HeatLink SSPLR106T Installation and operating instructions

SSP Series
SS Manifold Pump Panel
Installation, Operation, and Maintenance Manual
®
Heat Link
L6SSPxx000x
MECHANICAL
ROOM IN A BOX
™
SSPLR106T
SSPSS106B
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION115 VOLTS ONLY
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION115 VOLTS ONLY

®
Heat Link
www.heatlink.com
2
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Table Of Contents
Warnings........................................................................................................................3
Tools Needed ...............................................................................................................3
Function.........................................................................................................................4
Unpacking.....................................................................................................................5
Panel Components ....................................................................................................6-7
Specications...............................................................................................................8
Panel Component Specications .........................................................................9-14
Manifold Balancing....................................................................................................11
Recessed Housing Mounting.................................................................................15-16
Surface Mount Housing Mounting......................................................................17
Piping Hookup ............................................................................................................18
Fill and Purge ...............................................................................................................19
Panel Wiring .................................................................................................................20
Panel Control Sequence & Wiring.........................................................................21
Troubleshooting .........................................................................................................22
Maintenance ................................................................................................................22
Schematics
Mechanical ...............................................................................................................23-24
Electrical Detail .......................................................................................................25
Electrical Rough-in ................................................................................................26

®
Heat Link
3
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Warnings
The zone control panel is for indoor use only and must be installed by a qualied installer/service technician. This product
must be installed and operated in strict accordance with the terms set out in this manual and in accordance with the relevant
requirements of the Local Authority Having Jurisdiction. Failure to comply will result in a void of warranty, and may also result
in property damage, serious injury, or death.
Servicing
Prior to commencing installation of this panel it is necessary to read and understand all sections of this manual. The
symbols below are used throughout this document to ensure proper operation of the panel, and your safety. Please pay
attention to these symbols.
Disclaimer
HeatLink Group Inc. shall not be responsible for errors in its brochures or printed materials. HeatLink Group Inc. reserves
the right to alter its products at any time without notice, provided that alterations to products already on order shall not
require material changes in specications previously agreed upon HeatLink Group Inc. and the Purchaser. All trademarks
in this material are property of the respective companies. HeatLink and the HeatLink logotype are trademarks of HeatLink
Group Inc. All rights reserved.
Tools For Installation
• Level
• Screwdriver or power drill
• Flat head bit
• Phillips head bit # 2
• O-ring Lubricant (#79951 or #79952)
In order to avoid injury or death, switch o the power to the panel prior to
inspecting or making connections to the terminal strip.
Warning
Possible Hazard
Warning
Live Power
Warning
Hot Pipes
Warning
Treated Water

®
Heat Link
www.heatlink.com
4
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Function
This panel can provide distribution, and zoning for a wide variety of hydronic heating applications.
The eectiveness of the system is dependant on the system being designed and installed correctly. Proper consideration
of factors such as BTU loads, outdoor design temperature, indoor design temperature, room set-point temperature(s),
dierential uid temperatures, head loss, ow rates, and transfer capacities of the heat emitters is critical.
Once these factors have been considered and the system requirements determined, these can then be evaluated and
compared to the zone control panel capabilities (refer to pages 6-14).
Note: This panel does not regulate or monitor the operating safety limit temperatures of the uid leaving the heat source.

®
Heat Link
5
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Unpacking
Step 1 Examine carton for any damage that may have occurred during shipping. If damage is visible notify your courier and
supplier immediately.
Step 2 Open the carton by removing the strapping.
Step 3 Remove the cardboard spacers from the carton, then remove the panel from the carton. Lift the panel by the
enclosure, not the cover.
Step 4 Remove the cover from the panel by unlocking the coin/screwdriver locks. Lift the top of the cover upwards to
disengage the tongues from the slots at the bottom of the panel and then pull the cover o.
Step 5 Verify the following items:
• (2) 1" rubber washers (2 spares)
This panel is heavy; 2-3 person lift required.

