Hitachi Relion SAM600 Quick start guide

Relion SAM600
Switchgear control unit SAM600-IO
Version 2.2
Commissioning manual


Document ID: 1MRK511447-UEN
Issued: June 2023
Revision: E
Product version: 2.2
© 2017 - 2023 Hitachi Energy. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written permission from
Hitachi Energy, and the contents thereof must not be imparted to a third party, nor used for any
unauthorized purpose.
The software and hardware described in this document is furnished under a license and may be used
or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit
(https://www.openssl.org/). This product includes cryptographic software written/developed by: Eric
Young ([email protected]) and Tim Hudson ([email protected]).
Trademarks
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Energy
company. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest Hitachi Energy representative.

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that each
intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and/or product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken
to exclude or mitigate such risks.
This document has been carefully checked by Hitachi Energy, but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall Hitachi Energy be responsible
or liable for any loss or damage resulting from the use of this manual or the application of the
equipment.

Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits
(Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by Hitachi
Energy in accordance with the product standard EN 60255-26 for the EMC directive, and with the
product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.

Table of contents
Section 1 Introduction....................................................................................................5
1.1 This manual...........................................................................................................................5
1.2 Intended audience.................................................................................................................5
1.3 Product documentation......................................................................................................... 5
1.3.1 Product documentation set..................................................................................................5
1.3.2 Document revision history...................................................................................................6
1.3.3 Related documents............................................................................................................. 7
1.4 Document symbols and conventions.....................................................................................7
1.4.1 Symbols...............................................................................................................................7
1.4.2 Document conventions........................................................................................................8
1.5 IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping......................................................8
Section 2 Safety information....................................................................................... 11
2.1 Symbols on the product.......................................................................................................11
2.2 Warnings..............................................................................................................................11
2.3 Caution signs.......................................................................................................................12
Section 3 Available functions......................................................................................13
3.1 Control and monitoring functions.........................................................................................13
3.2 Communication................................................................................................................... 14
3.3 Basic IED functions............................................................................................................. 15
Section 4 User interface...............................................................................................17
4.1 Introduction..........................................................................................................................17
4.2 PCM600 tool........................................................................................................................17
4.2.1 Connectivity packages...................................................................................................... 17
4.3 SAM600-IO LHMI service kit...............................................................................................17
4.3.1 Display...............................................................................................................................18
4.3.2 Keypad.............................................................................................................................. 18
4.3.3 LED indication................................................................................................................... 20
4.3.4 Front communication.........................................................................................................21
4.3.5 Connecting the LHMI service kit to SAM600-IO................................................................22
4.3.6 Removing the LHMI service kit from SAM600–IO.............................................................22
Section 5 Starting up....................................................................................................23
5.1 Factory and site acceptance testing....................................................................................23
5.2 Commissioning checklist.....................................................................................................23
5.3 Checking the power supply................................................................................................. 23
5.4 Energizing the IED.............................................................................................................. 24
5.4.1 Checking the IED operation.............................................................................................. 24
5.4.2 IED start-up sequence ......................................................................................................24
5.5 Setting up communication between PCM600 and the IED................................................. 25
5.5.1 When IED has blank front panel........................................................................................25
1MRK511447-UEN Rev. E Table of contents
Switchgear control unit SAM600-IO 1
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

