FIGURE 3.
NFPA STYLE B WIRING DIAGRAM
TB1 TB2
EB
DCP-CZM
24V-
24V+
SC
S
OUT-
IN+
OUT+
IN-
JP2
TB2
FIGURE 3.
S
SC
24V+
24V-
EB
IN-
OUT+
IN+
OUT-
SER. NO. 210300001
DCP-CZM
SC
24- 24V+
STB1
JP2
DETECTORS
MAX. 25 CONVENTIONAL
DETECTORS
MAX. 25 CONVENTIONAL
PART# 1700-10170
(PG 2 OF 2, 05/17)
HA-06-101
DWG. #
CLASS A
CLASS B
1-2: CLASS B
HA's Sales department for proper procedure for claims and return of merchandise. This warranty is in lieu of all other warranties
specifications in any way. HA will not be responsible for any dismantling, reassembling or re-installation charges. Please contact
abused, improperly installed, altered or otherwise misused or damaged or exposed to conditions outside the products
delivery. All warranties are void and HA is not obligated to repair or replace equipment which has been repaired by others,
and to be free from defects in materials and workmanship under normal use and service for a period of one (1) year from date of
Hochiki America (HA) warrants its digital communication modules to be in conformance with it's own plans and specifications
expressed or implied.
One Year Limited Warranty
EXPLODED VIEW
EXPLODED VIEW
NOTE: ENSURE JUMPER IS IN CORRECT POSITION
FOR WIRING CONFIGURATION. (POSITION 3-4)
FOR WIRING CONFIGURATION. (POSITION 1-2)
NOTE: ENSURE JUMPER IS IN CORRECT POSITION
3-4: CLASS A
NEXT DEVICE
NEXT DEVICE
24- 24V+
+
SC
S
-
SCS
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
S
COMPATIBLE
FIRE CONTROL
PANEL
SC
U.L. LISTED
NFPA STYLE D WIRING DIAGRAM
OPTIONAL BRANCH CIRCUIT TO
NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
OPTIONAL BRANCH CIRCUIT TO
NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
ALL WIRING IS SUPERVISED AND POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
TB1/TB2 ARE SUPERVISED AND POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
SECURITY DEVICES OR LINE TYPE HEAT CABLES ON
THE SAME MODULE.
-
+
0400-03190
PART NUMBER
E.O.L. DEVICE 4.7K
HOCHIKI AMERICA CORP.
E.O.L. DEVICE 4.7K
0400-03190
PART NUMBER
INSTALL ONLY DETECTORS LISTED AS UL
COMPATIBLE WITH THE CONVENTIONAL ZONE
MODULE (CZM) AS REFERENCED IN THE CHART
BELOW.
Hochiki America Corporation
Hochiki America Corporation
MODULE
CONVENTIONAL ZONE
NOTE: Only the same size wire
from 12 to 22 AWG may be
connected terminal block TB1
when more than one conductor is
being connected under each
terminal. Maximum of 2 conductor
per terminal.
Detector Model
SLR-835BH-2/-2W
DCD-135/-190
Detector
Identifier
Detector Type
HD-6
HD-3 Heat Fixed Temp/Rate of Rise
Base
w/thermal (baseless)
Photoelectric (8-35V)
Base Model
Detectors
Max
N/A
HB-5
N/A 25
25
SLR-835B-2/-2W HD-6 Photoelectric (8-35V) (baseless) N/A N/A 25
NS4-224, NS6-224
HD-3SLR-24H Photoelectric w/heat NS4/NS6-220/-224 HB-3/HB-5 25
SLR-24V Photoelectric
SLR-835/-835W HD-3 Photoelectric (8-35V) NS4/NS6-220/-220W/-224/-224W 25
Indetifier
SLR-835H/-835HW HD-5 Photoelectric (8-35V)
w/thermal NS4/NS6-224/-224W/-220/-220W 25
SLV-24/-24N/-24V HD-3 Photoelectric NS4-224, NS6-224 HB-5 25
NS4-224W, NS6-224W
UL LISTED 1481
24VDC
REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.
UL LISTED 1481
24VDC
REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.
DCD-135/-190 HD-3 Heat Fixed Temp/Rate of Rise HB-3 25
NS4-220, NS6-220
SLV-24/-24N/-24V HD-3 Photoelectric NS4-220, NS6-220 HB-3 25
NS4-220W, NS6-220W
For Dry Indoor Use Only
For Proper Mounting/Installation See
HA-06-101 05/17
Compatibility Identifier: A
POWER LIMITED
SER. NO. 210300001
For Dry Indoor Use Only
For Proper Mounting/Installation See
HA-06-101 05/17
Compatibility Identifier: A
POWER LIMITED
MODULE
CONVENTIONAL ZONE
Compatible Linear Heat Detection Cable for use with the CZM:
Proline Protection Systems TH 105
Proline Protection Systems TH 68 Fixed Temp. line type heat detector cable 155 F (68 C) 8,000ft. (2,438m)
Proline Protection Systems TH 88
Manufacturer Model Description Maximum Lenght
Fixed Temp. line type heat detector cable 190 F (88 C)
Fixed Temp. line type heat detector cable 221 F (105 C)
8,000ft. (2,438m)
8,000ft. (2,438m)
INSTALLATION WIRING SHALL NOT EXCEED 50
OHMS (12-22 AWG) WHEN USING CONVENTIONAL
DETECTORS
Compatible Two Wire Detectors for use with the CZM with zone identifier A:
SEE UL CERTIFICATE FOR COMPLETE LIST
HD-3 Photoelectric (8-35V) 25
SOC-24V/-24VN
/-24VW
NS4/NS6-100,NS4/NS6-220/-221/-224,
HSC-220R/-224R
HD-3 NS4/NS6-220/-224 HB-3/HB-5 25
HB-3/HB-5
HB-3/HB-5
HB-55/HB-3/HB-4
/HB-5/HB-72/HB-73