®
Heat Link
www.heatlink.com
6
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Panel Components
# Component
Part Number
SSPSx1xxx SSPLx1xxx SSPLx2xxx
1Primary Pump PUMP1558 PUMP2699 PUMP2699
2Stainless Steel Manifold 76100 series 76100 series 76200 series
Flow Meter Valve Insert (supply)
(0-1.5 US gpm lock nut) 76916 76916 n/a
Balancing Valve Insert (supply) n/a n/a 76912
Zone Valve Insert (return) 76911 76911 76911
3Thermometer – – –
4SS Manifold Port Caps 77100 77100 77100
5Hose Bib 76930 76930 76930
6Isolation Ball Valve – – –
7120V(ac) terminal strip – – –
824V(ac) 40VA Transformer –––
9StatLink®Base Module 40226 40226 40226
10 Enclosure Recessed or
Surface Mount
Recessed or
Surface Mount
Recessed or
Surface Mount
Cover (not shown) – – –
11 Key Lock (installed on cover) 71902 71902 71902
Accessory Pack – – –
1" Washer NTRWSH1 NTRWSH1 NTRWSH1
Optional Installed Items
12 SSAPB - Installed Accessory Pressure Bypass
for SS Manifolds 76936 76936 76936
13 SSASLEM - Installed StatLink®4 Zone
Expansion Module 40234 40234 40234
14 SSASLEMHD - Installed StatLink®2 Zone
Heavy Duty Expansion Module 40242 40242 40242
Sold Separately
15 PEX to Manifold Connectors
1⁄2" 77105 77105 77105
5⁄8" 77119 77119 77119
3⁄4" 77122 77122 77122

®
Heat Link
7
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
11
15
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION 115VOLTS ONLY
106030C
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION 115VOLTS ONLY
1
1
3
3
2
2
5
5
5
5
7
7
8
8
9
9
10
10
6
6
6
6
4
4
4
4
SSPLR106T
SSPSS106B
14
13
12

®
Heat Link
www.heatlink.com
8
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Specications
SSPSx104x SSPSx106x SSPSx108x SSPSx110x SSPSx112x
Nominal panel output 45,000 Btu/h 62,000 Btu/h 78,000 Btu/h 90,000 Btu/h
Nominal flow 4.5 US gpm @
20°F ∆T
6.2 US gpm @
20°F ∆T
7.8 US gpm @
20°F ∆T
9.0 US gpm @
20°F ∆T
Nominal pressure drop outside of
panel
based on 250' loops of 1⁄2" tubing
Max ambient temperature 120°F
Max water temperature 180°F
Circulator Ferrous, Grundfos UPS15-58
Power supply:
pre-wired on system controller
110 V(ac);
max. current 3A
Auxiliary terminal Yes
Piping 1" piping
Piping connections 1" FNPT
Enclosure Galvanized steel, visible parts are satin coated steel.
Recessed Surface Mount
4-6 loop 8-10 loop 12 loop 4-6 loop 8-10 loop 12 loop
Enclosure Width 34-1⁄2"
(876 mm)
42-1⁄2"
(1080 mm)
46-1⁄2"
(1180 mm)
34-1⁄2"
(876 mm)
42-1⁄2"
(1080 mm)
46-1⁄2"
(1181 mm)
Enclosure Height 28-1⁄2"
(724 mm)
28-1⁄2"
(724 mm)
28-1⁄2"
(724 mm)
28-1⁄2"
(724 mm)
28-1⁄2"
(724 mm)
28-1⁄2"
(724 mm)
Enclosure Depth 5-7⁄8"
(149 mm)
5-7⁄8"
(149 mm)
5-7⁄8"
(149 mm)
5-7⁄8"
(149 mm)
5-7⁄8"
(149 mm)
5-7⁄8"
(149 mm)
Door Width 36"
(915 mm)
44"
(1118 mm)
48"
(1219 mm)
32-7⁄8"
(835 mm)
40-7⁄8"
(1038 mm)
44-7⁄8"
(1140 mm)
Door Height 30"
(762 mm)
30"
(762 mm)
30"
(762 mm)
26.9"
(683 mm)
26.9"
(683 mm)
26.9"
(683 mm)
Weight

®
Heat Link
9
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Panel Component Specications
Thermometer
The pipe mounted thermometer reads the supply uid
temperature.
Specications:
• Temperature range of 32-210°F (0-100°C).
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
StatLink® 6 Zone Base Module (40226)
The StatLink® base module connects room thermostats to their corresponding actuators. Each zone has an LED which
indicates if it is calling for heat. A timer thermostat (46643 or 46673) can send a setback signal to other thermostats via
terminal Clock 1 or 2. As soon as there is a heat demand from one zone, a relay with two dry contacts is switched on (Pump,
Boiler …). Add more zones by plugging in the #40234 or #40242 module.
Specications:
• Actuator Contact: Triac
• Pump Contact: DPST NO relay (8 amps)
• Other Contact: DPST NO relay (8 amps)
• Timer Channels: 2
CR