5.5.2 When IED has front port with RJ-45..................................................................................25
5.6 Writing an application configuration to the IED................................................................... 30
5.7 Using the RTXP test switch ................................................................................................30
5.8 Checking the binary input/output circuits.............................................................................30
5.8.1 Binary input circuits........................................................................................................... 30
5.9 Checking optical connections..............................................................................................30
Section 6 Configuring the IED and changing settings..............................................33
6.1 Overview............................................................................................................................. 33
6.2 Supervision of input/output modules................................................................................... 33
Section 7 Establishing connection and verifying the IEC 61850 communication..35
7.1 Overview............................................................................................................................. 35
7.2 Setting the station communication...................................................................................... 35
7.3 Verifying the communication .............................................................................................. 35
Section 8 Testing IED operation..................................................................................37
8.1 Preparing for test.................................................................................................................37
8.1.1 Requirements....................................................................................................................37
8.1.2 Preparing the IED to verify settings...................................................................................38
8.2 Activating the test mode......................................................................................................38
8.3 Preparing the connection to the test equipment..................................................................39
8.4 Connecting the test equipment to the IED...........................................................................39
8.5 Releasing the function to be tested.....................................................................................40
8.6 Forcing of binary input/output signals for testing.................................................................41
8.6.1 Forcing concept.................................................................................................................41
8.6.2 How to enable forcing........................................................................................................41
8.6.2.1 Enable forcing using TESTMODE function block.........................................................41
8.6.3 How to change binary input/output signals using forcing.................................................. 41
8.6.3.1 Forcing by using PCM600............................................................................................41
8.6.4 How to undo forcing changes and return the IED to normal operation............................. 43
8.6.4.1 Undo forcing by using TESTMODE component...........................................................43
8.6.4.2 Undo forcing by using PCM600................................................................................... 43
Section 9 Testing functionality by secondary injection............................................45
9.1 Testing disturbance report...................................................................................................45
9.1.1 Introduction........................................................................................................................45
9.1.2 Disturbance report settings............................................................................................... 45
9.1.3 Disturbance recorder (DR)................................................................................................ 45
9.1.4 Event recorder (ER) and Event list (EL)............................................................................46
9.2 Identifying the function to test in the technical reference manual .......................................46
9.3 Control.................................................................................................................................46
9.3.1 Apparatus control APC......................................................................................................46
9.4 Logic....................................................................................................................................46
9.4.1 Tripping logic, common 3-phase output SMPPTRC .........................................................46
9.4.1.1 Three-phase operating mode.......................................................................................46
9.4.1.2 1ph/3ph operating mode ............................................................................................. 47
Table of contents 1MRK511447-UEN Rev. E
2Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

9.4.1.3 1ph/2ph/3ph operating mode ...................................................................................... 47
9.4.1.4 Circuit breaker lockout................................................................................................. 48
9.4.1.5 Completing the test...................................................................................................... 49
9.5 Monitoring............................................................................................................................49
9.5.1 Gas medium supervision SSIMG...................................................................................... 49
9.5.1.1 Testing the gas medium supervision for pressure alarm .............................................49
9.5.1.2 Testing the gas medium supervision for temperature alarm ....................................... 49
9.5.1.3 Completing the test...................................................................................................... 49
9.5.2 Liquid medium supervision SSIML....................................................................................49
9.5.2.1 Testing the liquid medium supervision for level alarm and level lockout conditions.....49
9.5.2.2 Testing the gas medium supervision for temperature alarm and temperature
lockout conditions.........................................................................................................50
9.5.2.3 Completing the test...................................................................................................... 50
9.5.3 Breaker monitoring SSCBR...............................................................................................50
9.5.3.1 Verifying the settings.................................................................................................... 50
9.5.3.2 Completing the test...................................................................................................... 52
9.5.4 Limit counter L4UFCNT.....................................................................................................52
9.5.4.1 Completing the test...................................................................................................... 52
9.6 Basic IED functions............................................................................................................. 52
9.6.1 Parameter setting group handling SETGRPS...................................................................52
9.6.1.1 Verifying the settings.................................................................................................... 52
9.6.1.2 Completing the test...................................................................................................... 53
9.7 Exit test mode......................................................................................................................53
Section 10 Commissioning and maintenance of the fault clearing system..............55
10.1 Commissioning tests........................................................................................................... 55
10.2 Periodic maintenance tests................................................................................................. 55
10.2.1 Visual inspection............................................................................................................... 55
10.2.2 Maintenance tests............................................................................................................. 55
10.2.2.1 Preparation...................................................................................................................56
10.2.2.2 Recording.....................................................................................................................56
10.2.2.3 Secondary injection......................................................................................................56
10.2.2.4 Alarm test..................................................................................................................... 56
10.2.2.5 Self supervision check................................................................................................. 56
10.2.2.6 Trip circuit check.......................................................................................................... 57
10.2.2.7 Restoring......................................................................................................................57
Section 11 Troubleshooting...........................................................................................59
11.1 Checking the self supervision signals................................................................................. 59
11.1.1 Checking the self supervision function..............................................................................59
11.1.1.1 Determine the cause of an internal failure................................................................... 59
11.1.2 Self supervision data.........................................................................................................59
11.1.2.1 General IED status.......................................................................................................59
11.2 Fault tracing.........................................................................................................................60
11.2.1 Internal fault indications.....................................................................................................60
11.2.2 Using LHMI service kit-connected PC...............................................................................61
11.2.3 Diagnosing the IED status via the LHMI hint menu...........................................................62
1MRK511447-UEN Rev. E Table of contents
Switchgear control unit SAM600-IO 3
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

