HANYOUNG NUX GE Series User manual

1 2
MD0106E121109
• If the user use the product with methods other than specified by the
manufacturer, there may be bodily injuries or property damages.
• If there is a possibility of an accident caused by errors or malfunctions of
this product, install external protection circuit to prevent the accident.
• Since this product does not have the power switch or a fuse, please install
those separately on the outside. (Fuse rating: 250V 0.5A)
• To prevent damage or failure of this product, please supply the rated
power voltage.
• To prevent electric shock or equipment failure, please do not turn on the
power until completing wiring.
• Since this is not explosion-proof structure, please do not use in a place
where combustible or explosive gas is around.
• Never disassemble, modify, or repair the product. There is a possibility of a
malfunction, an electric shock, or a risk of fire.
• Please turn off the power when mounting/dismounting of the product. This
is a cause of an electric shock, a malfunction, or failure.
• Since there is a possibility of an electric shock, please use the product as
mounted on a panel while the power is being supplied.
• The contents of the instruction manual are subjective to change without
prior notice.
• Please make sure that the specification is the same as what you have
ordered.
• Please make sure that the product is not damaged during shipping.
• Please use this product in a place where corrosive gas (such as harmful
gas, ammonia, etc.) and flammable gas do not occur.
• Please use this product in a place where there is no direct vibration and a
large physical impact to the product.
• Please use this product in a place where there is no water, oil, chemicals,
steam, dust, salt, iron or others (Contamination class 1 or 2).
• Please do not wipe this product with organic solvents such as alcohol,
benzene and others. (Please use mild detergent)
• Please avoid places where excessive amounts of inductive interference
and electrostatic and magnetic noise occur.
• Please avoid places where heat accumulation occurs due to direct sunlight
or radiant heat.
• Please use this product in a place where the elevation is below 2,000 m.
• Please make sure to inspect the product if exposed to water since there is
a possibility of an electric leakage or a risk of fire.
• If there is a lot of noise from the power line, installing an insulated
transformer or a noise filter is recommended. The noise filter should be
grounded on the panel and the lead wire between the output of the noise
filter and the power terminal of the instrument should be as short as
possible.
• It is effective against noise if making the power lines of the product the
twisted pair wiring.
• Please do not connect anything to the unused terminals.
• Please connect wires properly after making sure the polarity of terminal.
• Please use a switch or breaker (IEC60947-1 or IEC60947-3 approved)
when the product is mounted on a panel.
• Please install a switch or break near the operator to facilitate its operation.
• In order to use this product properly and safely, we recommend periodic
maintenance.
• Some parts of this product have limited expected life span and aged
deterioration.
CAUTION
Model Code Description
GE
☐ -☐ ☐ ☐ ☐
Digital counter & timer
Appearance
3 96(W) × 48(H) ㎜
4 48(W) × 48(H) ㎜
672(W) × 36(H) ㎜
7 72(W) × 72(H) ㎜
Type P Preset counter
T Total counter (Only for indication)
Displayable digit 4 4 digits (9999)
*GE3 and GE7 are not selectable
66 digits (999999)
Setting stage
(excludes the total counter)
11 Stage setting
22 Stage setting
Power supply voltage A 100 - 240 V a.c 50 - 60 ㎐
D24 - 60 V d.c / a.c 50 - 60 ㎐
※ If you want to input and output type, please contact HANYOUNG sales office
Digital counter & timer
GE series
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
INSTRUCTION MANUAL
1381-3, Juan-Dong, Nam-Gu Incheon, Korea.
TEL:(82-32)876-4697 FAX:(82-32)876-4696 http://www.hynux.net
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
LIPPO CIKARANG CICAU, CIKARANG PUSAT BEKASI 17550 INDONESIA
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
HEAD OFFICE
INDONESIA
FACTORY
HANYOUNGNUX CO.,LTD
PT. HANYOUNG ELECTRONIC INDONESIA
Do not touch or contact the input/output terminals because it may cause
electric shock.
DANGER
WARNING
• The warranty of this product (including accessories) is 1 year only when it
is used for the purpose it was intended under normal condition.
• When the power is being supplied there should be a preparation time for
the contact output. Please use a delay relay together when it is used as a
signal on the outside of interlock circuit or others.
Suffix code
Specification
Model
GE4 GE6 GE3 GE7
Power supply voltage
100 - 240 V a.c 50 - 60 ㎐, 24 - 60 V d.c/a.c (voltage fiuctuation : ±10 %)
Power consumption
Approx. 13.5 VA(100 - 240 V a.c), approx. 5 W(24 - 60 V d.c),
Approx. 9 VA(24 - 60 V a.c)
Charater height(㎜)
11 (computed), 8 (set value) 13 (computed), 10 (set value)
Input counting
speed
1 cps, 30 cps, 1 kcps, 10 kcps
(ON/OFF ratio : 1:1, "H" level : 5 - 3 V d.c, "L" level : 0 - 2 V d.c)
Memory back-up
10 years (non-volatile memory)
Input
CP1, CP2, RESET, BATCH RESET (exclude TOTAL) 4inputs
[H] level 4 - 30 V d.c, [L] level 0 - 2 V d.c Internal pull up/pull down
resistance connection due to NPN/PNP setup
Min input
signal
Counter
External reset Min. input signal range : select among 0.1 ㎳, 1 ㎳, 20 ㎳
Timer
START, INHIBIT, RESET Min. input signal range : select either 1
㎳
, 20
㎳
External supplying power
12 V d.c 100
㎃
max
ONE SHOT output 0.01 - 99.99 s [OUT1, OUT2(OUT)]
Control
output
1st level
1c (OUT) 1a (OUT) 1c (OUT)
2st level
1a (OUT1), 1c (OUT2)
capacity
a contact : 250 V a.c 3 A (resistive load), b contact : 250 V a.c 2 A
1st level
NPN 2contacts (OUT, BAT.O)
2st level
- - NPN 2 contact (OUT1, OUT2)
capacity
Open collector, 30 V d.c, 100
㎃
max
Timer action error With power start : ±0.01 % ±0.05 sec max
With reset start : ±0.005 % ±0.003 sec max
Insulation
resistance
100 ㏁ min (500 V d.c) Between current-carrying terminals and exposed
non-current -carrying metal parts.
Dielectric strenght
2000 V a.c 60 Hz for 1 min (diferrerent recharging terminal from each other)
Noise resistance Square wave by the nois simulator (1
㎲
pulse per 16
㎳
)
±2
㎸
(Power supply terminal), ±500 V (Input terminal)
Vibration resistance
10 - 55
㎐
, peak amplitude 0.5
㎜
, 3 axis each direction for 2 hour
Shock resistance 300
㎨
, 3 axis each three times
Relay life
Electrical
100 thousand times min (250 V a.c 2 A resistance load)
Mechanical
1 million times min
Protection structure
IP65 (Front part only)
Storage temperature
-20 ℃ ~ 65 ℃
Ambient temperature
humidity
-10 ℃ ~ 55 ℃, 35
%
~ 85
%
RH
Weight 133 g max 138 g max 203 g max 203 g max
Contact
Non-contact
Safety information
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality.
DANGER
WARNING
CAUTION

