HealthWay 1200SC Series User manual

InstallationManual
1200SC ®
SELF CONTAINED DFS AIR CLEANING SYSTEM

©HealthWay 2015#10057

®
1200 SC Self Contained DFS Air Cleaning System
Installation and Operation Manual
MODELS
1200SC-120-1AL
120V
50/60Hz
Phase 1
1200SC-220-1AL
220V
50/60Hz
Phase 1
1200SC-220-3AL
208-240V
50/60Hz
Phase 3
1200SC-440-3AL
380-460V
50/60Hz
Phase 3
HealthWay’s DFS Technology (Disinfecting Filtration System) surpasses all other types of filtration. This revolutionary
technology traps microorganisms such as bacteria, mold and viruses, reduces bioburden and inhibits microorganism’s
growth through Microbiostatic condition, resulting in the most powerful indoor air purification in the world.
SPECIFICATIONS
•12 gauge aluminum construction
•Pre-drilled standing flanges to
accommodate attachmentto other
systemcomponents
•Dual access door, swing-open typefor
filter service from either side
•High-memory sponge neoprene door
gaskets to ensure door to filter seal
•Aluminum filter track design for 2”
standard prefilter and a track for High
Energy Grid Frame
•A polypropylene fin seal on the mainfilter
track to eliminate filter airbypass
FEATURES
• High Air Flow Capacity –delivers high CFM with low
energy consumption
• Modular Design –allowsfor stacking of modules to meet
any air flow capacity. Single Module capacity is 1200 CFM
–Nominal flow.
• 99.99% Filtration Efficiency –down to a size of 0.007
microns
• Self-Contained Design –results in no pressure drop when
installed on the Air handlingunit
• Independent Air flow/Distribution Control –to facilitate
Installation anywhere in thespace
• Patented V-Bank Filter –increases surface area and provides
higher dust loadingcapacity
• Three times longer filter span –compared to conventional
HEPA Filtration –Lower MaintenanceCost
• Housing Design –provides a 100 % seal around the filter
• Ease of Maintenance –filter access from either side of the unit.
• Electrical Panel –electronic components are contained in a
separate electrical box (notshown)
• Variable Frequency Drive (VFD) –modulation of airflow and
connectivity to Building Management Systems(BMS)
formonitoring
• Magnehelic Pressure Gauge –monitoring of pressure differential
across the filters
•Optional
Auto-FlowMonitoring
V- bank VOC Filter (70 lbs –Adsorbent Blend)
HydratedPhoto Catalytic Oxidation (HPCO) Odor-TVOC
Cartridge

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
©HealthWay
2015
Part Number: #10057
Revision Date: April 2015
Copyright: © 2015 All rights reserved.
Address: HealthWay, Inc.
3420 Maple Ave.
Pulaski, NY 13142
Phone No: 315-298-2904
1-800-843-3860
Fax No: 315-298-6992
Email: info@healthway.com
LIMITED WARRANTY
This one year Limited Warranty applies only to the repair and replacement of any manufactured or supplied part of
this product which, upon inspection by HealthWay authorized personnel, proves to have failed in normal use due to
defects in material or workmanship. A return authorization must be obtained before any product is shipped to the
manufacturer for warranty repair and all transportation charges must be prepaid all work must be performed by a
HealthWay authorized technician. The sole responsibility of HealthWay under this Limited Warranty is, at
its sole discretion, to either repair or replace a duly registered product (or defective part thereof) with the same
comparable model within a reasonable period of time, subject to the following exclusions, limitations, statutory rights,
and warranty claim procedures. This Limited Warranty is exclusive, and HealthWay expressly disclaims all other
or additional warranties, whether written or oral, expressed or implied, including, but not limited to, warranties of
merchantability, workmanship, or fitness for a particular purpose.
Exclusions:
A. This Limited Warranty does not apply, or is void, as to any product or part damaged by (1) accident, misuse,
abuse, or lack of reasonable care or normal maintenance; (2) installation or operation under conditions other
than those recommended by HealthWay; (3) subjection of the product to any but the specified voltage;
(4) servicing or disassembly by unauthorized personnel; (5) defacing the serial number; or (6) modifying the
original factory assembled unit in any way.
B. THIS LIMITED WARRANTY DOES NOT APPLY TO SHIPPING CHARGES FOR PRODUCT SHIPPED TO OR
FROM THE FACTORY OR DESIGNATED SERVICE CENTER IN CONNECTION WITH WARRANTY CLAIMS
NOR DOES IT APPLY TO ANY DAMAGES OCCURRING DURING SUCH SHIPMENT.
C. This Limited Warranty does not apply to labor for installation, removal, re-installation, and/or travel or shipping
expenses and related expenses.
This Limited Warranty does not apply to replaceable filters.
Limitations:
HealthWayshall not be liable for property, incidental, and/or consequential damages of any kind and, unless otherwise
prescribed by applicable state law, HealthWay shall not be liable for personal injury resulting from malfunctions,
defects, misuse, improper operation or installation, or alteration of a HealthWay product or any part thereof. The
exclusive remedy for a breach of this Limited Warranty is the repair or replacement of the defective product. In no
case, shall liability under any other remedy prescribed by law exceed the purchase price of the product.
Warranty Claim Procedure:
This information is provided as a guide regarding warranty claim procedures for HealthWay Products, Inc air
purification systems.
1. Determine model number from the label on the unit.
2. For technical support, warranty information, warranty parts or replacement parts, call HealthWay Products from
The following is a history of the
Instruction Manual for
1200 SC Self Contained DFS Air Cleaning System
Initial Printing ............................... 5/12
Revision........................................ 4/15