®
Heat Link
www.heatlink.com
10
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Type UPS 15-58 CIL2
115 V ~
60 Hz
8 μF
P/N: 97948357
PC: 1131HLK
IP42
TF 95
Max. 1.0MPa
Max. water temp. 203°F
FR
IMPEDANCE PROTECTED
FOR INDOOR USE ONLY
|1/1(A) P1 (W)
0.51
0.59
0.64
56
67
73
UPS15-58CIL2 Pump Curve
0
2
4
6
8
10
12
14
16
18
20
0 2 4 6 8 10 12 14 16
Flow (gpm)
Head (feet)
1st Speed 2nd Speed 3rd Speed
Circulator
The circulators moves the heated uid through the hydronic system when there is a call for heat from the thermostat. Factory
set to 3rd speed.
Specications:
• The following pump curves apply.
UPS26-99FC Pump Curve
0
5
10
15
20
25
30
35
0 5 10 15 20 25 30 35
Flow (gpm)
Head (feet)
1st Speed 2nd Speed 3rd Speed
Type UPS 26-99 FC
115 V 1 PH
60 Hz
20 uF
P/N: 52722512 P1
PC: 0939
US
IMPEDANCE
PROTECTED
FOR INDOOR USE ONLY
Class F
|1/1(A) P1 (w)
1.30
1.50
1.80
150
179
197
CUS
99K4
UL
LISTED
MAX. FlUID
TEMP. 230˚F 99K4LISTED UL

®
Heat Link
11
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Supply Manifold
Secondary Balancing (Fine Tuning).
CCW = open CW = closeCCW = open CW = close
Return Manifold
Primary Balancing.
Black cap for manual shut-off only.
Use drip cap ➀for balancing.
Balancing Method 1:
Valve setting or ow characteristic
known (pre-balancing)
1. Fully open supply valve (ow
meter) [factory open].
2. Close return valve completely
[factory open].
3. Open return valve the number of
turns as per heatloss calculation or
friction head graph.
4. After all valves are set, eld
adjustments may be necessary.
Notes:
• Hose bib thread is an ASME thread.➁
• After ll procedure: the drip cap ➀should be
placed back on to the hose bib ➁.
• Pipe to manifold connectors sold separately.
Balancing Method 2:
Only ow rate known
1. Ensure all supply valves are open
[factory open].
2. Ensure all return valves are open
(remove black cap).
3. Use the return valve to adjust ow
to desired setting (ow meter).
4. Valves adjusted rst may need to
be re-adjusted once all other loops
have been set.
Remove locking cap to adjust flow meter.
Please note:
Do not use tools to adjust flow
meters. (Damage to the flow meter
will occur, and will not be covered
under warranty).
Balancing Notes:
Return : Use for primary balancing purposes and manual shut-o. Use drip cap
to adjust the return manifold.➀➁
Caution: Opening the return valve too far will result in removing
the valve stem.
Supply : Use for secondary balancing / ne tuning the ow rate. Remove
locking cap to adjust the ow meter by hand, do not use tools.
Flow meter balancing adjustment range:
0-1.5 US gpm or 0-5 L/min.
Stainless Steel Manifold
Specications:
• Material: Stainless Steel EN 1.4301 (X5CrNi18-10) which is equivalent to SAE 304 (V2A)
• Maximum Trunk Flow Rate: 18 US gpm (4.1 m3/h)
• Maximum Circuit Flow Rate: 76100 Series - 1.5 US gpm (0.34 m3/h)
76200 Series - 2.5 US gpm (0.57 m3/h)
2
1
1
➀
CCW = open CW = close
76200
Series
76100
Series

®
Heat Link
www.heatlink.com
12
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
1
(3.78)
0.1
(0.38)
3
(11.36)
0.5
(1.89)
0.01
(0.04)
0.05
(0.19)
Mass Flow Rate in US gpm (L/min)
1(3)
5(15)
0.1 (0.3)
0.5 (1.5)
0.01
0.05 (0.15)
Pressure Drop in ft H2O (kPa)
10 (30)
30 (90)
(0.03)
1
0.50.25
Stainless Steel Manifold # of turns from closed position
0.75
1.5
2
3.5
Working loop ow ranges from 0.1 to 1.25 US gpm (0.38 to 4.7 L/m) for oor heating and from 1.5 to 2.5 US gpm (5.7 to 9.5
L/m) for snowmelting. Pressure drop must be closely checked when water ow is beyond the upper working range.
76100 Series (Flow Meter) Friction Head Graph

