HMS Intesis INMBSFGL016O000 User manual

Fujitsu VRF Air Conditioning
USER MANUAL
Issue date: 02/2020 r1.0 ENGLISH

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 25
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any
inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability
for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product
development. The information in this document shall therefore not be construed as a commitment on the part of
HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment
to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only
intended to help improve understanding of the functionality and handling of the product. In view of the wide range
of possible applications of the product, and because of the many variables and requirements associated with any
particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on
the data, examples or illustrations included in this document nor for any damages incurred during installation of the
product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the
product is used correctly in their specific application and that the application meets all performance and safety
requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will
under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of
undocumented features or functional side effects found outside the documented scope of the product. The effects
caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility
issues and stability issues.

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
3 / 25
Gateway for the integration of Fujitsu VRF systems into Modbus
(RTU and TCP) systems.
ORDER CODE
LEGACY ORDER CODE
INMBSFGL016O000
FJ-AC-MBS-16

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4 / 25
INDEX
1. Description............................................................................................................................................................ 5
1.1. Introduction..................................................................................................................................................... 5
1.2. Functionality.................................................................................................................................................... 6
1.3. Capacity of Intesis .......................................................................................................................................... 7
2. Modbus interface.................................................................................................................................................. 8
2.1. Functions supported ....................................................................................................................................... 8
2.2. Modbus RTU................................................................................................................................................... 8
2.3. Modbus TCP................................................................................................................................................... 8
2.4. Modbus Address Map..................................................................................................................................... 9
3. Connections........................................................................................................................................................ 12
3.1. Power device ................................................................................................................................................ 13
3.2. Connect to Fujitsu VRF installation............................................................................................................... 13
3.3. Connection to Modbus.................................................................................................................................. 13
3.3.1. Modbus TCP............................................................................................................................................ 13
3.3.2. Modbus RTU............................................................................................................................................ 13
3.4. Connection to PC (Configuration tool).......................................................................................................... 13
4. Set-up process and troubleshooting................................................................................................................... 14
4.1. Pre-requisites................................................................................................................................................ 14
4.2. Intesis MAPS. Configuration & monitoring tool for Intesis Modbus series ................................................... 14
4.2.1. Introduction.............................................................................................................................................. 14
4.2.2. Connection............................................................................................................................................... 14
4.2.3. Configuration tab ..................................................................................................................................... 15
4.2.4. Modbus Slave configuration .................................................................................................................... 15
4.2.5. Fujitsu configuration................................................................................................................................. 16
4.2.6. Signals..................................................................................................................................................... 17
4.2.7. Sending the configuration to Intesis ........................................................................................................ 18
4.2.8. Diagnostic................................................................................................................................................ 18
4.2.9. Set-up procedure..................................................................................................................................... 19
5. Electrical & Mechanical Features....................................................................................................................... 21
6. Dimensions......................................................................................................................................................... 22
7. AC Unit Types compatibility................................................................................................................................ 23
8. Error codes for Indoor and Outdoor Units.......................................................................................................... 24

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 25
1. Description
1.1. Introduction
This document describes the integration of Fujitsu VRF air conditioning systems into Modbus compatible devices
and systems using gateway the Intesis Modbus Server to Fujitsu VRF communication gateway.
The aim of this integration is to monitor and control Fujitsu air conditioning systems, remotely, from a Control Center
using any commercial SCADA or monitoring software that includes a Modbus Master driver (RTU and/or TCP). To
do it so, Intesis performs as a Modbus Server, allowing poll and write requests from any Modbus master device.
Intesis makes available the Fujitsu air conditioning system indoor units’ datapoints through independent Modbus
registers.
Up to 16 indoor units supported, depending on product version.
This document assumes that the user is familiar with Modbus and Fujitsu technologies and their technical terms.
Integration of Fujitsu’s compatible systems into Modbus systems

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
6 / 25
1.2. Functionality
IntesisTM continuously monitors Fujitsu VRF network for all configured signals and keeps the updated status of all
of them in its memory, ready to be served when requested from the Modbus master.
Commands toward the indoor units are permitted.
Each indoor unit is offered as a set of MBS objects.
Element
Object supported
Outdoor Unit
•Status
Indoor Unit
•Status
•Command
•Communication
status
General signals
(all units)
•Command

