Page. 6 / 10
Doc. no. : HTML-S_Kor_2016, Rev. 0
Issued date : 2016. 11
HITROL Co., Ltd
company to minimize noise of the signal line by mitigating EMI, etc.
7.4 For the functional test, the detailed wiring shall be as follows:
7.4.1 Remove the sensor lines from the terminal block, and connect the decade box.
7.4.2 Connect the power to terminals AC1−AC2 of the terminal block.
8. Checkpoints for Functional Test
8.1 Check the testing instruments.
8.2 Check the calibration period of the testing instruments.
8.2.1 Simulator (Decade box)
Check that it satisfies the resistance range, and that its calibration period has not
expired.
8.2.2 Multimeter
Check that its calibration period has not expired.
8.3 Check the L/E.
Check the resistance values of the sensors and the heater.
8.3.1 Resistance range of the sensors and the heater
1) RA: 1,000 Ω = 0℃, ∴ △3.76 Ω/℃ (e.g., 20℃ = 1,075.2 Ω ± 1%)
2) RR: 1,000 Ω = 0℃, ∴ △3.76 Ω/℃ (e.g., 20℃ = 1,075.2 Ω ± 1%)
3) Heater: 220 Ω ± 1%
8.3.2 Check the output current of the heater.
Apply power to the L/T (warm-up: 20 minutes), and measure the output current at the
power supply terminal for checking that it is 75 mA ± 1%. (Use of variable resistor, R2) If
the current is beyond the range, adjust it by using R2.
8.4 Check voltage at the TP (test point) of the power board.
8.4.1 Act. At the RTD of 1,000 Ω, check if the voltage between TP1 and TP3 is 0.5 V.
If the voltage is beyond the range, adjust it by using R35.
8.4.2 Ref. At the RTD of 1,000 Ω, check if the voltage between TP2 and TP3 is 0.5 V.
If the voltage is beyond the range, adjust it by using R23.
8.4.3 Act. At the RTD of 1,500 Ω, check if the voltage between TP1 and TP3 is 4.5 V.
If the voltage is beyond the range, adjust it by using R34.
8.4.4 Ref. At the RTD of 1,500 Ω, check if the voltage between TP2 and TP3 is 4.5 V.
If the voltage is beyond the range, adjust it by using R22.