11.2.4 Hardware re-configuration.................................................................................................63
11.3 Repair instruction................................................................................................................ 64
11.4 Repair support.....................................................................................................................64
11.5 Maintenance........................................................................................................................64
Section 12 Glossary....................................................................................................... 65
Table of contents 1MRK511447-UEN Rev. E
4Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v21
The commissioning manual contains instructions on how to commission the IED. The manual can
also be used by system engineers and maintenance personnel for assistance during the testing
phase. The manual provides procedures for the checking of external circuitry and energizing the IED,
parameter setting and configuration as well as verifying settings by secondary injection. The manual
describes the process of testing an IED in a substation which is not in service. The chapters are
organized in the chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11
This manual addresses the personnel responsible for commissioning, maintenance and taking the
IED in and out of normal service.
The commissioning personnel must have a basic knowledge of handling electronic equipment. The
commissioning and maintenance personnel must be well experienced in using protection equipment,
test equipment, protection functions and the configured functional logics in the IED.
1.3 Product documentation
1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16
IEC07000220-4-en.vsd
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication
protocol manual
Cyber security
deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN-US
Figure 1: The intended use of manuals throughout the product lifecycle
1MRK511447-UEN Rev. E Section 1
Introduction
Switchgear control unit SAM600-IO 5
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

The engineering manual contains instructions on how to engineer the IEDs using the various tools
available within the PCM600 software. The manual provides instructions on how to set up a PCM600
project and insert IEDs to the project structure. The manual also recommends a sequence for the
engineering of protection and control functions, as well as communication engineering for IEC 61850.
The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the chronological
order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The manual can
also be used by system engineers and maintenance personnel for assistance during the testing
phase. The manual provides procedures for the checking of external circuitry and energizing the IED,
parameter setting and configuration as well as verifying settings by secondary injection. The manual
describes the process of testing an IED in a substation which is not in service. The chapters are
organized in the chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of the
IED. The manual also describes how to identify disturbances and how to view calculated and
measured power grid data to determine the cause of a fault. The manual provides information related
to the need of LHMI service kit to monitor diagnostics and make configuration changes.
The application manual contains application descriptions and setting guidelines sorted per function.
The manual can be used to find out when and for what purpose a typical protection function can be
used. The manual can also provide assistance for calculating settings.
The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols supported by the IED.
The manual concentrates on the vendor-specific implementations.
The cyber security deployment guideline describes the process for handling cyber security when
communicating with the IED. Certification, Authorization with role based access control, and product
engineering for cyber security related events are described and sorted by function. The guideline can
be used as a technical reference during the engineering phase, installation and commissioning
phase, and during normal service.
1.3.2 Document revision history GUID-7099E1DB-1CD6-4037-A418-92AB57FA9462 v6
Document
revision
Date Product revision History
A 2017-12 2.2.1 First release for product version 2.2
B 2019-05 2.2.1 PTP enhancements and corrections
2.2.2 Document not released
2.2.3 Document not released
2.2.4 Document not released
Table continues on next page
Section 1 1MRK511447-UEN Rev. E
Introduction
6Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Document
revision
Date Product revision History
C 2021-06 2.2.5 Functions ALGOS, IEC61850SIM, RSTP added. Support for
COMTRADE2013 added.
D Document not released
E 2023-06 2.2.6 SNMP support, IEC 61850 Ed2.1, new variants of single mode
SFP added. Functions C1RADR, GOOSEACRCV,
SNMPSERVERCONF, and SNMPUSERCONF added.
Functions INTERRSIG, SETGRPS, TERMINALID, VSGAPC,
SMPPTRC, BTIGAPC, IB16, ITBGAPC, SSCBR, SPGAPC,
SP16GAPC, IEC61850-8-1, LD0LLN0, AP_1 - AP_6,
AP_FRONT, and updated. Ordering section updated.
1.3.3 Related documents GUID-67D1F667-746E-4B71-875A-4CBEAB6EC5E1 v1
Documents related to SAM600–IO Document numbers
Application manual 1MRK 511 445-UEN
Commissioning manual 1MRK 511 447-UEN
Product guide 1MRK 511 448-BEN
Technical manual 1MRK 511 446-UEN
Type test certificate 1MRK 511 448-TEN
Operation manual 1MRK 500 131-UEN
Engineering manual 1MRK 511 442-UEN
Installation manual 1MRK 514 030-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK 511 440-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK 511 441-UEN
Accessories guide 1MRK 514 012-BEN
Cyber security deployment guideline 1MRK 511 443-UEN
1.4 Document symbols and conventions
1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13
The electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
The warning icon indicates the presence of a hazard which could result in personal injury.
Class 1 Laser product. Take adequate measures to protect the eyes and do not view
directly with optical instruments.
The caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could result in
corruption of software or damage to equipment or property.
1MRK511447-UEN Rev. E Section 1
Introduction
Switchgear control unit SAM600-IO 7
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a
certain function.
Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. It is important that the user fully complies with all
warning and cautionary notices.
1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v9
• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal name may
be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be connected to
another function block in the application configuration to achieve a valid application
configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned then
the dimension is in millimeters.
1.5 IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping
GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v10
Function block names are used in ACT and PST to identify functions. Respective function block
names of Edition 1, Edition 2, and Edition 2.1 logical nodes are shown in the table below.
Table 1: IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping
Function block name Edition 1 logical nodes Edition 2 and Edition 2.1 logical
nodes
- - ALGOS
AGSAL AGSAL
SECLLN0
AGSAL
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BTIGAPC B16IFCVI BTIGAPC
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
INDCALH INDCALH INDCALH
ITBGAPC IB16FCVB ITBGAPC
L4UFCNT L4UFCNT L4UFCNT
LD0LLN0 LLN0 -
LPHD LPHD
MVGAPC MVGGIO MVGAPC
Table continues on next page
Section 1 1MRK511447-UEN Rev. E
Introduction
8Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Function block name Edition 1 logical nodes Edition 2 and Edition 2.1 logical
nodes
QCBAY QCBAY BAY/LLN0
RCHLCCH RCHLCCH RCHLCCH
SCHLCCH SCHLCCH SCHLCCH
SCSWI SCSWI SCSWI
SLGAPC SLGGIO SLGAPC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
TEIGAPC TEIGGIO TEIGAPC
TMAGAPC TMAGGIO TMAGAPC
VSGAPC VSGGIO VSGAPC
WRNCALH WRNCALH WRNCALH
1MRK511447-UEN Rev. E Section 1
Introduction
Switchgear control unit SAM600-IO 9
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