1 2
Setting lists Setting information
Divice
change
1st level setting type
2nd level setting type
1st level setting counter
2nd level setting counter
Input
mode
CP1, CP2 Individual input UP mode action
CP1, CP2 Individual input DOWN mode action
Refer to the input action (counter)
Output mode
Refer to the output action (counter)
Output time
(0 : Self holding output, 0.01 - 99.99 : Delay output time)
(0.01 - 99.99 : One shot output time)
Output time
It is not displayed in the 1st level output product
BATCH output
Set the batch output port
Relay Transister
Computation speed
Set or when using contact
Pre-scale
Default value
Pre-scale
decimal point
setting
Able to set up to 5 decimal points
and able to shift up to 4 digits
Display unit
decimal point setting
Applied when set decimal point on the display
unit and able to set up to 3 decimal point
RESET TIME
Minimum signal range of external RESET signal input
Power
backup memory
Save the computed value when power is OFF
Initialize the computed value when power is OFF
Input logic
check
Varies depending on the handling of internal seitch
Key lock Key Lock Key lock cancellation
all keys prohibited ( excluded )
Using , , , keys prohibired
Using font part prohibited
Pressing key will return to operation mode without saving. Return to operation mode if there is
no key input more than 60 seconds. With function setup mode, it ignores external signal input and
maintains output in OFF state
①
②
③
④
⑤⑥⑦⑧
⑨
⑩
⑫
⑪
①
②
③
④
⑤⑥⑦⑧
⑨
⑩
⑫
⑪
①
②
③
④
⑤⑥
⑦
⑧
⑨
⑩
⑪
⑬
①
②
③
④
⑤⑥
⑦
⑧
⑨
⑫
⑩
⑪
⑭
During the first 100
㎳
after power input and first 200
㎳
after power
opening, it is consider as ascend and descend time of internal power
and external output power. Therefore, it does not operate during
unstable period in order to prevent from malfunction which is caused by
unstable output operation of external sensor
※ Supply signal only after 100
㎳
following the power input.
※ Supply power only after 200
㎳
following the power shutdown.
※ Minimum Signal Time refers to ‘ON’ Time.
Maximum coefficient speed is maximum response speed when entering in the
duty ratio (ON. OFF ratio) of coefficient input signal as one to one ratio (1:1)
① As for the input signal below the maximum coefficient speed, if either ON or
OFF time is unilaterally less than the standard value of minimum signal width
then it may not be counted
② Minimum Input Time
• TOTAL product does not display setting lists such as output mode, OUT2
output time, OUT1 output time, BATCH output and etc
• 1st setting product does not display OUT1 output time
•
Selecting for BATCH output setting, it limits the setting function and display function.
NONE
▒ GE3
▒Counter function setting mode
▒ GE6
① Coefficient display (RED FND)
Display coefficient value (counter), time process value (timer), batch coefficient
value and setup list.
② Setup display (GREEN FND)
Display setup value (counter), setup time (timer), batch setup value, instant
output setup (batch setup is 0 in Timer) and setup contents
③ SET1, SET2 (SET), BAT
Indicates the status of coefficient section and setup section
(BAT lamp corresponds to batch status.)
④ TIM (Timer)
This flashes when the timer progresses and remains lighted when the device
stops from inhibit input or reset.
(It is indicated in Change Mode of the device during TIM/TTWIN setup.)
⑤ CNT (Counter)
This is indicated during 1CNT/2CNT setup in Change Mode of the device.
⑥ OUT1, OUT2(OUT), BAT.O (Output Action Indication)
• BAT.O lights up when the batch setup value is set. (OUT1 Output)
• BAT.O lights up and outputs when the device operates with the instant output
• where the batch setup value is 0 (timer).
• CP1, CP2, RST : Verification of Input Status. (Exclusively for TOTAL)
⑦
LOCK:Key Lock (KEY LOCK) Action IndicationThis lights up during Lock Setup.
⑧
: This key is for function setup Mode Entry and Mode change. It can also be
used for ending after saving when changing the setup value
⑨ : Setup value change Entry and Location shift
⑩ : UP Key
⑪ : RESET KEY ③When SET, BAT lamp light, RESET key will not operate.
⑫ : Batch and operation mode 1 stage and 2 stage conversion key. When BAT
lamp light, it is batch mode and keep operate.
⑬ + : Push both of keys together, It operate same as key.
⑭ : DOWN Key
※ TOTAL Model does not have Setup Indication Section, SET1, SET2 and BAT
Lamp. OUT1, OUT2, BAT.O change their use as CP1, CP2, RST Input Status
Check Lamp. 1 Stage Setup Model does not have SET1 and OUT1 Lamp, and
SET2 is displayed as SET and OUT2 is displayed as OUT.
▒ GE4
▒ GE7
Coefcient Speed Selection
Minimum Input Signal
1 cps 250 ㎳
30 cps 11 ㎳
1 K cps 0.3 ㎳
10 K cps 0.05 ㎳
Pressing the"MD" key in the operation mode for 2sec will set the funcion setting mode ( : Default set value)
Power supply Counter mode setting method
Maximum coefficient speed
Part name and functions