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
©HealthWay
2015
8:00 AM-5:00 PM EST a HealthWay representative will help you troubleshoot and diagnose the problem.
Warranty matters involving products sold through a manufacturer representative should be directed to the
appropriate representative.
3. Important: Do NOT return anything without a Return Authorization.
4. All returned parts are quality tested. If the returned part is found not to be defective, you may be invoiced for the
new part.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
©HealthWay
2015
Table of Contents
Safety Precautions.......................................................................... 7
System Overview..........................................................................9
UnitDescription................................................................................9
ComponentDescription..................................................................10
Receiving and Unpacking..............................................................11
Receiving .......................................................................................11
Storage...............................................................................................11
Unpacking and Inspection..............................................................11
Installation Procedures...................................................................13
PowerRequirements......................................................................13
LocationDetermination ..................................................................13
Standard Inlet/Return Duct Connection .........................................14
Standard Supply (Outlet)Duct Connection....................................14
ElectricalConnection .....................................................................15
Low VoltageControl Connection....................................................15
System Operation...........................................................................17
Maintenance ...................................................................................19
PrefilterReplacement.....................................................................19
V-Bank MainFilter Replacement ...................................................20
Cleaning the Unit............................................................................21
Parts List........................................................................................22
Troubleshooting.............................................................................23
DFS Troubleshooting Guide...........................................................24
Figures and Schematics.............................................................1-1
Figure A.........................................................................................1-1
1200SC-120-1ALSchematic.........................................................1-2
1200SC-220-1AL Schematic ........................................................1-3
1200SC-220-3AL Schematic........................................................1-4
1200SC-440-3AL Schematic........................................................1-5

