Measurements 105 x 80 x 30 mm
Voltage 10-28 VDC
Current Standby approx 16 mA, 500 mA peak
Inputs 4 inputs NO or NC, alternative temperature
Outputs 2 Closing rely outputs 1A 24V AC/DC
Temperature-
measurement Internally or optional temperature sensors on input
1-4. measurement area +50 till –35 grader
Ambient
temperature -20 to +55 centigrade's, non condensing
Technical data
Radiolink GSM-A2 Quick-start
1
INTRODUCTION
Thank you for choosing the GSM-A2.
For using the product to its full poten-
tial, please note that this is a quick-
start guide. A complete manual are in
preparation and will be ready Q3 2011
Function
GSM-A2 is compact universal GSM
communicator that can alert on vari-
ous events by sending SMS as power
fail, triggering of inputs, temperature,
or other sensors.
Alarm types
GSM-A2 is designed to send SMS to
subscribers in the mobile phone net-
work. Some mobile operators have
SMS to mail service.
SIM card
GSM-A2 is designed for operation in
the GSM network and a valid SIM card
must be inserted in the unit.
It works in the 2G network and SIM-
card with only 3G can not be used.
We recommend subscription but pre-
paid can be used.
Presets:
In GSM-A2 it is possible to select
different presets that covers the most
common applications and lets you
start-up the unit quick and simple.
With one SMS command you select
one of 3 applications described on
page 4-6.
Programming
With the PC program GSM Toolkit you
have power tool to program your
GSM-A2 and optimize it for your appli-
cation.
Distance programming and trouble
shooting with SMS saves a lot of time
and travel
Application for ANDROID and internet
programming are in preparation and
coming in Q3 2011.
Package:
GSM-A2 unit
GSM-antenna
Quick-start instruction
Options:
Antennas
Antenna cables
Temperature sensor
Magnetic contacts
PIR sensors
GSM Toolkit compact disc with cables
ANDROID APP
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500
Selhella 13
220 Hafnarfjörður
Sími: 554 0500
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is

Radiolink GSM-A2 Quick-start
2
STEP 1
Install a valid 2G GSM SIM-card in the unit and do the following:
Note the SIM-cards subscriber number.
The SIM-card must be activated by the operator
If pre-paid make sure that it is filled up with credits
The PIN code must be deactivated.
Insert the SIM card gently with the contact surface facing the front and
the cut of corner down to the left.
1A
FUSE
Input 1
Input 2
Input 3
Input 4
COM
Supply voltage
+10-28 VDC
System ground
REL-1
REL-1
REL-2
REL-2
1
2
3
4
COM
-
+
STEP 2
Mount GSM-A2 in a place protected from water, dust etc.
Wire according to the above diagram.
As soon as the power is connected to GSM-A2, the status LED will flash
rapidly in 30-40 seconds. When is makes 1-5 slow flashes it has logged on
to the GSM network. The slow flashes indicates the signal strength of the
GSM network on a scale from 1-5 units. Must be at least 1.
Wiring diagram
REL–1 LED
REL-2 LED
GSM LED
Radiolink GSM-A2 Quick-start
7
SMS command Action Answer Comment
A2!! Activation of factory
presets. A2 Initiering OK Sending cell
phone number
will be first alarm
number
Status? Status question Return SMS with
status answer System check
Tele?? Query programmed
telephone numbers Return SMS with
all programmed
numbers Number check
Tele!*2,
+46701234567
Add telephone num-
ber 2 with country
code Return SMS with
all programmed
numbers Same procedure
for remaining
numbers. (max 8)
Tele!*2, Erase telephone
number 2 Return SMS with
all programmed
numbers Overwrites old
number
Aon Alarm on Return SMS with
status Alarm on
Aoff Alarm off Return SMS with
status Alarm off
Temp? Query actual tem-
perature Return SMS with
temperature Actual value
Volt? Query actual supply
voltage Return SMS with
actual voltage Actual value
On*1* Activate rely REL-1 Return SMS with
status Only if REl-1 is
free and not
programmed for
another function)
On*2* Activate rely REL-2 Return SMS with
status Se above
Off*1* Avaktivera REL-1 Return SMS with
status Se above
.
Off*2* Avaktivera REL-2 Return SMS with
status Se above
Heaton Activates heating Return SMS with
status Heating on
Heatoff Deactivates heating Return SMS with
status Heating off
Termon Activates
maintenance heat Return SMS with
status Mainte-
nance heat on
Termoff Deactivates
maintenance heat Return SMS with
status Mainte-
nance heat off
Commands shortform & SMS questions to GSM-A2
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500