3 4
Post count up action
Coefficient value indication is maintained and setting up HOLD (0)
leads to self holding output. Also, setting up time leads to OUT2
output after one shot delay setup. OUT1 and OUT2 become OFF
when reset and return to Start.
Coefficient value indication is continuously processed and setting up
HOLD (0) leads to self holding output. Also, setting up time leads to
OUT2 output after one shot delay setup. OUT1 and OUT2 become
OFF when reset and return to Start
Coefficient value indication is continuously processed during START
state and OUT2 yields one shot output. Self holding output of OUT1
is turned off when OUT2 is turned OFF
(Repetitive action)
Coefficient value indication is maintained during One Shot Time, and
then resets. (Repetitive Action)
Coefficient value indication is continuously processed. OUT2 yields
one shot output. Self-maintenance output of OUT1 is turned off after
one shot time of out2
When coefficient value returns to initial state, then coefficient value
indication is maintained for one shot time. After processing one shot
time, it displays processed coefficient value.
(Repetitive Action)
Coefficient value increases and OUT2 yields One Shot Output. The
device is reset after the One Shot Output.
(Repetitive Action)
Coefficient value is maintained and OUT2 yields one shot output.
OUT1 and OUT2 are independent from each other.
If OUT1 is same as setup value of SET1, it leads to one shot output
or self-maintenance output. (In case of Level 1 setup type, OUT1
and OUT2 are same each other)
Reset refers to OUT1 and OUT2 become OFF and coefficient value
being initialized.
Output
Mode
Input Mode
UP DOWN UP/DOWN/A,B,C
※ As for 1 Stage counter (OUT), it is the same as
2ND output (OUT2) action.
One Shot output time
0.01s~99.99s
Self holding output
Self holding output
One shot output of OUT1 output
One shot output of OUT1 output
Self holding output
Input connection method
Counter output action mode
●PNP (voltage input) state
Input
type
PNP setting NPN setting
Voltage Input Input PNP O.C
NPN voltage Input
NPN O.C
H 5 - 30 V d.c 5 - 30 V d.c 0 - 2 V d.c 0 - 2 V d.c
L 0 - 2 V d.c OPEN 5 - 30 V d.c
OPEN
※ For receiving Open Collector Input, Input Logic (PNP/NPN) Conversion Switch is embedded
internally to Pull up / Pull down the resistance of 4.7 kΩ (NPN Setup during shipment)
▒
Input Logic Selection
Operate the conversion switch after confirming NPN/PNP indication which is displayed on the right
●NPN (non-voltage input) state
▒
Input connection