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
7
©HealthWay
2015
Safety Precautions
SAFETY PRECAUTIONS
Personnel, who will operate this system, or those who will perform maintenance thereon, must be given all
manuals and other instructions regarding safe operation of the filtration system.
This manual contains general recommendations, but specific requirements may apply to individual
installations. Such requirements are outlined in federal, state, and local codes. Compliance with
applicable codes and strict adherence to these installation instructions are the sole responsibility of the user.
This symbol will be used throughout this manual to indicate safety checkpoints.
Failure to heed these warnings and notices may result in damage to the unit and/or
injury or death topersonnel.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
9
©HealthWay
2015
System Overview
UNIT DESCRIPTION
The Air Cleaning System is a high performance system that utilizes patented award winning Disinfecting
Filtration System technology. DFS technology electrically enhances a low efficiency, high flow, low pressure
drop (0.79” @ 1200cfm) filter to high efficiency while retaining the low pressure drop and longer life
advantages of the base filter material. Thistechnologyhas also beenshown to inhibitbacteriagrowthon thefilter.
The Electrical Components are located in a separate Electrical Box outside of the unit.
The 1200 SC Self Contained DFS Air Cleaning System is available in the following models:
Model
Power Requirement
Flow
V
Hz
Phase
60Hz
50Hz
1200SC-120-1AL
120
50/60
1
1200
1000
1200SC-220-1AL
220
50/60
1
1200
1000
1200SC-220-3AL
208-240
50/60
3
1200
1000
1200SC-440-3AL
380-460
50/60
3
1200
1000
Model Description:
1200SC-(Voltage)-(Phase)-(Housing Material)
Other Housing Material Options: SS=Stainless Steel G=Galvanized
Height
Width
Depth
Weight
Ship Wt
1200SC Unit
23in
584mm
28in
711mm
32in
813mm
190lb
86kg
217lb
98kg
Electrical Box
20in
508in
19in
483mm
9in
222mm
Please confirm your model number and follow the instructions for thatmodel. The
electrical power requirements for each individual unit are on the data plate label
adjacent to the electrical connections. These requirements supersede all other
inferences to powerrequirements.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
1
0
©HealthWay
2015
#1005
7
1
1
©HealthWay
2015
System Overview
System Overview Receiving and Unpacking
COMPONENT DESCRIPTION
The 1200SC DFS Air Cleaning System integrates the system components into a single, self-contained unit:
the Prefilter, V-Bank Main Filter and the High Energy Grid are accessible from the service door on either
side. The unit is also remotely controllable by using an optional remote controller/indicator. The fan inlet
screen is located on the back of the unit and provides protection from loose items being drawn into the fan
and thus damaging the unit and the internal components.
Electrical controls are located in a separate Electrical Box. They consist of the Main Power ON-OFF switch
with a Green LED to indicate HVPS power status.
Components
Efficiency
Pressure Restriction
(inch of w.g.)
Replacement
Period*
Initial
Final
Prefilter
MERV-8 (30% Efficiency)
0.22
1.00
1-4 times per year
DFS V-
Bank Main
Filter
99.99% Efficient
(down to .007 microns)
0.77
1.54
once a year
High Energy Grid
*Replacement period depends on the level of pollution in the environment
RECEIVING
Equipment is prepared for shipment in accordance with the Uniform Freight Classification. It is thoroughly
inspected at the factory and barring damage in transit, should be received in good condition.
When a freight carrier signs the HealthWay bill of lading, the carrier accepts the responsibility for any
subsequent shortages or damage evident or concealed. Inspection by the carrier of damage evident or
concealed must be requested. Evident shortage or damage should be noted on the carrier’s delivery
document before signature of acceptance. Claims must be made against the carrier by the purchaser.
Filtration systems are shipped as fully assembled filter units with field installation necessary. These filter
units must be handled and moved using proper rigging techniques, avoiding concentrated stresses that will
distort the parts.
STORAGE
If the unit is not to be installed promptly, store it in a dry place protected against moisture, dust, physical
damage, weather, corrosion and excessive heat.
UNPACKING AND INSPECTION
To un-crate the main unit, remove the strapping and the box top. Using the 4 eye-bolts, carefully remove the
unit from the box without damaging the fan inlet screen.
Carefully un-crate the components and identify each item according to the Component Description (on the
previous page) and the Electrical Schematics (located in the back of the manual). Inspect for damages not
previously evident.
Open the filter service door. The High Energy Grid wires may be viewed by removing the prefilter, confirm that
all wires are in place. The wires are spaced 1” apart. Avoid removal of the V-Bank Main Filter as the filterseal
may be compromised.
Make certain the V-Bank Main Filter is secure by checking to see if the bolts are tight.
Do not lift unitmanually.
Lift using good rigging techniques, using all foureye-bolts.
Components
Description
Impeller Fan
Backward curved motorized centrifugal impeller
Magnehelic Pressure Gauge
Monitoring of pressure restriction across the filters