10

Section 2 Safety information
2.1 Symbols on the product GUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4
All warnings must be observed.
Read the entire manual before doing installation or any maintenance work on the product.
Class 1 Laser product. Take adequate measures to protect your eyes and do not view
directly with optical instruments.
2.2 Warnings IP1504-1 v2
Observe the warnings during all types of work related to the product.
GUID-C9B6638A-57E7-4E05-9A33-A60E359C54AF v1
Only electrically skilled persons with the proper authorization and knowledge of any
safety hazards are allowed to carry out the electrical installation.
M2366-2 v2
National and local electrical safety regulations must always be followed. Working in a
high voltage environment requires serious approach to avoid human injuries and damage
to equipment.
M2362-2 v1
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
M2364-2 v1
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
M2370-2 v1
Never connect or disconnect a wire and/or a connector to or from a IED during normal
operation. Hazardous voltages and currents are present that may be lethal. Operation
may be disrupted and IED and measuring circuitry may be damaged.
GUID-BEDD698E-356C-4CF9-9DAE-64DB3CEADEAD v1
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has
been disconnected.
M2369-2 v3
Always connect the IED to protective earth, regardless of the operating conditions. This
also applies to special occasions such as bench testing, demonstrations and off-site
configuration. This is class 1 equipment that shall be earthed.
1MRK511447-UEN Rev. E Section 2
Safety information
Switchgear control unit SAM600-IO 11
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

M2372-2 v1
Never remove any screw from a powered IED or from a IED connected to powered
circuitry. Potentially lethal voltages and currents are present.
SEMOD168311-3 v1
Take adequate measures to protect the eyes. Never look into the laser beam.
GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2
The IED with accessories should be mounted in a cubicle in a restricted access area
within a power station, substation or industrial or retail environment.
2.3 Caution signs IP1503-1 v1
GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v3
Whenever changes are made in the IED, measures should be taken to avoid inadvertent
tripping.
GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1
The IED contains components which are sensitive to electrostatic discharge. ESD
precautions shall always be observed prior to touching components.
M2695-2 v2
Always transport PCBs (modules) using certified conductive bags.
M2696-2 v1
Do not connect live wires to the IED. Internal circuitry may be damaged
M2697-2 v2
Always use a conductive wrist strap connected to protective earth when replacing
modules. Electrostatic discharge (ESD) may damage the module and IED circuitry.
M2698-2 v2
Take care to avoid electrical shock during installation and commissioning.
M2693-2 v2
Changing the active setting group will inevitably change the IED's operation. Be careful
and check regulations before making the change.
Section 2 1MRK511447-UEN Rev. E
Safety information
12 Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