3 4
‘A’ needs value greater than min signal width, B need value greater than half of min signal width.
■Set value is first to decrease within Down Mode
•-99999 (6 digits),-999 (4 digits), it flashes and does not get counted
• Within UP MODE, it increases to the maximum display value, initializes to 0 and
increases again
UP DOWN UP/DOWN/A,B,C
• When using encoder (incremental method). Please use
Noice) The input Login of above list is PNP.
※ Total (product) does not have output time list and BAT setting list
※ 1st level output model does not support twin timer function
※ To prevent chattering during the use of Contact Input Counter, setup the
coefficient speed at 1 or 30 cps in Function Setup Mode.
※ Input Logic Setup Status can be
verified in Function Setup Mode.
※ Internal Impedance is 4.7㏀, and
switches over to Pull Up or Pull Down
from NPN/PNP Selection.(Refer to
Input Connection)
Setting lists Setting information
Chang
the device
1st level setting type
2nd level setting type
Timer
Twin Timer
Default value
Decimal system / Sexagesimal system
TIM (TIMER setting)
TTIM (TWN TIMER setting)
0.01 s ~ 999999 h
UP / DOWN selectable
Not display in the product (display only) and
some of operation mode in the TWIN TIMER
one shot or self-maintenance selectable
Set Batch output port
: Relay : Transistor
Save current time and batch counter
value when OFF the power
Initialize the computed value when
OFF the power
Non-voltage
Voltage input
key lock setting in the operation state
(4 levels)
Key lock cancellation
all keys prohibited ( excluded )
Using , , , keys prohibired
Using font part prohibited
Input terminal minimum input time
selectable
1 ㎳ / 20 ㎳ (INHIBIT, START,
RESET)
Varies depending on the handling of internal switch
Changing the setting in the menu is prohibited, Only reading
1st level output model does not
support please refer to the
output action mode chart for detailed
information
Chang
the system
Operation
mode
Output
time
BATCH
output
Input
time
Power
backup memory
Input
logic check
Key lock
Time
range
Total(display only)
Counter input action
Timer mode setting method
Counter output operation of exclusive indication (GE-T)
▒Function Setup Mode (Timer / Twin timer)