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
1
3
©HealthWay
2015
Installation Procedures
POWER REQUIREMENT
The power requirements are as follows:
*Electrical disconnects may also be required - check local electrical codes
Model
Power
FLA
Maximum
Over-Current
Protection
Power Usage
V
Hz
Phase
AMPS
WATTS
1200SC-120-1AL
120
50/60
1
5.5/5
15
650/590
1200SC-220-1AL
220
50/60
1
2.7/2.2
15
585/495
1200SC-220-3AL
208-240
50/60
3
1.7/1.5
15
400/375
1200SC-440-3AL
380-460
50/60
3
1.1/0.9
15
485/435
LOCATION DETERMINATION
The filtration system location should be carefully planned with consideration given to the ease of access to
the electrical box and the filter service doors.
Enough room (min 30” or 76cm) must be available next to a filter service door for filter replacement.
If the filter unit is to be located on a platform or the floor it should be located 6” off the ground to facilitate
access to the filter turn down bolts; located on the filter inlet.
The inlet duct also must have at least 8” of straight duct before any bends are made.
The Electrical Box must be installed within 6’ of the unit.
There should be no use or spillage of powdered products, aerosols, sprays, or mists near the inlet connection to
the filter.
Do not installthe filtration system in an exterior environment, unless it is specificallymade for exterior installations.
Standard units are for indoor use only.
The wiring or strapping must be at least 350-pound test weight.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
Installation Procedures Installation Procedures
STANDARD INLET / RETURN DUCT CONNECTION
A 20” x 16” (out flanged) duct may be connected to the unit using the instructions below, refer to (fig-A)*:
Align duct with 14, threaded 10-32 holes on filter inlet panel.
Secure with 14, #10-32 x ¾” machine screws (G-4) being careful not to damage gasket. Do not use screws
longer than ¾” as damage to the filter unit may occur.
The inlet duct must have at least 8” of straight duct before any bends are made to facilitate access to the
filter turn down bolts.
All ductwork must be kept clean and be properly sealed.
STANDARD SUPPLY (OUTLET) DUCT CONNECTION
A 22” x 14” (out flanged) duct may be connected to the unit using the instructions below, refer to (fig-A)*:
Align duct with 14, threaded 10-32 holes on filter inlet panel.
Secure with 14, #10-32 x ¾” machine screws (G-4) being careful not to damage gasket. Do not use screws
longer than ¾” as damage to the filter unit may occur.
The inlet duct must have at least 8” of straight duct before any bends are made to facilitate access to the
filter turn down bolts.
All ductwork must be kept clean and be properly sealed.
ELECTRICAL CONNECTION
After mounting the electrical box, remove the electrical knock-out that is not being used.
A separate electrical disconnect may be required by local electrical code.
Connect the proper size wires to terminals (L1) (L2)* (L3)* N (neutral)** and G (ground), check local electrical
codes for wire sizing.
LOW VOLTAGE CONTROL CONNECTION
Reference the table below to find the correct schematic. Follow the directions included on the schematic for
connections and wiring details.
Model
Refer to Page #
1200SC-120-1AL
1-2
1200SC-220-1AL
1-3
1200SC-220-3AL
1-4
1200SC-440-3AL
1-5
*(L2) and (L3) only exist in 3 Phase models.
**Neutral exists only in 1 Phase and custom 3 Phase models
*Refer to page 1-1 for a
Disconnect power to the unit beforeservicing.
Check the model data plate on the front of the electrical box, which indicates all the
electrical requirements for this unit.
Do not connect power to the unit until the High Energy Grid wires have been
checked for proper connection. (Refer to page11)
All electrical connections must be done by a certified electrician,
following the directions listed in thismanual.
fig-A
21.500
23.500
2.000
10-32ThreadedInsert
14Total
10-32ThreadedInsert
14Total
5.833
5.833
5.833
7.000
7.000
7.000
1.250
6.500
6.335
14.000
16.670
15.500
6.335
6.500
1.250
2.250
1.250
22.000
Inlet - Intake Side Duct Connection
Outlet - Exhaust Side Duct Connection

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
larger figure if needed
#10057
1
4
©HealthWay
2015 #1005
715 ©HealthWay 2015

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
1
7
©HealthWay
2015
System Operation
TO TURN ON THE UNIT
Turn on the Main Switch located on the top of the unit, it should illuminate, indicating the power is on,
the Green LED should also come on. (fig-B,C)
TO TURN OFF THE UNIT
To turn off the unit, simply turn off the main switch located on the top of the unit.
While operating the 1200SC system with an HVAC system, both
systems must work in unison being on and off at the same time.
The filter unit will not turn on if the Safety Switch Screw, located on the
Filter Access Door is not fullysecured.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
1
7
©HealthWay
2015
fig-B
fig-C