®
Heat Link
13
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Stainless Steel Manifold # of turns from closed position
1
(3.78)
0.1
(0.38)
5
(18.9)
0.5
(1.89)
0.01
(0.04)
0.05
(0.19)
Mass Flow Rate in US gpm (L/min)
1(3)
5(15)
0.1 (0.3)
0.5 (1.5)
0.01
0.05 (0.15)
Pressure Drop in ft H2O (kPa)
10 (30)
30 (90)
(0.03)
10.50.25 0.75
1.5
2
2.5
3
3.5
76200 Series (High Flow) Friction Head Graph

®
Heat Link
www.heatlink.com
14
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
SSAPB - Optional Installed Accessory Pressure Bypass (#76937)
Adjustable pressure bypass valve kit for 76100 and 76200 series
stainless steel manifolds. This valve prevents a steep rise of the
pump head and maintains ow at a stable rate. Also ensures only
required amount of circulating water is used for hydronic systems.
Specications:
• Adjustment Range: 0.05 - 0.5 bar (1.67 - 16.73 ft H2O)
106030C
SSASLEM - Optional Installed StatLink®4 Zone Expansion
Module (40234)
The StatLink® 4 zone expansion module connects to the
StatLink® 6 zone base module, allowing 4 more room
thermostats to connect to their corresponding actuators.
SSASLEMHD - Optional Installed StatLink®2 Zone Heavy
Duty Expansion Module (40243)
The StatLink® 2 zone heavy duty expansion module (40242)
connects to the StatLink® 6 zone base module, allowing 2 more
room thermostats to connect to up to 12 actuators each.

®
Heat Link
15
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Step 2 If electrical wiring will be coming from the top, remove the appropriate knockouts.
Recessed Enclosure Mounting
Step 1 Use a screwdriver or similar thin tool through the hole to bend the mounting tabs out 90 degrees
from the enclosure.
42-1⁄2"
7⁄8" O.D.
7⁄8" O.D.
2"
14-13⁄16"
27-5⁄8"
40-1⁄2"
2"
12-3⁄16"
22-5⁄16"
32-7⁄16"
34-1⁄2"
3-3⁄4"
3-3⁄4"
Step 3 Build a 2x6 supporting frame where the panel is to be mounted.
The panel should be mounted at least 12" above the oor.

®
Heat Link
www.heatlink.com
16
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Step 4 Lift and place the panel onto the supporting frame.
This panel is heavy; 2-3 person lift required.
Step 5 Complete the supporting frame by adding a top plate.
Be sure to drill corresponding holes in the top plate if any
knockouts were removed.
Step 6 Secure the panel in place by putting screws into each of the
mounting tabs.
Note: Panel contents are not shown in the diagrams.
Recessed Housing Mounting continued

®
Heat Link
17
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION115 VOLTSONLY
Surface Mount Housing Mounting
Prior to mounting the panel, ensure the wall is capable
of supporting the weight of the panel.
Step 1 Determine the locations and distance between
the wall studs. With a level at a minimum
height of 4' from the oor draw a straight line
on the wall and mark the stud locations.
If the housing cannot be secured directly to
the studs, or suitable backing boards, plywood
may need to be installed behind the housing to
properly secure it in place.
Step 3 Screw three of the supplied mounting screws
into the wall studs (or backing plywood)
leaving ¼" of screw out from the wall.
Step 4 Lift and place the housing onto the mounting
screws.
Step 5 Screw the remaining mounting screws into the
holes at the bottom of the housing and tighten
the top screws.
Note: Skirting by others.
16"
7-1⁄8"
4-5⁄8"
3-1⁄8"
16"
16"
4-7⁄8"
6-1⁄8"
3"
3-1⁄8"
16"
1⁄4"
Wall Stud
Top Feed
Bottom Feed
4' min
from oor