5 6
TIM(TIMER) Setting TTIM(TWIN TIMER) Setting For total model
Power RUN / ON delay
Signal START / ON delay
Signal START / ON delay
Signal RUN / ON delay
Signal RUN / OFF delay
Interval / Signal RUN
Interval / Signal START
Flicker / Signal START
Flicker (Counter Mode)
Flicker (Counter Mode)
Flicker (Counter Mode)
Signal Addition
Power RUN
–ON delay
Power RUN
–OFF delay
Signal START
–ON delay
Signal START
–OFF delay
Power ON RUN
–OFF time
Power RUN
Signal RUN
Range selection symbol 4 digits time range 6 digits time range
UP DOWN
Decimal System Sixagecimal system Decimal System Sixagecimal system
99.99 s 59.99 s 9999.99 s 59 m 59.99 s
999.9 s 9 m 59.9 s 99999.9 s 9 h 59 m 59.9 s
9999 s 59 m 59 s 999999 s 99 h 59 m 59 s
9999 m 99 h 59 m 999999 m 9999 h 59 m
9999 h 99 d 23 h 999999 h 9999 d 23 h
▒ Signal START / ON delay
▒ Signal START / On delay (Counter F output mode action)
▒ Signal RUN / ON delay
▒ Signal RUN / OFF delay
▒ Interval / Signal RUN
• Output will become ON only when START (CP2) is in ON state and time will
display the initial value.
• Time activates the initial value to operate only when START (CP2) is in OFF state
• When setup time is elapsed, indication value will be initialized and output will
become OFF.
• Runs when START (CP2) is ON and Resets when it is OFF.
• Output is in ON state during the set time and initial value will be initialized and
output will become OFF when set time elapses.
•
Runs when CP2 (START) is ON and Resets when it is OFF within in the initial setup value.
• When setup time is exceeded, it maintains the displaying value and when sets the
, it yields the ON shot output.
• Runs when START (CP2) is ON within the initial setup value
• When setup time is exceeded, it yields on shot output only when maintaining
the indication value and setting up the ( ).
※ 1 Stage Setup Type Output is OUT.
※ INHIBIT (CP1) temporarily stops the time.
▒ Power RUN / ON delay
• Runs when ‘POWER ON’
• When Reset signal is authorized, process value initializes and runs.
•CP1/INHIBIT function stops the time.
•[S.---] is activated when CP2 (START) is ‘ON’
•[S ---] is activated when CP2 is maintained ‘ON’, and resets when ‘OFF’.
•[P ---] activates with ‘POWER ON’
※ Setup as in order to compensate for interruption of electric power during
‘POWER OFF’
(Indicates the Memorized Value when electric power is inputted again.)
● Example of non-contact output
• When using the inductive load (relay and
etc), please conect the surge observer
(diode and varistor) on the both ends of
the load. Also please use with GND since
the internal circuit and non-contact output
are isolated from one another. please
select the proper power for load and
load. Non-contact output cannot exceed
the max 30 V 100
㎃
.
● Example of contact output
• Avoid the flow of excessive current since
it is 250 V a.c NO 3 A (loadresistance)
NC 2 A
(load resistance), and theconnection
must correspond to standard connection
method.
※ s : second m : minute h : hour d : day
Timer time range
Output connection
Timer operation mode
Timer output action mode
• Runs when START (CP2) is ON in the initial set value
• When setup time is exceeded, display value increases and yields output (Yields
one shot output with setting)

5 6
▒ Power RUN / OFF time
▒ Signal START - OFF delay
▒ Signal START - ON delay
▒ Power RUN - OFF delay
• t : possible to set from 0 to 99.99 sec by setting fuse time with
• RUNS when POWER is ON
• Runs when START (CP2) is ON in the initial set value
• OFF Output for T1 Time / ON for T2 Time. Repetition
• Initializes and stops when RESET is ON
• RUNS when POWER is ON
• Runs when START (CP2) is ON in the initial set value
• ON Output for T1 Time / OFF for T2 Time. Repetition
• Initializes and stops when RESET is ON
• Set the individual output control and fuse time
• Possible to set max 99.99sec when fuse time is set as .
• Runs when Power is ON
•
①
Yields the output OUT1 during SET1 TIME AND OUT1 OFF during fuse time
•
②
Yields the output OUT2 during SET2 TIME and OUT2 OFF during fuse time
• Repeats the operation
①
and
②
▒ Interval / Signal START
▒ Flicker / Signal START
▒ Signal Addition
[HOLD] Setup (when output time is set at HOLD)
- Setup Set Time in Run Mode
• Maintains the indication of initial value when Power is “ON”
• Runs when becomes START (CP2).
• ON/OFF Repetitious Action of control output after reaching
the Set Time.
• Initializes and stops when Reset is “ON”
ONE SHOT TIME Setup (when output time is set at more than 1)
- Setup Set2 Time in Run Mode.
• Maintains the indication of initial value when Power is “ON”
• Runs when Power is “ON”
• One Shot Output after reaching the Set Time.
• Initializes and stops when Reset is “ON”
• Runs when START (CP2) becomes ON
• Output is in ON state during the set time and initial value will be initialized and
output will become OFF when set time elapses
• Runs when maintaining START (CP2) as ON state and Holds when
maintaining START (CP2) as OFF state (cumulative timer function)
※ does not operate within the DOWN time range
• RUNS when POWER is ON
• ON Output for T1 Time / OFF for T2 Time. Repetition
• Initializes and stops when RESET is ON
▒ Power RUN - ON delay
• RUNS when POWER is ON
• OFF Output for T1 Time / ON for T2 Time. Repetition
• Initializes and stops when RESET is ON
▒ Flicker (Counter Mode)
▒ Flicker (Counter Mode)
▒ Flicker (Counter Mode)
Twin timer output action