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
©HealthWay
2015
#1005
7
1
9
©HealthWay
2015
Maintenance
PREFILTER REPLACEMENT
Only one Filter Access Door needs to be removed to replace the Prefilter.
Remove Safety Switch Screw located on the bottom of the Filter Access Door towards the Inlet Side of the
housing then the flange nuts. The Safety Switch Screw disengages the Filter Access Door’s safety disconnect
switch thereby disabling the power switch. (fig-1)
Filter Access Door removal may require a firm pulling effort.
Loosen the top and bottom Scissor Locking Mechanism located near the motor plate on the Inlet Sideof
the filter unit. Make sure the Scissor Locking Mechanism is fully opened.(fig-2)
Disconnect the High Voltage Lead from the High Energy Grid. (fig-3)
Simply slide the Prefilter out of the filter channel.
To install a new Prefilter, slide the Prefilter back in the channel.
Pay attention to the Flow Direction Arrow
on the Prefilter, the arrow should point
towards the Supply/Outlet Side of the unit.
(fig-4)
Tighten the top and bottom
Scissor Locking Mechanism.
Reconnect the High Voltage Lead.
Return the Filter Access Door.
When returning the Filter Access Door,
the Safety Switch Screw must be placed in
the appropriate location to complete the
electrical path through the Safety Switch.
When replacing filters use only HealthWay certified filters. HealthWay filters are
designed for high voltage operation. Use of non-HealthWay filters canbe hazardous
to personnel and equipment voiding the warranty.
Always turn off the electrical switches and circuit breakers/disconnects
before maintenance on the unit. Wait a minimum of 30 seconds before
touching the unit or electricalbox.
fig-2
fig-1

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
20
©HealthWay
2015
#1005
7
2
1
©HealthWay
2015
Maintenance Maintenance
V- BANK MAIN FILTER REPLACEMENT
Only one Filter Access Door needs to be removed to replace the filters.
Remove Safety Switch Screw located on the bottom of the Filter
Access Door towards the Inlet Side of the housing then the flange nuts. The Safety Switch Screw disengages
the Filter Access Door’s safety
disconnect switch thereby disabling the power switch. (fig-1)
Filter Access Door removal may require a firm pulling effort.
Loosen the top and bottom Scissor Locking Mechanism located near the motor plate on the Inlet Side of the
filter unit. Make sure the Scissor Locking Mechanism is fully opened. (fig-2)
Disconnect the High Voltage Lead from the High Energy Grid. (fig-3)
Using a firm pull, remove the V-Bank Main Filter and High Energy Grid
Assembly out of the filter access opening.
Inspect and clean the inside of the unit. Refer to page 21 for proper instructions.
Remove the Prefilter, replace if necessary. (fig-4)
Separate the High Energy Grid from the V-Bank Main Filter by removing
the two screws in the center of the V-Bank Main Filter. (fig-5)
Replace the V-Bank Main Filter. Pay attention to the Flow Direction Arrow on the Prefilter, the arrow
should point towards the Supply/Outlet Side
of the unit. (fig-6)
Secure the V-Bank Main Filter to
the High Energy Grid by using the
two center screws in the center of
the
V- Bank Main Filter.
Return the Prefilter.
Slide the V-Bank Main Filter and
HighEnergyGridAssemblybackintotheunit.
Tighten the top and bottom
Scissor Locking Mechanism.
Reconnect the High Voltage Lead. (fig-7)
Return the Filter Access Door. (fig-8)
When returning the Filter Access Door,
the Safety Switch Screw must be placed
in the appropriate location to complete the
electrical path through the Safety Switch.
CLEANING THE UNIT
Depending on contamination level, this procedure should be conducted about once a year or during each
filter change or if an electrical problem occurs.
Remove the V-Bank Main Filter and High Energy Grid Assembly
Refer to page 20 for proper instructions.
To clean the wires, use a fiber free swab, either dry or moistened with distilled or deionized water, clean
along the length of each wire, spring clip, and ceramic insulator.
Clean the inner surfaces of the High Energy Grid material using a lint cloth moistened with distilled or
deionized water.
Clean the High Energy Grid surface by vacuuming between the wires using a small vacuum attachment or by
using a lint free cloth, either dry or moistened with distilled or deionized water. Take care to avoid leaving
large fibers snagged on the wires, control grid, or other components of the High Energy Grid.
Make sure that any contaminant that falls to the bottom of the filter unit is removed.
In extreme cases, it may be necessary to remove the wires from the springs attached at each end to the power
distribution bars, thus allowing complete access to the inside of the High Energy Grid assembly for cleaning
as previously described. It is recommended that the manufacturer be contacted for detailed instructions
should this step appear necessary.
Vacuum the bottom of the filter seal plate section and of the filter unit to remove any particles dislodged during
cleaning. Reinstall the High EnergyGrid, V-Bank Main Filter and Filter Access Door as previouslyinstructed.
Do not use alcohol or cleaners that may damage acrylics, plastics or aluminum.
fig-5
fig-6