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
7 / 25
1.3. Capacity of Intesis
Element
Max.
Notes
Number of indoor units
16 *
Number of indoor units that can be controlled through Intesis
* There are different models of Intesis MBS –Fujitsu VRF each one with different capacity. The table above shows
the capacity for the top model (with maximum capacity).
Their order codes are:
▪INMBSFGL016O000: Model supporting up to 16 indoor units

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
8 / 25
2. Modbus interface
In this section, a common description for all Intesis Modbus series gateways is given, from the point of view of
Modbus system which is called from now on internal system. Connection with the Fujitsu VRF system is also called
from now on external system.
2.1. Functions supported
This part is common for Modbus RTU and TCP.
Modbus functions 03 and 04 (Read Holding Registers and Read Input Registers) can be used to read Modbus
registers.
Modbus functions 06 and 16 (Single Multiple Holding Registers and Write Multiple Holding Registers) can be used
to write Modbus registers.
Configuration of poll records is possible between Modbus addresses 0 and 20000. Addresses that are not defined
in section 2.2 (Modbus map of the device) are read-only and will always report 0.
Modbus error codes are supported, they will be sent whenever a non-valid Modbus address is queried.
All registers are 16-bit signed integer, in standard Modbus Big Endian (MSB/LSB) format.
Intesis supports Modbus RTU and Modbus TCP and both interfaces can be used simultaneously.
2.2. Modbus RTU
Both EIA485 and EIA232 physical layers are supported. Only the lines RX, TX and GND of the EIA232 connector
are used (TX and RX for EIA485).
Baud rate can be selected between 1200, 2400, 4800, 9600, 19200, 38400, 56700 and 115200. Parity (none, even
or odd) and stop bits (1 or 2) can be selected as well.
Modbus slave number must be configured and the physical connection (RS232 or RS485) can also be selected
2.3. Modbus TCP
TCP port to use (default is 502) and keep alive period must be configured.
IP settings of Intesis (DHCP status, own IP, net mask and default gateway) must be configured as well.

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
9 / 25
2.4. Modbus Address Map
Modbus address from the formula is expressed in link layer format. This is, first register address is 0.
Modbus Address
First Address is 0
Read
/Write
Register/signal name
Possible values
0
R/W
Gateway Energy Saving
0-Disable energy saving
1-Enable energy saving
1
R
Gateway error
0-Normal
1-Error
2
R
Gateway error code
0-No error
1-Comm. error
2-No config. error
3
W
On (all the units)
1-Set all the units On
4
W
Off (all the units)
1-Set all the units Off
5
W
Operation Mode Auto (all the units)
1-Set Auto Mode
6
W
Operation Mode Heat (all the units)
1-Set Heat Mode
7
W
Operation Mode Dry (all the units)
1-Set Dry Mode
8
W
Operation Mode Fan (all the units)
1-Set Fan Mode
9
W
Operation Mode Cool (all the units)
1-Set Cool Mode
10
W
Fan Speed Auto (all the units)
1-Set Fan Speed Auto
11
W
Fan Speed Quiet (all the units)
1-Set Fan Speed Quiet
12
W
Fan Speed Low (all the units)
1-Set Fan Speed Low
13
W
Fan Speed Med-Low (all the units)
1-Set Fan Speed Mid-Low
14
W
Fan Speed Med-High (all the units)
1-Set Fan Speed Mid-High
15
W
Fan Speed High (all the units)
1-Set Fan Speed High
16
W
Temperature Setpoint (x10ºC) (all units)
Cool: 19…30°C; Heat: 17…30°C
Outdoor units
(ID+1)*25+10000+0
Where ID stands for ID field in
Fujitsu VRF configuration in MAPS,
from 0 to 31
R
Capacity save
0-Not set
1-100%
2-90%
3-80%
4-70%
5-60%
6-50%
7-40%
(ID+1)*25+10000+1
R
Forced Off
0-Not forced
1-Forced off