Radiolink GSM-A2 Quick-start
6
REL-1
REL-1
REL-2
REL-2
1
2
3
4
COM
-
+
1A
FUSE
Supply voltage
Matningsspänning
+10-28 VDC
System jord/system ground
A2!!02
GSM LED
REL-1 LED
REL-2 LED
Pre programming SMS Command A2!! 02
Application
GSM-A2 is used for control-
ling the temperature and
sending SMS alert to pre
programmed (maximum 8)
telephone numbers in a list.
Wired like this a closing of
inputs will generate an SMS
to all number in the list.
Input 3 is used for control-
ling the embedded thermo-
stat.
Input 4 is used for the tem-
perature sensor
GSM-A2 sends low tempera-
ture warning and are con-
trolling the heat.
Preset values:
Freeze warning: +3˚5 min
Away heating: +10˚5 h
Stay heating: +20˚5 h
Rel-2 are free to be con-
trolled by SMS command.
LED Indicators
GSM LED flashes short indi-
cates standby/ready mode.
Steady on indicates activity.
After activity GSM flashes
with 1-5 flashes indicating
the GSM network signal
strength. Returns to short
flash after while.
Tempera-
turgivare
Slinga 1
Slinga 2
Slinga 3
Slinga 4
COM
Termostat
knapp
Power rely
AC/DC
Max 30 V 1A
REL-1 contact are used for heat control
REL-1 LED indicates heat control status
Heatoff = LED out
Heaton = LED steady on.
Termon = LED short flashing, thermostat is on, REL-1 is off (heat off)
Termon = LED long flashing, thermostat is on, REL-1 is on (heat on)
Radiolink GSM-A2 Quick-start
3
STEP 3
Quick-start in initiated by sending a command to the unit with SMS.
The unit load the selected pre-set and the sending number is added to
telephone list as first alarm number.
Send text: A2!!XX (XX = preset number)
Answer: A2 initiering ok
You have now completed the quick-start of your new GSM-A2
Check unit status, information of power, alarm and more.
Send text: Status?
GSM-A2 responds with status message
Add a second number for SMS alert, max 8 number.
Send text: TELE!*2+4670123456
Activate any of inputs 1-4 and check that you receive an SMS.
Inputs/outputs
1-4 is external inputs
5 is the internal temperature sensor
The function of the in and outputs can be altered by SMS
Trouble shooting
No SMS is coming in at alarm condition.
Try to send VER? GSM-A2 should respond with the version number.
Check that correct number is programmed
Send text: TELE?? GSM-A2 shall respond with programmed numbers.
Bad GSM network? Is the led flashing OK?
Check that SIM PIN code is deactivated.
Check the wiring
Repeat step 3
Change text message.
After preset you can change the texts 1-4 by sending a new text with
SMS as following:
Text!*01,High level Pump 12, building 4
When the answer: Text**01,High level Pump 12, building 4 is the
new text entered and GSM-A2 is ready to use.
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500

Radiolink GSM-A2 Quick-start
4
REL-1
REL-1
REL-2
REL-2
1
2
3
4
COM
-
+
1A
FUSE
Input 1
Input 2
Input 3
Input 4
COM
Supply voltage
+10-28 VDC
System ground
A2!!
Pre programming SMS Command A2!!
Application
GSM-A2 are used for send-
ing SMS to pre programmed
maximum 8 telephone num-
bers in a list.
Wired like this a grounding
of one of the inputs will
generate an SMS to all num-
ber in the list.
Rel-1 & Rel-2 are available
to be controlled by SMS
command.
Commands
On*1*
Off*1*
On*2*
Off*2*
LED Indicators
GSM LED flashes short indi-
cates standby/ready mode.
Steady on indicates activity.
After activity GSM flashes
with 1-5 flashes indicating
the GSM network signal
strength. Returns to short
flash after while.
LED REL-1 & REL-2 acti-
vated on indicates relay on.
REL–1 LED
REL-2 LED
GSM LED
Radiolink GSM-A2 Quick-start
5
REL-1
REL-1
REL-2
REL-2
1 30 sec
2
3
4
COM
-
+
1A
FUSE
Supply voltage
+10-28 VDC
System ground
A2!!01
GSM LED
REL-1 LED
REL-2 LED
Pre programming SMS Command A2!!01
Application
GSM-A2 is used for sending
SMS to pre programmed
(maximum 8) telephone
numbers in a list.
Wired like this an opening of
one of the inputs will gener-
ate an SMS to all number in
the list.
Input 4 is used for set the
alarm on/off with key switch
or code keyboard.
Closed input = alarm off
Open input = alarm on
To the other inputs
switches, magnetic contacts
or PIR with normally closed
contact can be connected.
Rel-2 are free to be con-
trolled by SMS command.
LED Indicators
GSM LED flashes short indi-
cates standby/ready mode.
Steady on indicates activity.
After activity GSM flashes
with 1-5 flashes indicating
the GSM network signal
strength. Returns to short
flash after while.
LED REL-1 on = siren active
LED REL-2 indicates alarm
status. Flashes at alarm on.
(LED only, relay 2 is free for
remote control)
+ DC -
Sirén
Input 1
Input 2
Input 3
Input 4
COM
Inp 4
Alarm
On/Off
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500
E-mail: info@bodtaekni.is
Hemsíða www.bodtaekni.is
Selhella 13
220 Hafnarfjörður
Sími: 554 0500