total required heat output over several
boilers can be accommodated by the use of the ACV multiple boiler
frame & header kit options.
All headers and pipe work should be insulated in accordance
with the Non Domestic Building Services Compliance Guide. To
ensure compliance with the maximum heat loss criteria, insulation
thickness should be calculated according to BS EN ISO 12241 using
standardised assumptions.
* Max 6 x 100 kW only.
2.1 FRAME AND HEADER KIT DESIGN OPTIONS
The Evo S boilers are suitable for use in a multiple boiler conguration. The Evo S multiple boiler system is available in side by
side and giving the opportunity to choose the optimum footprint size or wall space for a given output. 80-150 kW kits include the
support frame. Boilers can be wall mounted required.
2 GENERAL DESCRIPTION OF SYSTEMS
continued . . . . .
Available Rig
Congurations
Total Output
Required kW
Number of boilers
and Frames
Footprint Size
W x D x H (mm)
Frame and Header Kit
Range Size Prod. No
Single Frame Congurations 80-120 1 500 x 704 x 1535 DN80 XB150011
Twin Frame Congurations 160-240 2 1000 x 704 x 1535 DN80 XB150012
Triple Frame Congurations 240-360 3 1500 x 704 x 1535 DN80 XB150013
Quad Frame Congurations 320-480 4 2000 x 704 x 1535 DN80 XB150014
Five Frame Congurations 400-600 5 2500 x 704 x 1535 DN80 XB150015
Six Frame Congurations 480-600 6* 3000 x 704 x 1535 DN80 XB150016
Available Rig
Congurations
Total Output
Required kW
No of boilers
and Frames
Footprint Size
W x D x H (mm)
Size Frame and Header Kit
Range No sep/
LLH PHEX sep
Single Frame Congurations 150 1 500 x 794 x 1830 DN100 XB150017 XB150023
Twin Frame Congurations 300 2 1000 x 794 x 1830 DN100 XB150018 XB150024
Triple Frame Congurations 450 3 1500 x 794 x 1830 DN100 XB150019 XB150025
Quad Frame Congurations 600 4 2000 x 794 x 1830 DN100 XB150020 XB150026
Five Frame Congurations 750 5 2500 x 794 x 1830 DN100 XB150021 XB150027
Six Frame Congurations 900 6 3000 x 794 x 1830 DN100 XB150022 XB150028
Note. All boilers need to be sized in accordance to the total required heat load and the modulation capabilities of the appliances.
H=Height from oor to top of frame, D=Depth from installed wall to front of kit, W=Width of installed kit
DN80 DN100
XB150030 XB150031
kW Product No.
Evo S 80 100008264400
Evo S 100 100008264500
Evo S 120 100008264600
Evo S 150 100008264700
Table 1 80-120 kW
Table 2 150 kW only
Table 3 Available Evo S Boilers Table 4 Low Loss Header Accessories
** See Table 6 for Gas Header sizing.
** See Table 6 for Gas Header sizing.