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
10 / 25
Modbus Address
First Address is 0
Read
/Write
Register/signal name
Possible values
(ID+1)*25+10000+2
R
Error
0-No error
1-Error
(ID+1)*25+10000+3
R
Error code
0-No error
Any other value: error
Individual units
(ID+1)*100 +0
Where ID stands for ID field in
Fujitsu VRF configuration in MAPS,
from 0 to 31
R/W
On/Off
0-Off, 1-On
(ID+1)*100 +1
R/W
Operation Mode
0-Auto, 1-Heat, 2-Dry. 3-Fan, 4-Cool
(ID+1)*100 +2
R/W
Fan Speed
0-Auto,1-Quiet,2-Low,3-Med,4-High
0-Auto,1-Quiet,2-Low,3-Med-Low,4-
Med-High,5-High
(ID+1)*100 +3
R/W
Vane Position U-D
1-Pos1…4-Pos4
10-Swing
(ID+1)*100 +4
R/W
Vane Position L-R
1-Pos1…5-Pos5
10-Swing
(ID+1)*100 +5
R/W
Temperature Setpoint (x10ºC/ºF)
Cool:19…30°C; Heat:17…30°C
(ID+1)*100 +6
R
Ambient Temperature (x10ºC/ºF)
0…63,5ºC / 32…147ºF
(ID+1)*100 +7
R
Temperature Limit Valid
0-Invalid,
1-Valid
(ID+1)*100 +8
R/W
Heat Setpoint Up Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +9
R/W
Heat Setpoint Low Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +10
R/W
Cool Setpoint Up Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +11
R/W
Cool Setpoint Low Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +12
R/W
Auto Setpoint Up Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +13
R/W
Auto Setpoint Low Limit (x10)
10…30ºC / 50…86ºF
(ID+1)*100 +14
R
Unit Error
0-No error
1-Error
(ID+1)*100 +15
R
Unit Error code
0-No error
Any other: error
(ID+1)*100 +16
R
Filter Alarm
0-Normal
1-Alarm
(ID+1)*100 +17
W
Filter Alarm Reset
1-Reset
(ID+1)*100 +18
R
Communication Error IU
0-No error
1-Error
(ID+1)*100 +19
R
Emergency
0-OFF
1ON

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 25
Modbus Address
First Address is 0
Read
/Write
Register/signal name
Possible values
(ID+1)*100 +20
R/W
Allow full control from RC
0-Allow
1-Not allow
(ID+1)*100 +21
R/W
Allow On/Off from RC
0-Allow
1-Not allow
(ID+1)*100 +22
R/W
Allow mode from RC
0-Allow
1-Not allow
(ID+1)*100 +23
R/W
Allow Setpoint from RC
0-Allow
1-Not allow
(ID+1)*100 +24
R/W
Thermo off
0-Thermo OFF
1-Thermo ON

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
12 / 25
3. Connections
Find below information regarding the Intesis connections available.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and
SELV rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the
voltage applied is within the range admitted (check table
below). The power supply can be connected to earth but
only through the negative terminal, never through the
positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24
Vac). Do not connect any of the terminals of the AC power
supply to earth, and make sure the same power supply is
not supplying any other device.
Ethernet / Modbus TCP (TCP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the
connector ETH of the gateway. Use an Ethernet CAT5
cable. If communicating through the LAN of the building,
contact the network administrator and make sure traffic on
the port used is allowed through all the LAN path (check the
gateway user manual for more information). Default IP is
192.168.100.246. DHCP is enabled by default.
PortA / Fujitsu VRF
Connect the terminals (X1 X2) of Fujitsu Outdoor Unit to the connectors A3 and A4 of gateway’s PortA.
There is no polarity to be respected.
PortB / Modbus-RTU RS485
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices
connected to the bus, and in each end of the bus it must be a termination resistor of 120 Ω. Bus biasing and
termination resistor for EIA485 can be enabled for PortB by means of a dedicated DIP:
SW1: ON: 120 Ω termination active
OFF: 120 Ω termination inactive (Default setting).
SW2+3:
ON: Polarization active
OFF: Polarization inactive (Default setting).
If the gateway is installed in one bus end, make sure that termination is active.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not an HDD) if required.
Ensure proper space for all connectors when mounted (see 6DIMENSIONS).