®
Heat Link
www.heatlink.com
18
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Piping Hookup
Step 1 Before making any connections, identify the
required connections to and from the panel.
Step 2 Connect mains piping using 1" MNPT ttings.
Note: Use precautions when soldering or
applying heat within 16" of the panel.
120
140
160
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GROUND
NEUTRAL
CAUTION115 VOLTSONLY
Primary
Return
Primary
Supply
Floor Return
Floor Supply
SSPLR106T shown
Step 3 Connect all tubing to manifold adapters. (77100 series connecters sold separately)
1. Lubricate the inside of the manifold port with silicone o-ring lubricant (#79952 sold separately).
2. Cut the PEX tubing at a 90˚ angle.
3. Place the Nut and Split Ring Ferrule onto the PEX tubing.
Note: For the 3⁄4" connecter, the Split RIng Ferrule must be placed inside the Nut before putting them onto the
PEX tubing.
Method A
5. Push the Brass Insert onto the PEX tubing as far as it will go.
6. Push the PEX tubing with Brass Insert as far as it will go into the manifold module. Ensure the o-ring is clean and
take care not to pinch it.
Method B
5. Push Brass Insert as far as it will go into the manifold. Ensure the o-ring is clean and take care not to pinch it.
6. Push PEX tubing onto the Brass Insert as far as it will go.
7. Use a wrench to tighten the nut.
90° Brass Insert with
O-ring
Split Ring Ferrule
Nut

®
Heat Link
19
www.heatlink.com SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
SSP Panel
T
SSP Panel
T
Fill And Purge
The following steps are recommended in order to ll the panel
with water and purge entrained air once piping is completed,
and before activation of the panel.
Note: Additional purging steps may be required for the rest of
the hydronic system.
Note: Isolation and drain valves are not included with the
panel, but are necessary to properly ll and purge the
panel, and to isolate the panel for service.
Step 1 Ensure the panel is not powered.
Step 2 Fully close valves A, B, and C. Fully close all supply
Eand all return Fmanifold valves.
Fully open valve D.
Step 3 Attach a purge hose (not included) to D. Pressurize
the main supply line. Open valve B.
Step 4 Open the rst return manifold valve F. Open the rst
supply manifold valve E. Watch the hose in the pail
until you observe a steady stream of water (no air or
spitting). Close the rst return manifold valve F.
Step 5 Repeat Step 4 for each loop until all loops are lled
with water, and air is purged from pipes.
Step 6 Purging is complete when there is no more air and/or
spitting. Close valve Dthen valve B.
Step 7 Remove hose from drain valve D.
Step 8 Check for leaks at connections. If any leaks are found
use a back-up wrench and carefully tighten until leak
stops. Do not overtighten.
The discharged system uid from the ll and purge
process is not for consumption or washing.
E
F
F
E
A
A
B
B
C
C
D
D
SSTL Series bottom feed
SSTL Series top feed

®
Heat Link
www.heatlink.com
20
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Panel Wiring
Note: Terminal headers are removable to make wiring connections easier.
• 24V low voltage power may be supplied to the thermostat. Wiring of thermostat
should be done by qualied electrician and should meet local codes and
jurisdictions. Wiring to the terminal strip requires 18 gauge 4 wire.
Thermostat Wiring
2-Wire Thermostat
(battery only or non-electric)
3-Wire Thermostat
(HeatLink thermostats)
4-Wire Thermostat
(with dry contact signal)
W
R
C
1
2
1
1
2
2
24 V
Signal W
R
C
1
2
1
1
2
2
24 V
24 V
Signal W
R
C
1
2
1
1
2
2
Signal
24 V
24 V
Jumper to
Dry Contact
Other Terminals
Auxiliary Contacts The auxiliary contact set is dry, meaning no supply of power is present at the terminal. The
maximum allowable load is 8A. The auxiliary dry contact located on the terminal is to switch
another device (ie. the heat source) when there is a call for heat from any zone.
Actuator Contacts Connect up to 4 actuators per zone.
Auxiliary
Contacts
This manual suits for next models
1
Table of contents
Popular Water Pump manuals by other brands

Oase
Oase ProMax MudDrain 7000 operating instructions

Annovi Reverberi
Annovi Reverberi AR 245 LFP instruction manual

KMT
KMT STREAMLINE SL-IV PLUS Operation and service manual

Wayne
Wayne WSF50 quick start guide

Franklin Electric
Franklin Electric Little Giant 555702 HRK-360S instruction sheet

Xylem
Xylem e-1532 Series instruction manual