Section 3 Available functions
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v2
The following tables list all the functions available in the IED. Those functions that are not
exposed to the user or do not need to be configured are not described in this manual.
Table 2: Example of quantities
2 = number of basic instances
0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)
C30 =1/2 CB application. For the pre-configured variants
3.1 Control and monitoring functions GUID-AE265B38-C04D-4415-BAA4-EFB62EAFAFF1 v2
IEC 61850 or
function name ANSI Function description Switchgear control
unit
SAM600-IO
Control
QCBAY Bay control 2
SXSWI Circuit switch 18
SCSWI Switch controller 30
LOCREM Handling of local/remote switch positions 1
SXCBR Circuit breaker 3B
6-H56
POS_EVAL Evaluation of position indication 30
SLGAPC Logic rotating switch for function selection and LHMI presentation 15
VSGAPC Selector mini switch 30
DPGAPC Generic communication function for Double Point indication 16
SPC8GAPC Single point generic control function, 8 signals 5
Logic
SMPPTRC 94 Tripping logic 12
SMAGAPC General start matrix block 12
TMAGAPC Trip matrix logic 12
ALMCALH Logic for group alarm 5
WRNCALH Logic for group warning 5
INDCALH Logic for group indication 5
AND, GATE, INV,
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Basic configurable logic blocks (see Table 3) 40-160
FXDSIGN Fixed signal function block 1
B16I Boolean to integer conversion, 16 bit 18
BTIGAPC Boolean to integer conversion with logical node representation, 16 bit 16
IB16 Integer to Boolean 16 conversion 24
ITBGAPC Integer to boolean conversion with logical node representation, 16 bit 16
TEIGAPC Elapsed time integrator with limit transgression and overflow supervision 54
Table continues on next page
1MRK511447-UEN Rev. E Section 3
Available functions
Switchgear control unit SAM600-IO 13
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved

IEC 61850 or
function name ANSI Function description Switchgear control
unit
SAM600-IO
INTCOMP Comparator for integer inputs 30
REALCOMP Comparator for real inputs 30
Monitoring
DRPRDRE,
B1RBDR-
B22RBDR
Disturbance report 1
SPGAPC Generic communication function for single point indication, 1 input 128
SP16GAPC Generic communication function for single point indication, 16 inputs 16
MVGAPC Generic communication function for measured values 60
RANGE_XP Measured value expander block 66
SSIMG 63 Insulation supervision for gas medium 21
SSIML 71 Insulation supervision for liquid medium 3
SSCBR Circuit breaker condition monitoring 27
L4UFCNT Event counter with limit supervision 30
Table 3: Total number of instances for basic configurable logic blocks
Basic configurable logic block Total number of instances
AND 160
GATE 40
INV 80
LLD 40
OR 160
PULSETIMER 40
RSMEMORY 60
SRMEMORY 60
TIMERSET 40
XOR 40
3.2 Communication GUID-C1FB7B84-2F43-4F15-9264-F33832C8036B v2
IEC 61850 or function
name ANSI Function description Switchgear control
unit
SAM600-IO
Station communication
IEC 61850-8-1 IEC 61850 1
IEC 61850SIM IEC 61850 simulation mode 1
GOOSEBINRCV GOOSE binary receive 16
GOOSEDPRCV GOOSE function block to receive a double point value 64
GOOSEINTRCV GOOSE function block to receive an integer value 32
GOOSEMVRCV GOOSE function block to receive a measurand value 60
GOOSESPRCV GOOSE function block to receive a single point value 60
ALGOS Supervision of GOOSE subscription 100
AGSAL Generic security application component 1
LD0LLN0 IEC 61850 LD0 LLN0 1
Table continues on next page
Section 3 1MRK511447-UEN Rev. E
Available functions
14 Switchgear control unit SAM600-IO
Commissioning manual
© 2017 - 2023 Hitachi Energy. All rights reserved
This manual suits for next models
1
Table of contents
Other Hitachi Industrial Equipment manuals

Hitachi
Hitachi KPI-252-2002E4E User manual

Hitachi
Hitachi TRF-NP63S1 User manual

Hitachi
Hitachi TRF-NP63S1 User manual

Hitachi
Hitachi ABB RELION REB500 User manual

Hitachi
Hitachi SuperDrive 75 Series User manual

Hitachi
Hitachi P1 Installation guide

Hitachi
Hitachi Relion REL670 User manual

Hitachi
Hitachi Relion 670 Series User manual

Hitachi
Hitachi MICRO-EHV+ OBV-AIG User manual

Hitachi
Hitachi HC Series User manual