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
13 / 25
3.1. Power device
The first step to perform is to power up the device. To do so, a power supply working with any of the voltage range
allowed is needed (check section 5). Once connected the ON led will turn on.
WARNING! In order to avoid earth loops that can damage the gateway, and/or any other equipment connected to
it, we strongly recommend:
•The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a
DC power supply with the positive terminal connected to earth.
•The use of AC power supplies only if they are floating and not powering any other device.
3.2. Connect to Fujitsu VRF installation
Use the PortA connector in the top corner of the Intesis device in order to connect the X1X2 bus to the Intesis.
Remember to follow all safety precautions indicated by Fujitsu.
Connect the Fujitsu X1X2 bus to connectors A3 and A4 of gateway’s PortA. Bus is not sensitive to polarity.
3.3. Connection to Modbus
3.3.1. Modbus TCP
The gateways Ethernet port connection is used for Modbus TCP communication. Connect the communication cable
coming from the network hub or switch to the Ethernet port of Intesis. The cable to be used shall be a straight
Ethernet UTP/FTP CAT5 cable.
TCP port to use (default 502) and keep alive period must be configured.
IP settings of the gateway (DHCP status, own IP, netmask and default gateway) must be configured as well.
3.3.2. Modbus RTU
Connect the communication cable coming from the motbus network to the port marked as Port B of the Intesis.
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices
(without repeaters) connected to the bus, and in each end of the bus it must be a termination resistor of 120 Ω. The
gateway has an internal bus biasing circuit that incorporates the termination resistor.Bus biasing and termination
resistor for EIA485 can be enabled for PortB by means of a dedicated DIP switch.
3.4. Connection to PC (Configuration tool)
This action allows the user to have access to configuration and monitoring of the device (more information can be
found in the configuration tool User Manual). Two methods to connect to the PC can be used:
•Ethernet: Using the Ethernet port of Intesis.
•USB: Using the console port of Intesis, connect a USB cable from the console port to the PC.

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
14 / 25
4. Set-up process and troubleshooting
4.1. Pre-requisites
It is necessary to have the Modbus RTU or TCP master/client device (BMS side device) operative and properly
connected to the corresponding port of the gateway and the Fujitsu VRF installation connected to their
corresponding ports as well.
Connectors, connection cables, PC for the Configuration Tool usage and other auxiliary material, if needed, are not
supplied by Intesis for this standard integration.
Items supplied by HMS Networks for this integration are:
•Intesis gateway.
•Link to download the configuration tool.
•USB Console cable to communicate with Intesis.
•Product documentation.
4.2. Intesis MAPS. Configuration & monitoring tool for Intesis
4.2.1. Introduction
Intesis MAPS is a Windows®compatible software developed specifically to monitor and configure Intesis new
generation gateways.
The installation procedure and main functions are explained in the Intesis MAPS User Manual. This document can
be downloaded from the link indicated in the installation sheet supplied with the Intesis device or in the product
website at www.intesis.com.
In this section, only the specific case of Fujitsu VRF to Modbus systems will be covered.
Please check the Intesis MAPS User Manual for specific information about the different parameters and how to
configure them.
4.2.2. Connection
To configure the Intesis connection parameters press on the Connection button in the menu bar.
Figure 4.2.2.1 MAPS connection

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
15 / 25
4.2.3. Configuration tab
Select the Configuration tab to configure the connection parameters. Three subsets of information are shown in
this window: General (Gateway general parameters), Modbus Slave (Modbus interface configuration) and Fujitsu
(Fujitsu interface parameters).
Figure 4.2.3.1 Intesis MAPS configuration tab
4.2.4. Modbus Slave configuration
Set parameters of Modbus Slave interface of Intesis.
Figure 4.2.4.1 Intesis MAPS Modbus configuration tab
1. Modbus Configuration
1.1.Modbus type selection. Select RTU, TCP or simultaneous RTU and TCP communication.
2. TCP Configuration.
2.1. Modbus TCP Port: Modbus TCP communication port setting. Default port 502.
2.2. Keep Alive. Set the time of inactivity to send a keep Alive message. Default 10 minutes.
3. RTU Configuration.
3.1. RTU bus connection type. Select the RTU connection type serial bus RS485 or 232.
3.2 Baudrate. Set the RTU bus communication speed. Default: 9600 bps.
•Available values: 1200, 2400, 4800, 9600,19200, 38400, 57600, 115200 bps.
3.3 Data Type. Set the Data-bit/parity/stop-bit. Default: 8bit/None/1.

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
16 / 25
•Available selection: 8bit/None/1, 8bit/Even/1, 8bit/Odd/1, 8bit/None/2.
3.4 Slave Number. Set the Modbus Slave address. Default slave address: 1.
•Valid address: 1…255.
4.2.5. Fujitsu configuration
Set parameters for connection with Fujitsu’s installation.
Figure 4.2.5.1 Intesis MAPS Fujitsu configuration tab
In Gateway Configuration section, it is necessary to define the address of the gateway inside the Fujitsu VRF
network. In addition, it is possible to define the temperature scale between Celsius and Fahrenheit.
In Air Units Configuration section, you can do both:
•Add. To do a manual configuration of the Fujitsu VRF system. To do this configuration it is not necessary
to be connected to the VRF system:
Figure 4.2.5.5 Add new air unit
Consider that it is necessary to know the information of the different units:
oIndoor / outdoor: depending type of the AC unit.
oRefrigerant system: as is defined in the VRF network for this certain unit.
oDescription. Descriptive name to easy identification of the unit (for example, ‘living room floor 1
unit’).