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
22
©HealthWay
2015
#1005
7
2
3
©HealthWay
2015
Maintenance Troubleshooting
PARTS LIST
HealthWay recommends that the following spare parts be available on-site at all times.
For additional troubleshooting assistance refer to the DFS Troubleshooting Guide on the following page or
contact HealthWay; Monday-Friday, 8am-5pm EST:
Phone No:
315-298-2904
Order all parts by contacting:
1-800-843-3860
Phone No:
315-298-2904
Fax No:
315-298-6992
1-800-843-3860
Email:
info@healthway.com
Fax No:
315-298-6992
Email:
info@healthway.com
Problem Description
RecommendedAction
Green LED (HVPS-1) is OFF - Fan is running
1. Check the High Energy Grid for broken, loose
or disconnected wires and debris. If the
problem persists then refer to the
DFS Troubleshooting Guide.
2. If the problem persists, then call for assistance.
Fan motor not running
1. Check whether the unit is running on the
required supply voltage and confirm the status
of breakers and fuses.
2. If problem persists, then check for disconnected
wires or connectors inside the unit and its
Electrical Box including all low voltage
control connections.
3. If the problem persists, then call for assistance.
Green LED (HVPS-1) is OFF - Fan is not running
1. Check whether the unit is running on therequired
supply voltage and confirm the status of
breakers and fuses.
2. If the problem persists, check the Safety Switch
Screw (2) located on each access door.
Make sure that both Safety Switch Screws are in
the correct position and tightened.
3. If the problem persists, then call for assistance
Description
Part Number
Prefilter
FT-101-2
V-Bank Main Filter
1200-VB-92
120v Power Supply
2010
Interlock Switch
2034
Standoff
7047
Power Relay, 120vac Coil
EC-037
120-24 Step-down Transformer
EC-040
380-120 Step-down Transformer
EC-041
TMK-355, 230-440 3-ph motor-355-4-34
EC-049
Relay
EC-058
VFD
EC-080
Signal Isolator
EC-081
24 VOC Green LED
ES-004
Poly Tubing
HA-072
Magnehelic Pressure Gauge 0-2
HA-096
High Energy Grid
TC-019
1/2” S.S. Spring
NZ-004
High Energy Grid Wires
NZ-023
Multiplier
NZ-025