7 8
▒ Batch computation and output operation
• Batch counting value continues to increase until Batch Reset is supplied in.
• When batch coefficient value exceeds 999999
(4 rows 9999), it initializes to 0 and display.
• In case of batch display state (BAT lamp is lighted), press the key (located
on the front side) to reset the batch value.
• Even in the batch display state, counter/timer action still operates normally.
• Batch coefficient increases when yielding the output as OUT2 (OUT)
• Batch output yields the output as (BAT.O). (BAT.O lamp is lighted)
▒ Instant output setup
• Function switches over to instant output when the batch
value is set at 0. (BAT.O lamp is lighted)
▒ Batch Counter setup Method
1. Press key
Enter to setup state, 6 rows (4rows) FND flickers, set "100" by pressing
/ key (When use want to set 100 batch.)
2.
Pressing key will complete setup. (Pressing key will exit without changing)
3. Pressing key will return to operation mode. (Left side BAT lamp off)
※ Properly operates within BATCH display mode
※ Possible to setup BAT only with , BAT setting.
48.0
48.0
96.0
48.0
5.089.6
107.6
44.8
91.0
45.0
60.0 min
120.0 min
66.5
32.0
97.0
57.0
72.0
36.0
86.0
66.0 15.0
30.5
5.0
84.3
64.3
5.0 15.0
44.8
45.0
45.0
60.0
60.0
72.0
72.0
72.0
92.0
5.015.0
67.0
68.0
68.0
82.0
82.0
▒ Signal RUN
• In case of when Power is ON, supplying in the RUN RESET signal will initialize
the indicating value and setting up the RUN Down mode will start to decrease
the value from the set value.
• OFF set is available for the up time range of decimal system (press key for 2 sec)
▒ Power RUN
[Unit:㎜]
Dimension and panel cutout
Batch counter
Timer action of exclusive indication(GE-T)
▒ GE6
▒ GE3
▒ GE7
▒ GE4
●Dimension
●Dimension
●Dimension
●Dimension
●
Panel cutout
●
Panel cutout
●
Panel cutout
●
Panel cutout
• Runs when turning ON the START (CP2) and Resets when turning OFF the
START (CP2). Starts to decrease from the set time when Down Mode is
being setup.

7 8
▒ GE4-P 1
▒ GE3-P 2
▒ GE7-P 2
▒ GE4-P 2
▒ GE6-P 1 ▒ GE6-P 2
▒ GE3-P 1
※ Connection of NPN input
※ GE4-T6: Total model does not have relay output with transistor.
※ Connection of NPN input
※ GE6-T6 : Total model does not have relay output with transistor.
※ Connection of NPN input
※ GE3-T6 : Total model does not have relay output with transistor.
※ Connection of NPN input
※ GE7-T6 : Total model does not have relay output with transistor.
▒ GE7-P 1
Connection diagram
This manual suits for next models
4
Table of contents
Other HANYOUNG NUX Cash Counter manuals
Popular Cash Counter manuals by other brands

Trotec
Trotec PC220 Quick start manual

Electro Industries/GaugeTech
Electro Industries/GaugeTech Shark 100B quick start guide

Synetica
Synetica enLink Status-P user guide

Eaton
Eaton Durant AMBASSADOR Series Installation and operation manual

MZ electronic
MZ electronic EV-030 Instructions for use

Innovative Instruments & Controls
Innovative Instruments & Controls Cx-428 User's operating manual