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
17 / 25
•Scan. To do an auto configuration of the gateway by retrieving the information from the Fujitsu VRF system.
To do so, it is necessary to be connected to the VRF system:
Figure 4.2.5.6 Scan VRF units in network
It is possible to priorize the SCAN function within the VRF network (activated by default). In addition, to short the
time that the scanning may take, the integrator can define the range for the refrigerant system in advance.
By pressing Scan button, Fujitsu X1X2 bus will be scanned for available units. Error window will appear if there is a
problem in the connection with X1X2 bus (units not powered, bus not connected, …).
A progress bar will appear during the scan. After scan is complected, detected units will be shown in units newly
detected.
Select the units to add (or replace) in installation, according to selection Replace Units / Add Units.
After units to be integrated are selected, click button Apply, and changes will appear in previous Units
Configuration window.
4.2.6. Signals
All available Modbus registers, its corresponding description and other main parmaters are listed in the signals tab.
Figure 4.2.6.7 Intesis MAPS Signals tab

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
18 / 25
4.2.7. Sending the configuration to Intesis
When the configuration is finished, follow the next steps.
1.- Save the project (Menu option Project->Save) on your hard disk (more information in Intesis MAPS User
Manual).
2.- Go to tab ‘Receive / Send’ of MAPS, and in Send section, press Send button. Intesis will reboot
automatically once the new configuration is loaded.
Figure 4.2.7.8 Intesis MAPS Receive/Send tab
After any configuration change, do not forget to send the configuration file to the Intesis using the
Send button in the Receive / Send section.
4.2.8. Diagnostic
To help integrators in the commissioning tasks and troubleshooting, the Configuration Tool offers some specific
tools and viewers.
To start using the diagnostic tools, connection with the Gateway is required. The Diagnostic section is composed
by two main parts: Tools and Viewers.
•Tools
Use the tools section to check the current hardware status of the box, log communications into
compressed files to be sent to the support, change the Diagnostic panels’ view or send commands
to the gateway.
•Viewers
In order to check the current status, viewer for the Internal and External protocols are available. It
is also available a generic Console viewer for general information about communications and the
gateway status and finally a Signals Viewer to simulate the BMS behavior or to check the current
values in the system.
Figure 4.2.8.9 Diagnostic

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
19 / 25
More information about the Diagnostic section can be found in the Configuraion Tool manual.
4.2.9. Set-up procedure
See connection details of the gateway in 3CONNECTIONS.
1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by
the Installation wizard.
2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface
(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
3. If using Modbus RTU, connect the communication cable coming from the EIA485 port of the Modbus RTU
installation to the port marked as Port B of Intesis.
If using, Modbus TCP, connect the communication cable coming from the Ethernet port of the Modbus TCP
installation to the port marked as Ethernet Port of Intesis.
4. Connect the communication cable coming from the Fujitsu VRF installation to the port marked as Port A of
Intesis.
5. Power up Intesis. The supply voltage can be 9 to 36 Vdc or 24 VAC. Take care of the polarity of the supply
voltage applied.
WARNING! To avoid earth loops that can damage Intesis and/or any other equipment connected to it, we
strongly recommend:
•The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a
DC power supply with the positive terminal connected to earth.
•The use of AC power supplies only if they are floating and not powering any other device.
6. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as Ethernet
of Intesis.
If you want to connect using USB, connect the USB cable from the laptop PC to the port marked as Console of
Intesis.
7. Open Intesis MAPS, create a new project selecting a copy of the one named INMBSFGL016O000.
8. Modify the configuration as desired, save it and download the configuration file to Intesis as explained above.
9. Visit the Diagnostic section, enable COMMS () and check that there is communication activity, some TX frames
and some other RX frames. This means that the communication with the Centralized Controller and Modbus
Master devices is OK. In case there is no communication activity between Intesis and the Centralized Controller
and/or Modbus devices, check that those are operative: check the baud rate, the communication cable used to
connect all devices and any other communication parameter.

IntesisTM Modbus Server –FUJITSU VRF User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
20 / 25
Figure 4.2.9.10 Enable COMMS
This manual suits for next models
1
Table of contents
Other HMS Server manuals