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
24
©HealthWay
2015
#1005
7
2
5
©HealthWay
2015
Troubleshooting Troubleshooting
DFS TROUBLESHOOTING GUIDE
Refer to pages 19 and 20 to view figures
Symptom: The unit has been turned on but the High Voltage Power Supply Indicator Light (HVPS1) is OFF
Probable cause #1: Short in High Energy Grid (foreign debris, loose wires, loose electricalconnection)
Confirmation:
Step 1: Disconnect power to unit
Step 2: Remove a Filter Access Door by first removing the Safety Switch Screw located on the bottom of
the Filter Access Door towards the Inlet Side of the housing then the flange nuts. (fig-1)
Step 3: Disconnect the High Voltage Lead from the High Energy Grid. (fig-3)
Step 4: Safely secure the male end of the High Voltage Lead between the Prefilter and the High Energy
Grid as to ensure that the High Voltage Lead cannot contact the blower wheel.
Step 5: The following steps should be done with extreme care and the person(s) performing this
test should ensure that unauthorized personnel cannot come in contact with dangerous
moving parts and high voltages.
Defeat Safety Interlock: Replace the Safety Switch Screw (without the Filter Access Door) and
tighten (by hand) until the Safety Switch Screw is tightened.
Step 6: Return power to the unit and put the unit into run mode. Observe the status of the High Voltage
Power Supply Indicator Light (HVPS1). If the light is now functioning the problem is in the High
Energy Grid.
Disconnect power to the unit, remove the Safety Switch Screw and follow these steps:
(A) Loosen the top and bottom Scissor Locking Mechanism located near the motor plate on the
Inlet Side of the filter unit. Make sure the Scissor Locking Mechanism is fully opened.(fig-2)
(B) Ensure the High Voltage Lead is disconnected from the High Energy Grid. (fig-3)
(C) Using a firm pull, remove the V-Bank Main Filter and High Energy Grid Assembly out of the
filter access opening.
(D) Separate the High Energy Grid from the V-Bank Main Filter by removing the two screws in
the center of the V-Bank Main Filter. (fig-5)
(E) Inspect the High Energy Grid and its wires, they should be free from debris and evenly
tensioned. Loose wires can cause arcing or cause the protection circuit to trip.
(F) Inspect the “V” sections of the V-Bank Main Filter and ensure that it is free of metal debris,
excess dirt or hair etc…
(G) Secure the V-Bank Main Filter to the High Energy Grid by using the two center screws in the
center of the V-Bank Main Filter.
(H) Stand the V-Bank Main Filter and High Energy Grid Assembly up (as it sits in the unit) and
inspect the gasket on the seal side of the Assembly. Replace the gasket if it is damaged
(I) Slide the V-Bank Main Filter and High Energy Grid Assemblyback into theunit.
(J) Tighten the top and bottom Scissor Locking Mechanism.
(K) RepeatStep5fromaboveandplacetheunitin runmodetoconfirm theproblemhas beenresolved.
Conclusion: If the High Voltage Power Supply Indicator Light stays off this indicates a faulty Voltage
Multiplier. Disconnect power from the unit and replace the Voltage Multiplier. Repeat Step 5
from above and place the unit in run mode to confirm the problem has been resolved.

1200 SC Self Contained DFS Air Cleaning
System
1200 SC Self Contained DFS Air Cleaning
System
#1005
7
24
©HealthWay
2015
#1005
7
2
5
©HealthWay
2015
DFS TROUBLESHOOTING
GUIDE
Probable Cause #2: Faulty Voltage Multiplier / Faulty High Voltage Power Supply (HVPS)
Confirmation:
Step 1: Disconnect power to unit
Step 2: Open the Electrical Box attached to the unit with (2) gray flexible electrical conduits
Step 3: Locate the Voltage Multiplier in the bottom right hand corner of the Electrical Box. The Voltage
Multiplier is a gray, rectangular device with red and black wires at one end and a single red wire
at the opposite end. (fig-9)
Step 4: Disconnect the red wire of the Voltage Multiplier from the “J3” terminal of the High
Voltage Power Supply (HVPS). Stay clear of this terminal while testing and Do Not attempt
to
re-connect the terminal with power applied to the unit.
Step 5: Re-connect power to the unit
Step 6: Place the unit in “run” mode and observe the status of the High Voltage Power Supply
Indicator Light (HVPS1)
Conclusion: If the High Voltage Power Supply Indicator Light stays off with no Voltage Multiplier
attached there is a fault in the High Voltage Power Supply. Disconnect power from the unit
and replace the High Voltage Power Supply.
If the High Voltage Power Supply
indicator light is on with no Voltage Multiplier attached the fault
is either in the High Energy Grid or in the Voltage Multiplier.
Variable Frequency Drive
High Voltage PowerSupply
VoltageMultiplier
fig-9

1200 SC Self Contained DFS Air Cleaning System
Inlet/Outlet Connection
2.000
5.833
21.500
5.833
5.833
10-32
Threaded Insert
14 Total
7.000
23.500
7.000
7.000
10-32
Threaded Insert
14 Total
6.335
1.250
6.500
16.670 14.000 15.500
6.335 6.500
2.250 1.250
1.250
22.000
Inlet - Intake Side Duct Connection Outlet - Exhaust Side Duct Connection
HealthWay Products, Inc
1200SC Installation Dimensions
Inlet/Outlet Connection
This manual suits for next models
4
Table of contents
Other HealthWay Air Cleaner manuals